2015-03-30 06:57:41 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 14120431 |
| ADD: 321 23RD ST. |
| PCN:74-43-43-10-19-003-0143 |
| CONT: PETROCCHI CONSTRUCTION |
| TEL: (305)495-3745 |
| E-MAI: [email protected] |
| |
| PARK PALM BEACH MULTIFAMILY RESIDENTIAL |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| 2ND REVIEW |
| DATE: SAT. 27/ 2015 |
| ACTION: DENIED |
| NOTICE: CHAPTER 553.80(2)(B) FLORIDA STATUTES STATES |
| THAT A LOCAL GOVERNMENT SHALL IMPOSE A FEE OF FOUR |
| TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE REJECTED |
| (3) OR MORE TIMES FOR REPEATED FAILURE TO CORRECT A |
| CODE VIOLATION. |
| |
| NOTICE: ART IN PUBLIC PLACES |
| THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES |
| ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR |
| NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT |
| APPLICATION WAS SUBMITTED AFTER 7/1/14, AND THE TOTAL |
| PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN |
| $500,000. PER CITY OF WEST PALM BEACH ORDINANCE NO. |
| 4504-14, AND CITY OF WEST PALM BEACH CODE OF |
| ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION |
| 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS |
| 1% OF THE TOTAL PROJECT CONSTRUCTION COST. |
| |
| PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE |
| V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND |
| NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO |
| THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE |
| PROJECTS |
| |
| 1) THE PERMIT APPLICATION LIST THE ADDRESS OF 321 23RD |
| ST./ 74-43-43-10-19-003-0143, THIS IS A SINGLE LOT, |
| THIS WILL REQUIRE MORE THAN A UNITY OF TITLE, THIS |
| PROJECT WILL REQUIRE A REPLAT WITH A NEW PCN AND |
| POSSIBLE ADDRESS CHANGE. |
| 2) THIS PROJECT IS FOR A 4 STORY BUILDING THAT |
| QUALIFIES AS A THRESHOLD BUILDING. FL S. S. 553.71(7) " |
| THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS |
| GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH |
| HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN |
| THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. |
| IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| PERSONS. |
| 2A) 2ND. REQUEST. THE RESPONSE INDICATED THE WRITTEN |
| STRUCTURAL INSPECTION PLAN WAS ATTACHED TO THE RESPONSE |
| PACKAGE. NOTE I?VE GONE THROUGH ALL OF THE RESPONSE |
| PACKAGES, ARCHITECTURAL, STRUCTURAL, AND MEP RESPONSE |
| SHEETS; THERE IS NO WRITTEN STRUCTURAL INSPECTION PLAN. |
| 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A |
| (WRITTEN/ TYPED) SPECIAL INSPECTOR TO PERFORM |
| STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING PURSUANT |
| TO A STRUCTURAL INSPECTION PLAN PREPARED BY THE |
| ENGINEER OF RECORD. THE STRUCTURAL INSPECTION PLAN MUST |
| BE SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE |
| ISSUANCE OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A |
| THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL |
| INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION |
| PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE |
| ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED |
| DOCUMENTS. |
| 2B) COMPLIED. |
| THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B. AMENDMENT |
| 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH ARE |
| REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT OR |
| ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE |
| BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE |
| PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE |
| FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| FLORIDA STATUTE. |
| |
| 2C) 2ND. REQUEST. RESPONSE, OWNER WILL SUBMIT. FOR THE |
| SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' OF |
| INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME' |
| MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED |
| HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL |
| REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, AN |
| INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| MEETING THE ABOVE CRITERIA. |
| CONTACT KEN CONRAD |
| TEL: 561-805-6666 |
| E-MAIL: [email protected] |
| D) 2ND. REQUEST. RESPONSE, OWNER WILL SUBMIT. THE |
| CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY FOR |
| THIS TYPE OF CONSTRUCTION. THIS MAY BE SUBMITTED TO KEN |
| CONRAD BY E-MAIL. KEN CONRAD: [email protected] |
| E) NOTE NO ACTION IS REQUIRED, WE ARE E-MAILING YOU THE |
| THRESHOLD INSPECTOR DOCUMENTS AND FORMS TO THIS E-MAIL |
| ADDRESS; E-MAIL: [email protected] JAN. |
| 20/2015 |
| F) NOTICE: THIS IS A DIGITAL PLAN, AFTER PERMIT |
| ISSUANCE, THE PERMIT LIBRARIAN WILL E-MAIL YOU, THE |
| APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR |
| PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN |
| COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR |
| THE MEP INSPECTORS. |
| |
| G) NOTICE TO THRESHOLD INSPECTOR & CONTRACTOR. PLEASE |
| CALL THE CITY OF WEST PALM BEACH?S AUTOMATED TELEPHONE |
| INSPECTIONS LINE (561) 805-6700) FOR IN-PROGRESS |
| INSPECTIONS FOR AUDITING OF JOBSITE INSPECTIONS. |
| H) 2ND. REQUEST. RESPONSE INFORMATIONAL ONLY, PLEASE |
| INCORPORATE INTO THE PLANS UNDER FIRE STOPPING |
| PENETRATIONS. 109.3.6 THRESHOLD BUILDINGS, OPERATING |
| GUIDELINES FOR THRESHOLD INSPECTORS #26. ASSURE THAT |
| THE DESIGNER HAS REQUIRED ON THE PLANS OR |
| SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING |
| PENETRATIONS, FOR WALLS AND CEILINGS. |
| |
| 3) RESPONSE SEE RESPONSE FROM OWNER AND CONTRACTOR, |
| WHERE. THE PERMIT VALUATION OF $8,500,000.00 IS LOW |
| COMPARED TO THE CALCULATED VALUE FROM THE ICC BUILDING |
| VALUATION DATA AUGUST 2014 USING THESE TABLES THE |
| CALCULATED VALUE OF $9,855,203.00. PLEASE NOTE ANY |
| SUB-PERMIT THAT TAKES SEPARATE FEES AND REVIEWS PLEASE |
| LIST PERMITS AND VALUES, THESE WILL BE DEDUCTED FROM |
| THE PRIME VALUE. ANY PERMITS AND VALUES NOT INCLUDED IN |
| THIS LIST WILL REQUIRE SEPARATE FEES & REVIEWS. |
| 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION 108.3* BUILDING PERMIT |
| VALUATION. |
| IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| CONGRESS. |
| 4) COMPLIED. |
| PLEASE NOTE UNDER THE FOLDER SUPPORTING DOCUMENTS, |
| MISSING WAS THE SOILS REPORT PREPARED BY ANDAMAN FILE |
| 03-2310 02/06/04. 2010 FBC-B |
| 1803.5.2 QUESTIONABLE SOIL. WHERE THE CLASSIFICATION, |
| STRENGTH OR COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR |
| WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED |
| IN THIS CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE |
| PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION |
| BE CONDUCTED. |
| 5) PAGE 003/ A-1.00 CODE SUMMARY SHEET: |
| 5A) COMPLIED.. |
| 5B) OCCUPANCY & MEANS OF EGRESS HEADING: CORRECTION, |
| MERCANTILE 3,212 GRS SF / 30 SF PER OCC.=108 FBC-B |
| TABLE 1004.1.1 |
| 5C) OCCUPANCY & MEANS OF EGRESS HEADING: CORRECTION, |
| A-2 COURTYARD/ POOL & DECK CORRECTION 13 +104= 117 |
| OCCUPANTS. TYPO |
| 5D) COMPLIED. |
| ALLOWABLE EXTERIOR OPENINGS CANNOT BE VERIFIED, THE |
| PROPERTY LINES HAVE NOT BEEN PROVIDED AND THE DISTANCE |
| AWAY FROM THE PROPERTY LINE. FBC-B TABLE 602 EXTERIOR |
| FIRE RATINGS AND TABLE 705.8 ALLOWABLE OPENINGS. |
| |
| 6) PAGE 004/ A-1.01 (NOTE K)/ 008- A-1.05 ON BOTH |
| SHEETS THERE ARE NOTES TO COMPLY WITH 1207.2 AIR-BORNE |
| SOUND AND 1207.3 STRUCTURE BORNE SOUND. IN NEITHER CASE |
| HAS TESTING REPORTS SUBMITTED PROVIDING CODE |
| COMPLIANCE. PAGE 008 HAD A NOTE OF REPORT NGC7005033 |
| BUT NOT SUBMITTED. |
| THERE ARE GOING TO BE (2) ISSUES WITH THE RESPONSE |
| ABOUT AIR-BORNE TESTING AND STRUCTURE BORNE TESTING. |
| 6A)(1) THE 1ST ISSUE IS FOR FIELD TESTING OF FLOOR |
| SYSTEMS TO ASTM E90 AND ASTM E492 (2010 FBC-B 1207.3) |
| FOR EACH FLOOR SYSTEM WITH DIFFERENT ASSEMBLIES WILL BE |
| REQUIRED. STC/ IIC 45 FIELD TESTED. |
| 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1 107.3.3 CONTRACTOR IS AT OWN RISK, NO |
| ASSURANCES THAT A CERTIFICATE OF OCCUPANCY CAN BE |
| ISSUED WITHOUT CODE COMPLIANCE. |
| 6A(2) THERE WILL BE ADDITIONAL TESTING OF AIR-BORNE |
| SOUND (2010 FBC-B 1207.2 & 1207.2.1) FOR EACH TYPE OF |
| WALL ASSEMBLY, SHALL HAVE A SOUND TRANSMISSION CLASS |
| (STC) OF NOT LESS THAN 45 WHEN FIELD TESTED. |
| 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1 107.3.3 CONTRACTOR IS AT OWN RISK, NO |
| ASSURANCES THAT A CERTIFICATE OF OCCUPANCY CAN BE |
| ISSUED WITHOUT CODE COMPLIANCE |
| 6A)(3) CONCRETE MASONRY ASSEMBLIES SHALL BE CALCULATED |
| IN ACCORDANCE WITH TMS 0302 OR DETERMINED THROUGH |
| TESTING IN ACCORDANCE WITH ASTM E 90. |
| 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1 107.3.3 CONTRACTOR IS AT OWN RISK, NO |
| ASSURANCES THAT A CERTIFICATE OF OCCUPANCY CAN BE |
| ISSUED WITHOUT CODE COMPLIANCE |
| 6B) THE SECOND ISSUE THE ABOVE TESTING DOES NOT TAKE |
| PLACE UNTIL THE UNITS ARE FINISHED AND CREDITS ARE |
| BASICALLY TAKEN INTO ACCOUNT FOR FINISHES THAT ABSORB |
| SOUND TRANSFER. THE ISSUE WILL BE COMPLIANCE WITH |
| SECTION 2010 FBC-B 719.2 CONCEALED INSULATION OF |
| INSULATING MATERIALS, SHALL HAVE A FLAME SPREAD INDEX |
| OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT |
| MORE THAN 450. BEFORE THE INSULATION IS INSTALLED IN |
| WALLS OR FLOOR DECKS OR WITHIN FLOOR ASSEMBLIES THIS |
| CODE SECTION HAS TO BE MET. |
| 6C) NEW COMMENT DEALS WITH THE ENERGY CALCULATIONS AND |
| CREDITS TAKEN FOR FLOORS, THE 2ND FLOOR RESIDENTIAL |
| UNITS WITH THE GARAGE BENEATH AS WELL AS UNITS OVER THE |
| AIR CONDITIONED SPACE TAKE CREDIT FOR 1 FT. OF SOIL |
| CONCRETE FLOORS CARPET AND RUBBER PAD. SHEET 008/A-1.05 |
| FLOOR/ WALL ASSEMBLIES DETAIL # 40 SHOWS THE FLOOR/ |
| CEILING ASSEMBLY 1ST FLOOR RESIDENTIAL /GARAGE CEILING |
| ASSEMBLY NO R-VALUE ASSIGNED TO THE ASSEMBLY THROUGH |
| THE ENERGY CALCS. NOTE THERE IS AN OPTIONAL HIGH HAT |
| AND 5/8 INCH GYPSUM WALL BOARD. |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. SUCH DRAWINGS |
| AND SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE |
| FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE |
| SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE CITED AS |
| A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS |
| EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| INFORMATION. |
| |
| 7) PAGE 005/ A-1.02 OCCUPANCY & EGRESS PLAN / FIRE WALL |
| SEPARATION. |
| PAGE 023/ A-3.41 SOUTH STAIRS |
| PAGE 024/ A-4.11 FIRST FLOOR PLAN |
| |
| 7A)(1) COMPLIED. 4/01/2015 SPOKE WITH THE DESIGNER OF |
| RECORD, RESOLVED ISSUE WITH SECTION 1027.1 EXCEPTION |
| 1.1-1.3. |
| |
| 7A)(2) NEW COMMENT. THE LISTED ABOVE SHEETS DO NOT |
| PROVIDE DOOR IDENTIFICATION TAGS TO VERIFY FIRE |
| RESISTANCE RATINGS. 2010 FBC-B TABLE 715.4. |
| |
| 7B-H) COMPLIED. |
| |
| 8) COMPLIED. |
| 9) PAGE 42/ A-6.20 : |
| 9A) 2ND REQUEST. TRASH ROOM 2ND THROUGH THE 4TH FLOOR |
| SHOW THE WHOLE OF THE TRASH ROOM/ ENCLOSURE AS BEING |
| WITHIN THE 2 HOUR RATING FOR A SHAFT. DETAIL # 6 LABELS |
| THE REFUSE CHUTE ITSELF AS THE SHAFT, THIS IS JUST THE |
| TRASH CHUTE ITSELF. |
| FBC-B 708.13.1 REFUSE AND LAUNDRY CHUTE ENCLOSURES. A |
| SHAFT ENCLOSURE CONTAINING A REFUSE OR LAUNDRY CHUTE |
| SHALL NOT BE USED FOR ANY OTHER PURPOSE AND SHALL BE |
| ENCLOSED IN ACCORDANCE WITH SECTION 708.4. OPENINGS |
| INTO THE SHAFT, INCLUDING THOSE FROM ACCESS ROOMS AND |
| TERMINATION ROOMS, SHALL BE PROTECTED IN ACCORDANCE |
| WITH THIS SECTION AND SECTION 715. OPENINGS INTO CHUTES |
| SHALL NOT BE LOCATED IN CORRIDORS. DOORS SHALL BE SELF- |
| OR AUTOMATIC-CLOSING UPON THE ACTUATION OF A SMOKE |
| DETECTOR IN ACCORDANCE WITH SECTION 715.4.8.3, EXCEPT |
| THAT HEAT-ACTIVATED CLOSING DEVICES SHALL BE PERMITTED |
| BETWEEN THE SHAFT AND THE TERMINATION ROOM. |
| |
| 9B) 2ND REQUEST, SHAFT IS STILL ENCLOSING THE ACCESS |
| ROOM SEPARATING THE SHAFT FROM CORRIDOR. WITH THE |
| CORRECTED SHAFT THE ACCESS ROOM THAT LEADS FROM THE |
| CORRIDOR TO THE REFUSE CHUTE, THIS AREA WILL NEED TO |
| COMPLY WITH 708.13.3 A 1 HOUR FIRE BARRIER WITH 3/4 HR. |
| DOOR SELF-CLOSING OR AUTOMATIC CLOSING UPON THE |
| DETECTION OF SMOKE IN ACCORDANCE WITH SECTION |
| 715.4.8.3. DOOR IS SHOWN AS ? HR. |
| |
| 9C) COMPLIED. |
| DETAIL # 6 FOR THE TRASH COLLECTION ROOM FAILS TO |
| PROVIDE A FIRE RATING AT THE BOTTOM OF THE SHAFT, (2ND |
| FLOOR LEVEL). SEE FBC-B 708.11 ENCLOSURE AT THE BOTTOM. |
| NOTE THAT THE 3 HOUR FIRE RATED WALLS WOULD MEET THE |
| FIRE RATINGS REQUIRED, ONLY 2 HRS. REQUIRED BUT THE |
| OPENING PROTECTIVES WOULD THEN NEED TO BE 1 1/2 HOUR |
| FIRE RATING PER TABLE 715.4. |
| |
| 10-12) COMPLIED. |
| 13-18) REFER BACK TO THE REQUIREMENT OF COMMENT # 6 AND |
| RESPONSE TO BE AIR-BORNE & STRUCTURE BORN SOUND TO BE |
| FIELD TESTED. 2010 WEST PALM BEACH AMENDMENTS TO THE |
| FLORIDA BUILDING CODE, CHAPTER 1 107.3.3 CONTRACTOR IS |
| AT OWN RISK, NO ASSURANCES THAT A CERTIFICATE OF |
| OCCUPANCY CAN BE ISSUED WITHOUT CODE COMPLIANCE |
