2015-03-28 04:57:39 | 1) SHT.A1.00 - THERE IS STILL A CONFLICT WITH THE |
| ACCESSIBILITY NOTES. THE PLAN STILL STATES"ALL GROUND |
| FLOOR UNITS TO BE ADAPTABLE UNITS." DELETE THIS NOTE |
| AND ANY REFERENCE TO CHAPTER 11 AS ALL THE UNITS MUST |
| BE ADAPTABLE PER THE FHA. REFER TO PREVIOUS PLAN REVIEW |
| COMMENT DATED 12/10/14. |
| 2) SHT.A1.04 - THERE IS STILL A REFERENCE TO A 2007 |
| CODE FOR HOUSING ACCESSIBILITY. CLARIFY. |
| 3) SHT. A1.04 - GRAB BAR REINFORCING LOCATIONS - THE |
| HEIGHT OF THE BACKING FOR THE SHOWER BACK AND SIDE |
| WALLS - THE HEIGHT OF THE BACKING SHALL BE 32 INCHES |
| MAXIMUM TO THE BOTTOM OF THE BACKING WITH A 6 INCH |
| MAXIMUM WIDTH FOR THE SUPPORT WHICH WOULD BE A MINIMUM |
| OF 38 INCHES TO THE TOP OF THE BACKING. THE DETAIL |
| SHOWS 38 INCHES MINIMUM TO THE BOTTOM. |
| 4) SHT. A 4.11 - SHOWS THE POOL HEATER WITH AN 8" X 8" |
| EXHAUST AND REFERS TO MEP DWGS. THERE IS NO DETAIL FOR |
| THIS EXHAUST. SUBMIT A SECTION DETAIL FOR THE POOL |
| HEATER EXHAUST SHOWING THE HEIGHT ABOVE THE ROOF, THE |
| TYPE OF VENT, LOCATION ON THE ROOF, VENT MATERIAL & |
| LOCATION IN RELATION TO BUILDING OPENINGS. COMPLY WITH |
| THE 201 FLORIDA FUEL GAS CODE SECS. 502, 503. |
| 5) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE POOL |
| HEATER. COMPLY WITH 2010 FGC SEC.304. |
| 6) SHT. P1.00 - NOTE 1.9 READS "ALL GAS PIPING TO BE |
| SCH. 40 W/SCREWED FITTINGS & SHT. P4.06 NOTES WELDED |
| PIPE. CLARIFY. |
| 7) SHT. P1.01 - PLUMBING EQUIPMENT SCHEDULE FOR |
| APARTMENTS SHOWS THE MINIMUM EF FOR WATER HEATERS IN |
| APARTMENTS TO BE .93 BUT TABLE 504.2 OF THE 2010 FL. |
| ENERGY CODE APPEARS TO REQUIRE A MIN. OF .97. |
| 8) SHT. P1.01 - PLUMBING FIXTURE SCHEDULE FOR |
| APARTMENTS AND THE COMMON AREAS NOTES THE MINIMUM SIZE |
| TRAP FOR KITCHEN SINKS AND SINKS S-1 & S-2 AS 1 1/4". |
| THE MINIMUM SIZE TRAP SHALL BE 1 1/2 " PER TABLE 709.1 |
| OF THE 2010 FPC. |
| 9) DWELLING UNIT SHEETS P3.00-3.05 - THE WATER LINE |
| DIRECTLY SUPPLYING THE WATER HEATER SHALL BE EQUIPPED |
| WITH A FULL OPEN VALE PER THE 2010 FPC SEC. 606.1 (8). |
| THIS IS IN ADDITIONAL TO THE SHUTOFF VALVE AT THE |
| SUB-METER. |
| 10) SHTS. P4.00 & P4.01 - SUPLLY MATCH LINES ON THE |
| PLANS. IT IS DIFFICULT TO DETERMINE WHERE THE PIPNG |
| STARTS AND BEGINS FROM ONE PAGE TO THE NEXT. WPB AMEND. |
| TO 2010 FBC SEC. 107.2.1. |
| 11) SHT. P4.01 - SUBMIT A GAS PIPING RISER FOR THE GAS |
| LINE TO THE POOL HEATER. SUBMIT MANUF. SPECIFICATIONS |
| FOR THE POOL HEATER. THE POOL HEATER SHALL BE LISTED |
| AND LABELED PER THE 2010 FL. FUEL GAS CODE SEC. |
| 301.3.SHOW THE PSI OF THE GAS SYSTEM, THE TYPE OF PIPE |
| MATERIAL, THE TOTAL DISTANCE FROM THE GAS METER TO THE |
| POOL HEATER, THE LENGTH DIMENSIONS OF ALL SECTIONS OF |
| PIPE, AND THE LOCATION OF ALL PRESSURE REGULATORS. |
| REGULATORS LOCATED OUTDOORS SHALL BE APPROVED FOR |
| OUTDOOR INSTALLATION. 2010 FGC SEC.410.1. |
| 12) SHT. P4.01 - CLEARLY SHOW THE LOCATION OF THE POOL |
| HEATER ON THE PLANS. THE POLL HEATER SHALL COMPLY W/ |
| THE 2010 FGC SEC.305.3.2. |
| 13) SHT. P4.02 & 4.03 - PROVIDE A MATCH LINE ON THE |
| DRAWINGS FOR THE UNDERGROUND SANITARY COLLECTION |
| SYSTEM. IT IS DIFFICULT TO DETERMINE WHERE THE PLUMBING |
| SYSTEM CONTINUES FROM ONE SHEET TO THE NEXT. WPB AMEND. |
| TO 2010 FBC SEC. 107.2.1. |
| 14)SHT.P4.03 - THE LAYOUT OF THE UNDERGROUND SANITARY |
