Plan Review Notes
Plan Review Notes For Permit 14120431
Permit Number 14120431
Review Stop B
Sequence Number 3
Notes
Date Text
2015-06-04 09:54:49BUILDING PLAN REVIEW
 W. P. B. PERMIT: 14120431
 ADD: 312 23RD ST.
 PCN:74-43-43-10-19-003-0143
 CONT: PETROCCHI CONSTRUCTION
 TEL: (305)495-3745
 E-MAI: [email protected]
  
 PARK PALM BEACH MULTIFAMILY RESIDENTIAL
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
 3RD REVIEW
 DATE: FRI. MAY 29TH/ 2015
 ACTION: DENIED
 NOTICE: ART IN PUBLIC PLACES
 THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES
 ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR
 NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT
 APPLICATION WAS SUBMITTED AFTER 7/1/14, AND THE TOTAL
 PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $500,000. PER CITY OF WEST PALM BEACH ORDINANCE NO.
 4504-14, AND CITY OF WEST PALM BEACH CODE OF
 ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION
 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS
 1% OF THE TOTAL PROJECT CONSTRUCTION COST.
  
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS
  
 1) COMPLIED.
 2) THIS PROJECT IS FOR A 4 STORY BUILDING THAT
 QUALIFIES AS A THRESHOLD BUILDING. FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT.
 IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
 2A) 2ND. COMPLIED, WRITTEN INSPECTION PLAN.
 2B)SEMI- COMPLIED. THE SPECIAL INSPECTION FORMS WERE
 PARTIALLY FILLED OUT AND SIGNED , THE CONTRACTOR PAGE #
 5 HAS NOT BEEN FILLED OUT.
  
 2C) COMPLIED REQUEST. SPECIAL INSPECTOR RESUME' .
 2D) 3RD REQUEST. RESPONSE, OWNER WILL SUBMIT. THE
 CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY FOR
 THIS TYPE OF CONSTRUCTION. THIS MAY BE SUBMITTED TO KEN
 CONRAD BY E-MAIL. KEN CONRAD: [email protected]
 2E) NOTE NO ACTION IS REQUIRED, WE ARE E-MAILING YOU
 THE THRESHOLD INSPECTOR DOCUMENTS AND FORMS TO THIS
 E-MAIL ADDRESS; E-MAIL: [email protected]
 JAN. 20/2015
 2F) NOTICE: THIS IS A DIGITAL PLAN, AFTER PERMIT
 ISSUANCE, THE PERMIT LIBRARIAN WILL E-MAIL YOU, THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS.
 2G) NOTICE TO THRESHOLD INSPECTOR & CONTRACTOR. PLEASE
 CALL THE CITY OF WEST PALM BEACH?S AUTOMATED TELEPHONE
 INSPECTIONS LINE (561) 805-6700) FOR IN-PROGRESS
 INSPECTIONS FOR AUDITING OF JOBSITE INSPECTIONS.
 2H) NOTICE: REQUEST. RESPONSE INFORMATIONAL ONLY,
 PLEASE INCORPORATE INTO THE PLANS UNDER FIRE STOPPING
 PENETRATIONS. 109.3.6 THRESHOLD BUILDINGS, OPERATING
 GUIDELINES FOR THRESHOLD INSPECTORS #26. ASSURE THAT
 THE DESIGNER HAS REQUIRED ON THE PLANS OR
 SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING
 PENETRATIONS, FOR WALLS AND CEILINGS.
 3) MISSING THE REVISED COST CALCULATION SHEET.
 RESPONSE SEE RESPONSE FROM OWNER AND CONTRACTOR, WHERE.
 THE PERMIT VALUATION OF $8,500,000.00 IS LOW COMPARED
 TO THE CALCULATED VALUE FROM THE ICC BUILDING VALUATION
 DATA AUGUST 2014 USING THESE TABLES THE CALCULATED
 VALUE OF $9,855,203.00. PLEASE NOTE ANY SUB-PERMIT THAT
 TAKES SEPARATE FEES AND REVIEWS PLEASE LIST PERMITS AND
 VALUES, THESE WILL BE DEDUCTED FROM THE PRIME VALUE.
 ANY PERMITS AND VALUES NOT INCLUDED IN THIS LIST WILL
 REQUIRE SEPARATE FEES & REVIEWS.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 108.3* BUILDING PERMIT
 VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
 4) COMPLIED. SOILS REPORT.
  
 5)COMPLIED. PAGE 003/ A-1.00 CODE SUMMARY SHEET:
  
  
  
 6-18) COMPLIED. PROVISO: DEFERRED SUBMITTAL. CONTRACTOR
 SHALL SUBMIT FLOOR INSULATION IN ACCORDANCE WITH:
 FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND. FLOOR/CEILING
 ASSEMBLIES BETWEEN DWELLING UNITS OR BETWEEN A DWELLING
 UNIT AND A PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE
 SHALL HAVE AN IMPACT INSULATION CLASS (IIC) RATING OF
 NOT LESS THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN
 ACCORDANCE WITH ASTM E 492.
  
 FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
  
 19) COMPLIED. GUARD RAIL & ATTACHMENT
  
 20-22) COMPLIED
  
 23) BUILDING PROVISO: DEFERRED SUBMITTALS. 107.3.4.2
 CELCORE LIGHTWEIGHT INSULATING CONCRETE NOA 13-0307.02
 CIRCLE THE SUB-SYSTEM THAT IS TO BE USED ON THIS
 PROJECT AND THE ASSOCIATED PRESSURES. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED. 107.2.1.2 FOR ROOF
 ASSEMBLIES REQUIRED BY THE CODE, THE CONSTRUCTION
 DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND DELINEATE THE
 TYPE OF ROOFING SYSTEM, MATERIALS, FASTENING
 REQUIREMENTS, FLASHING REQUIREMENTS AND WIND RESISTANCE
 RATING THAT ARE REQUIRED TO BE INSTALLED. PRODUCT
 EVALUATION AND INSTALLATION SHALL INDICATE COMPLIANCE
 WITH THE WIND CRITERIA REQUIRED FOR THE SPECIFIC SITE
 OR A STATEMENT BY AN ARCHITECT OR ENGINEER FOR THE
 SPECIFIC SITE MUST BE SUBMITTED WITH THE CONSTRUCTION
 DOCUMENTS.
  
 24-27)BUILDING PROVISO: DEFERRED SUBMITTALS. 107.3.4.2
 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS SECTION,
 DEFERRED SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF
 THE DESIGN THAT ARE NOT SUBMITTED AT THE TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL
 OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF
 THE BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR
 REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  