Plan Review Notes
Plan Review Notes For Permit 14120431
Permit Number 14120431
Review Stop P
Sequence Number 2
Notes
Date Text
2015-03-28 04:57:391) SHT.A1.00 - THERE IS STILL A CONFLICT WITH THE
 ACCESSIBILITY NOTES. THE PLAN STILL STATES"ALL GROUND
 FLOOR UNITS TO BE ADAPTABLE UNITS." DELETE THIS NOTE
 AND ANY REFERENCE TO CHAPTER 11 AS ALL THE UNITS MUST
 BE ADAPTABLE PER THE FHA. REFER TO PREVIOUS PLAN REVIEW
 COMMENT DATED 12/10/14.
 2) SHT.A1.04 - THERE IS STILL A REFERENCE TO A 2007
 CODE FOR HOUSING ACCESSIBILITY. CLARIFY.
 3) SHT. A1.04 - GRAB BAR REINFORCING LOCATIONS - THE
 HEIGHT OF THE BACKING FOR THE SHOWER BACK AND SIDE
 WALLS - THE HEIGHT OF THE BACKING SHALL BE 32 INCHES
 MAXIMUM TO THE BOTTOM OF THE BACKING WITH A 6 INCH
 MAXIMUM WIDTH FOR THE SUPPORT WHICH WOULD BE A MINIMUM
 OF 38 INCHES TO THE TOP OF THE BACKING. THE DETAIL
 SHOWS 38 INCHES MINIMUM TO THE BOTTOM.
 4) SHT. A 4.11 - SHOWS THE POOL HEATER WITH AN 8" X 8"
 EXHAUST AND REFERS TO MEP DWGS. THERE IS NO DETAIL FOR
 THIS EXHAUST. SUBMIT A SECTION DETAIL FOR THE POOL
 HEATER EXHAUST SHOWING THE HEIGHT ABOVE THE ROOF, THE
 TYPE OF VENT, LOCATION ON THE ROOF, VENT MATERIAL &
 LOCATION IN RELATION TO BUILDING OPENINGS. COMPLY WITH
 THE 201 FLORIDA FUEL GAS CODE SECS. 502, 503.
 5) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE POOL
 HEATER. COMPLY WITH 2010 FGC SEC.304.
 6) SHT. P1.00 - NOTE 1.9 READS "ALL GAS PIPING TO BE
 SCH. 40 W/SCREWED FITTINGS & SHT. P4.06 NOTES WELDED
 PIPE. CLARIFY.
 7) SHT. P1.01 - PLUMBING EQUIPMENT SCHEDULE FOR
 APARTMENTS SHOWS THE MINIMUM EF FOR WATER HEATERS IN
 APARTMENTS TO BE .93 BUT TABLE 504.2 OF THE 2010 FL.
 ENERGY CODE APPEARS TO REQUIRE A MIN. OF .97.
 8) SHT. P1.01 - PLUMBING FIXTURE SCHEDULE FOR
 APARTMENTS AND THE COMMON AREAS NOTES THE MINIMUM SIZE
 TRAP FOR KITCHEN SINKS AND SINKS S-1 & S-2 AS 1 1/4".
 THE MINIMUM SIZE TRAP SHALL BE 1 1/2 " PER TABLE 709.1
 OF THE 2010 FPC.
 9) DWELLING UNIT SHEETS P3.00-3.05 - THE WATER LINE
 DIRECTLY SUPPLYING THE WATER HEATER SHALL BE EQUIPPED
 WITH A FULL OPEN VALE PER THE 2010 FPC SEC. 606.1 (8).
 THIS IS IN ADDITIONAL TO THE SHUTOFF VALVE AT THE
 SUB-METER.
 10) SHTS. P4.00 & P4.01 - SUPLLY MATCH LINES ON THE
 PLANS. IT IS DIFFICULT TO DETERMINE WHERE THE PIPNG
 STARTS AND BEGINS FROM ONE PAGE TO THE NEXT. WPB AMEND.
 TO 2010 FBC SEC. 107.2.1.
 11) SHT. P4.01 - SUBMIT A GAS PIPING RISER FOR THE GAS
 LINE TO THE POOL HEATER. SUBMIT MANUF. SPECIFICATIONS
 FOR THE POOL HEATER. THE POOL HEATER SHALL BE LISTED
 AND LABELED PER THE 2010 FL. FUEL GAS CODE SEC.
 301.3.SHOW THE PSI OF THE GAS SYSTEM, THE TYPE OF PIPE
 MATERIAL, THE TOTAL DISTANCE FROM THE GAS METER TO THE
 POOL HEATER, THE LENGTH DIMENSIONS OF ALL SECTIONS OF
 PIPE, AND THE LOCATION OF ALL PRESSURE REGULATORS.
 REGULATORS LOCATED OUTDOORS SHALL BE APPROVED FOR
 OUTDOOR INSTALLATION. 2010 FGC SEC.410.1.
 12) SHT. P4.01 - CLEARLY SHOW THE LOCATION OF THE POOL
 HEATER ON THE PLANS. THE POLL HEATER SHALL COMPLY W/
 THE 2010 FGC SEC.305.3.2.
 13) SHT. P4.02 & 4.03 - PROVIDE A MATCH LINE ON THE
 DRAWINGS FOR THE UNDERGROUND SANITARY COLLECTION
 SYSTEM. IT IS DIFFICULT TO DETERMINE WHERE THE PLUMBING
 SYSTEM CONTINUES FROM ONE SHEET TO THE NEXT. WPB AMEND.
