Plan Review Notes
Plan Review Notes For Permit 14120431
Permit Number 14120431
Review Stop M
Sequence Number 4
Notes
Date Text
2015-06-12 12:56:29MECHANICAL PROVIOS:
  
 1) SHEET M1.02 & M4.00: REVISION REQUIRED TO PROVIDE
 VENTILATION CALCULATIONS FOR THE CORRIDOR AND ELEVATOR
 LOBBY ON THE SOUTH END OF THE BUILDING, AND SHOW A
 MEANS OF VENTILATION ON THE PLAN.- TABLE 403..3 FMC-10
 2) M4.01: REVISION REQUIRED TO PROVIDE A VESTIBULE FOR
 THE MAINTENANCE ROOM PER SECTION 305.3.2 FBC-10 FUEL
 GAS, OR SUBMIT SPECS FOR THE HEATER SHOWING COMPLIANCE
 WITH SECTION 305.3.2 (EXCEPTION) FBC-10 FUEL GAS.
 3) M4.01: THE L1 INTAKE OPENING, AND THE COMBUSTION AIR
 INTAKE FOR THE POOL HEATER MUST BE RELOCATED A MINIMUM
 10' AWAY FROM THE PARKING AREA PER SECTION 401.4.1
 FMC-10 MECH.
 4) M4.02: THE DUCT SMOKE DETECTORS SHALL BE CONNECTED
 TO THE FIRE ALARM SYSTEM- SECTIONS 606.4 AND 606.4.1
 FMC-10 MECH: PLEASE PROVIDE THE CORRECT NUMBER LABELS
 ON THE SHAFT DETAIL FOR RTU'S 2,3, & 4.
 6) AC LOAD CALCULATIONS REVISONS: A) SUBMIT CALCS FOR
 RTU #1-5. B) THE FITNESS CENTER IS CALCULATED AT
 APPROXIMATELY 3-TON COOLING, HOWEVER THE EQUIPMENT
 SCHEDULE IS INDICATING A 5-TON SYSTEM- SHEET M1.02.
 7) ENERGY CALCULATION REVISIONSS: A) AHU-6 IS LISTED AT
 34.4 BTUH IN THE CALCS AND 57.5 IN THE SCHEDULE. B)
 AHU-4 IS LISTED AS 57.5 IN THE CALCS AND 23.4 IN THE
 SCHEDULE. C) AHU-4A NOT IN THE CALCS.
  
 CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  