Plan Review Notes For Permit 14120454 |
Permit Number |
14120454 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-01-13 16:31:42 | PLAN REVIEW COMMENTS | | | | 1ST REVIEW: FBC 2010 | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | MECHANICAL DENIED | | | | 1) THE 2ND FLOOR MECHANICAL PLAN DOES NOT MATCH THE | | ARCHITECTURAL PLANS. FBC 107.2.1 | | | | 2) THERE IS NO RETURN SHOWN FOR THE MASTER BEDROOM | | SUITE ON THE FIRST FLOOR. FBC R1602.4 | | | | 3) THE WINDSPEED IS INCORRECTLY SPECIFIED AS 140 MPH ON | | SHEET M-1. FBC-R 301.2.1 | | | | 4) THERE ARE SEVERAL ERRORS ON THE ENERGY CALCULATION | | FORM. BASED ON THE PLANS SUBMITTED, THIS IS A SINGLE | | FAMILY DWELLING. THERE ARE NO COMMON WALLS. THE | | OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY CALC. FORM. | | TWO SETS OF ENERGY CALCULATIONS AND EQUIPMENT SIZING | | CALCULATIONS ARE REQUIRED. FBC ENERGY CONSERVATION, FBC | | 107.1 AND FBC 107.2.1 | | | | | | |
|