2015-03-28 12:29:58PLAN DENIED
 1) REFER TO SECTION 503.2.5.4 SHUTOFF DAMPER
 CONTROLS.2010
 FLORIDA ENERGY CODE
 2) PROVIDE MANUFACTURE INSTALLATION INSTRUCTIONS FOR
 AIR CONDITIONING EQUIPMENT PER SECTION 304.1 2010
 FBC (M)
 3) REFER TO SECTION 606.2.2 COMMON SUPPLY AND
 RETURN AIR 2010 FBC (M)
 4) MARK RETURN AIR SIZE ON PLANS FOR BALANCED
 RETURN AIR. PER SECTION 107 FBC 2010
 5) PROVIDE MORE INFORMATION ON MULTI PURPOSE ROOM ON
 THE
 MECHANICAL PLAN. WHAT IS THE ROOM FOR ? PAGE A 411
 SHOWS
 POOL GAS HEATERS.
 6) REFER TO SECTION 602.2.1 MATERIALS WITHIN PLENUM'S
 2010 FBC (M)
 7) REFER TO SECTION 602.1 GENERAL 2010 FBC (M)
 AND DEFINITIONS UNDER FIRE AREA 902 FBC 2010
 8) REFER TO SECTION 607.3.3.3 COMBINATION FIRE
 SMOKE DAMPER 2010 FBC (M)
 9) REFER TO SECTION 306.5 EQUIPMENT AND APPLIANCES ON
 ROOFS OR ELEVATED STRUCTURES 2010 FBC (M)
 10) REFER TO SECTION 1509.7 MECHANICAL UNITS 2010 FBC
 11) REFER TO TABLE 1509.7 CLEARANCES BELOW RAISED ROOF
 MOUNTED
 MECHANICAL UNITS 2010 FBC
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676