2015-05-13 14:16:21 | 312 23RD STREET | | PERMIT #14120431 | | REVIEW COMMENTS - FIRE DEPARTMENT | | NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY | | REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE | | (2009 EDITION WITH FLORIDA AMENDMENTS.) | | | | RESPONSE COMMENT: THE VERTICAL STANDPIPE NEEDS TO BE | | PROTECTED IN A RATED ENCLOSURE EQUAL TO THE STAIR | | ENCLOSURE PROTECTION. SIMPLY PROTECTING THE FLOOR | | PENETRATIONS IS NOT THE EQUIVALENT. | | REPEAT COMMENT: VERTICAL STANDPIPE RISERS SUPPLYING THE | | FIRE DEPARTMENT VALVES ARE REQUIRED TO BE LOCATED IN A | | 2-HOUR FIRE BARRIER/SHAFT PER NFPA 14 SECTION 6.1.2.2. | | | | DISCLAIMER: FBC SECTION 105.4.1 PERMIT INTENT: A PERMIT | | ISSUED SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED | | WITH THE WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL, | | ALTER OR SET ASIDE ANY OF THE PROVISIONS OF THE | | TECHNICAL CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT | | THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A | | CORRECTION OF ERRORS IN PLANS, CONSTRUCTION OR | | VIOLATIONS OF THIS CODE. | | | | WESLEY JOLIN | | ASSISTANT FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 805-6730 |
|