 TO 2010 FBC SEC. 107.2.1.
 14)SHT.P4.03 - THE LAYOUT OF THE UNDERGROUND SANITARY
 COLLECTION SYSTEM ON THE PLAN VIEW DOES NOT CORRELATE
 WITH THE SANITARY RISER DIAGRAM ON P4.09 IN SEVERAL
 AREAS.ONE AREA IS THE LINE RUNNING TOWARDS THE MAIL
 CENTER & ELEVATOR #1. CHECK ALL SECTIONS OF THE PLAN
 VIEW & THE RISER DIAGRAM TO ENSURE THEY CORRELATE WITH
 EACH OTHER. WPB AMEND. TO 2010 FBC SEC. 107.2.1
 15) SHT. P4.06 & 4.07 - PROVIDE MATCH LINES ON THE
 PLANS. IT IS DIFFICULT TO DETERMINE WHERE THE PLUMBING
 SYSTEM CONTINUES FROM ONE SHEET TO THE NEXT. WPB AMEND.
 TO 2010 FBC SEC. 107.2.1.
 16) P4.00 - PROVIDE A SANITARY RISER DIAGRAM FOR THE
 SANITARY PIPING FOR THE SECOND FLOOR PLUMBING TO
 CORRELATE WITH SHT. P4.09 AND CLEARLY IDENTIFY THE
 RISERS ON SHT. P4.09 BY THE APPLICABLE RISER NUMBER.
 CURRENTLY THERE ARE ONLY NOTE REFERENCE NUMBERS ON THE
 RISERS WHICH IS CONFUSING AND UNCLEAR AS TO WHERE THE
 RISERS CONNECT.WPB AMEND. TO 2010 FBC SEC. 107.3.5.1.3.
 17) SHT. P4.06 - INDICATE THE SPECIFIC STRUCTURAL
 DRAWING NUMBERA FOR THE LOCATION OF THE GAS MAIN STAND
 & GAS MAIN PIPE STAND ANCHORING. THE STANDS SHALL BE
 DESIGNED FOR A 170 MPH WIND LOAD AS REQD. PER THE 2010
 FBC SEC.1609.
 18) SHTS. P 4.06 & P4.07- IDENTIFY THE GAS METERS ON
 THE ROOF. ONE GROUP CAN BE IDENTIFIED AND LABELED
 "TYPICAL". AS DRAWN, THE GAS PIPING APPEARS TO ALSO
 CONNECT TO SOME OF THE CONDENSING UNITS .CLARIFY. WPB
 AMEND. TO 2010 FBC SEC. 107.2.1.
 19) SUBMIT A TYPICAL DETAIL OF THE PIPNG FROM THE METER
 TO THE PIPE CHASE AND THE SUPPORT DETAIL FOR THIS
 PIPING.WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 20) PLEASE SUBMIT DOCUMENTATION FROM THE GAS PURVEYOR
 APPROVING THE LOCATION OF THE METERS ON THE ROOF. WPB
 AMEND. TO 2010 FBC SEC.107.2.1.
 21) MULTIPLE METER INSTALLATIONS SHALL BE MARKED FOR
 IDENTIFICATION PURPOSES PER THE 2010 FGC SEC.401.7.
 22) GAS PIPING SHALL BE IDENTIFIED PER THE 201 FGC
 SEC.401.5.
 23) SUPPLY A WATER PIPING DETAIL FOR THE WATER MAIN
 CONNECTION TO THE DOMESTIC WATER PUMP..WPB AMEND. TO
 2010 FBC SEC. 107.2.1.
 24) SHT. P4.09 - INDICATE THE DRAINAGE FIXTURE UNIT
 LOAD AT THE DIFFERENT SECTIONS OF THE UNDERGROUND
 SANITARY COLLECTION SYSTEM TO ENSURE COMPLIANCE WITH
 TABLE 710.1 (1) OF THE 2010 FPC.
 25) SHT. C2 - THE WATER MATER MAIN APPEARS TO ENTER THE
 PUMP ROOM THROUGH STAIRWELL # 2. CLARIFY. COMPLY WITH
 2010 FBC SEC.1022.4.
 26) SHT. C3 - INDICATE THE SQUARE FOOTAGE OF ROOF
 DRAINAGE COLLECTED BY EACH UNDERGROUND STORM DRAIN TO
 ENSURE COMPLIANCE WITH FPC TABLE 1106.3.
 27) CARBON MONOXIDE DETECTORS ARE REQUIRED IN AREAS AS
 MANDATED BY 2010 FBC SEC. 916 DUE TO THE LOCATION OF
 THE GAS POOL HEATER.
 28) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE GAS
 RANGE AND GAS DRYER.2010 FGC SEC.304.1.
 29) ROOF PLANP4.06 SHOWS THE GAS MAIN STANCIONS AND
 ATTACHMENTS TO THE A/C CONDENSER STAND. SHOW THE HEIGHT
 TO THE TOP OF THE GAS MAIN FROM THE FINISH ROOF. ACCESS
 TO EQUIPMENT (METERS) SHALL NOT REQUIRE CLIMBING OVER
 OBSTRUCTIONS GREATER THAN 30 INCHES HIGH. 2010 FGC
 SEC.306.5.
 30) SHT. P1.01 - WATER HEATER DETAIL - REFERS TO
 PLASTIC HEATER PAN. COMBUSTIBLE MATERIAL IS NOT
 PERMITTED WITHIN A RETURN AIR PLENUM PER THE FLORIDA
 MECHANICAL CODE SEC.602.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  