| COLLECTION SYSTEM ON THE PLAN VIEW DOES NOT CORRELATE |
| WITH THE SANITARY RISER DIAGRAM ON P4.09 IN SEVERAL |
| AREAS.ONE AREA IS THE LINE RUNNING TOWARDS THE MAIL |
| CENTER & ELEVATOR #1. CHECK ALL SECTIONS OF THE PLAN |
| VIEW & THE RISER DIAGRAM TO ENSURE THEY CORRELATE WITH |
| EACH OTHER. WPB AMEND. TO 2010 FBC SEC. 107.2.1 |
| 15) SHT. P4.06 & 4.07 - PROVIDE MATCH LINES ON THE |
| PLANS. IT IS DIFFICULT TO DETERMINE WHERE THE PLUMBING |
| SYSTEM CONTINUES FROM ONE SHEET TO THE NEXT. WPB AMEND. |
| TO 2010 FBC SEC. 107.2.1. |
| 16) P4.00 - PROVIDE A SANITARY RISER DIAGRAM FOR THE |
| SANITARY PIPING FOR THE SECOND FLOOR PLUMBING TO |
| CORRELATE WITH SHT. P4.09 AND CLEARLY IDENTIFY THE |
| RISERS ON SHT. P4.09 BY THE APPLICABLE RISER NUMBER. |
| CURRENTLY THERE ARE ONLY NOTE REFERENCE NUMBERS ON THE |
| RISERS WHICH IS CONFUSING AND UNCLEAR AS TO WHERE THE |
| RISERS CONNECT.WPB AMEND. TO 2010 FBC SEC. 107.3.5.1.3. |
| 17) SHT. P4.06 - INDICATE THE SPECIFIC STRUCTURAL |
| DRAWING NUMBERA FOR THE LOCATION OF THE GAS MAIN STAND |
| & GAS MAIN PIPE STAND ANCHORING. THE STANDS SHALL BE |
| DESIGNED FOR A 170 MPH WIND LOAD AS REQD. PER THE 2010 |
| FBC SEC.1609. |
| 18) SHTS. P 4.06 & P4.07- IDENTIFY THE GAS METERS ON |
| THE ROOF. ONE GROUP CAN BE IDENTIFIED AND LABELED |
| "TYPICAL". AS DRAWN, THE GAS PIPING APPEARS TO ALSO |
| CONNECT TO SOME OF THE CONDENSING UNITS .CLARIFY. WPB |
| AMEND. TO 2010 FBC SEC. 107.2.1. |
| 19) SUBMIT A TYPICAL DETAIL OF THE PIPNG FROM THE METER |
| TO THE PIPE CHASE AND THE SUPPORT DETAIL FOR THIS |
| PIPING.WPB AMEND. TO 2010 FBC SEC. 107.2.1. |
| 20) PLEASE SUBMIT DOCUMENTATION FROM THE GAS PURVEYOR |
| APPROVING THE LOCATION OF THE METERS ON THE ROOF. WPB |
| AMEND. TO 2010 FBC SEC.107.2.1. |
| 21) MULTIPLE METER INSTALLATIONS SHALL BE MARKED FOR |
| IDENTIFICATION PURPOSES PER THE 2010 FGC SEC.401.7. |
| 22) GAS PIPING SHALL BE IDENTIFIED PER THE 201 FGC |
| SEC.401.5. |
| 23) SUPPLY A WATER PIPING DETAIL FOR THE WATER MAIN |
| CONNECTION TO THE DOMESTIC WATER PUMP..WPB AMEND. TO |
| 2010 FBC SEC. 107.2.1. |
| 24) SHT. P4.09 - INDICATE THE DRAINAGE FIXTURE UNIT |
| LOAD AT THE DIFFERENT SECTIONS OF THE UNDERGROUND |
| SANITARY COLLECTION SYSTEM TO ENSURE COMPLIANCE WITH |
| TABLE 710.1 (1) OF THE 2010 FPC. |
| 25) SHT. C2 - THE WATER MATER MAIN APPEARS TO ENTER THE |
| PUMP ROOM THROUGH STAIRWELL # 2. CLARIFY. COMPLY WITH |
| 2010 FBC SEC.1022.4. |
| 26) SHT. C3 - INDICATE THE SQUARE FOOTAGE OF ROOF |
| DRAINAGE COLLECTED BY EACH UNDERGROUND STORM DRAIN TO |
| ENSURE COMPLIANCE WITH FPC TABLE 1106.3. |
| 27) CARBON MONOXIDE DETECTORS ARE REQUIRED IN AREAS AS |
| MANDATED BY 2010 FBC SEC. 916 DUE TO THE LOCATION OF |
| THE GAS POOL HEATER. |
| 28) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE GAS |
| RANGE AND GAS DRYER.2010 FGC SEC.304.1. |
| 29) ROOF PLANP4.06 SHOWS THE GAS MAIN STANCIONS AND |
| ATTACHMENTS TO THE A/C CONDENSER STAND. SHOW THE HEIGHT |
| TO THE TOP OF THE GAS MAIN FROM THE FINISH ROOF. ACCESS |
| TO EQUIPMENT (METERS) SHALL NOT REQUIRE CLIMBING OVER |
| OBSTRUCTIONS GREATER THAN 30 INCHES HIGH. 2010 FGC |
| SEC.306.5. |
| 30) SHT. P1.01 - WATER HEATER DETAIL - REFERS TO |
| PLASTIC HEATER PAN. COMBUSTIBLE MATERIAL IS NOT |
| PERMITTED WITHIN A RETURN AIR PLENUM PER THE FLORIDA |
| MECHANICAL CODE SEC.602.2.1. |
| |
| PLUMBING PLAN REVIEW |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |