2015-01-13 16:31:42PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 MECHANICAL DENIED
  
 1) THE 2ND FLOOR MECHANICAL PLAN DOES NOT MATCH THE
 ARCHITECTURAL PLANS. FBC 107.2.1
  
 2) THERE IS NO RETURN SHOWN FOR THE MASTER BEDROOM
 SUITE ON THE FIRST FLOOR. FBC R1602.4
  
 3) THE WINDSPEED IS INCORRECTLY SPECIFIED AS 140 MPH ON
 SHEET M-1. FBC-R 301.2.1
  
 4) THERE ARE SEVERAL ERRORS ON THE ENERGY CALCULATION
 FORM. BASED ON THE PLANS SUBMITTED, THIS IS A SINGLE
 FAMILY DWELLING. THERE ARE NO COMMON WALLS. THE
 OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY CALC. FORM.
 TWO SETS OF ENERGY CALCULATIONS AND EQUIPMENT SIZING
 CALCULATIONS ARE REQUIRED. FBC ENERGY CONSERVATION, FBC
 107.1 AND FBC 107.2.1
  
  
  