| 13A) PAGE 17/ A-3.10 THE EXIT ACCESS WALL COMMON TO |
| THIS UNIT HAS A WALL TAG # 21 THIS WALL DOES NOT |
| INDICATE COMPLIANCE WITH FBC-B 1207.2 AIR-BORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION |
| ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES; RECESSED |
| CABINETS; BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR |
| EXHAUST DUCTS SHALL BE SEALED, LINED, INSULATED OR |
| OTHERWISE TREATED TO MAINTAIN THE REQUIRED RATINGS. |
| THIS REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT |
| ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT |
| FITTING TO THE FRAME AND SILL. |
| |
| 13B) PAGE 18/ A-3.11 THE EXIT ACCESS WALL COMMON TO |
| THIS UNIT HAS A WALL TAG # 21 THIS WALL DOES NOT |
| INDICATE COMPLIANCE WITH FBC-B 1207.2 AIR-BORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION |
| ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES; RECESSED |
| CABINETS; BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR |
| EXHAUST DUCTS SHALL BE SEALED, LINED, INSULATED OR |
| OTHERWISE TREATED TO MAINTAIN THE REQUIRED RATINGS. |
| THIS REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT |
| ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT |
| FITTING TO THE FRAME AND SILL. |
| |
| 14A) PAGE 19/ A3.12 THE BATHROOM WALL NEXT TO THE |
| GARDEN TUB DOES NOT HAVE A WALL IDENTIFICATION TAG, |
| SHOW COMPLIANCE WITH FBC-B 1207.2 AIR-BORNE SOUND. |
| |
| 14B) PAGE 19/ A3.12 THE KITCHEN WALL NEXT TO THE SINK |
| HAS A WALL IDENTIFICATION TAG OF 33, THIS WALL DOES NOT |
| HAVE ANY SOUND RATING, SHOW COMPLIANCE WITH FBC-B |
| 1207.2 AIR-BORNE SOUND. |
| |
| 15) PAGE 20/ A3.20 THE EXIT ACCESS WALL COMMON TO THIS |
| UNIT HAS A WALL TAG # 21 THIS WALL DOES NOT INDICATE |
| COMPLIANCE WITH FBC-B 1207.2 AIR-BORNE SOUND. |
| |
| 16A) A3.21 THE EXIT ACCESS WALL COMMON TO THIS UNIT HAS |
| A WALL TAG # 21 THIS WALL DOES NOT INDICATE COMPLIANCE |
| WITH FBC-B 1207.2 AIR-BORNE SOUND. |
| |
| 16B) MASTER BATH GARDEN TUB WALL THAT BACKS UP TO |
| SHAFT, NO SHAFT IS SHOWN WALL TAG# 30 , WALL TYPE 30 |
| DOES NOT PROVIDE COMPLIANCE WITH FBC-B 1207.2 AIR-BORNE |
| SOUND. |
| |
| 17) A3.22 WALL TAGS 33 & 35, BOTH OF THESE WALLS DO NOT |
| PROVIDE COMPLIANCE WITH FBC-B 1207.2 AIR-BORNE SOUND. |
| |
| 18) PAGE 25, A4.12 HVAC SHAFT, THIS COMMENT STANDS FOR |
| ALL FLOORS, WALL TAG # 30 DOES NOT SHOW COMPLIANCE WITH |
| FBC-B 1207.2 AIR-BORNE SOUND. |
| |
| 19) 2ND REQUEST, THE DESIGNER OF RECORD HAS LISTED THE |
| CODE SECTION ON THIS SHEET, NOT THE DESIGN PARAMETERS. |
| 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION 107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. SUCH INFORMATION SHALL BE |
| SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE CITED AS |
| A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" OR |
| ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| INFORMATION. |
| |
| 1ST REVIEW COMMENT. PAGE 43/ A7.01 GUARD RAILINGS FOR |
| BALCONIES. DETAILS 3, 10 & 11 SHOW GUARD RAIL |
| ATTACHMENT TO THE STRUCTURE WITH EXPANSION BOLTS. THERE |
| IS A NOTE ON THE PLANS THAT THE CONNECTION DETAILS ARE |
| TO BE DESIGNED BY A ENGINEER LICENSED IN THE STATE OF |
| FLORIDA. WHAT THE DESIGNER OF RECORD FAILED TO PROVIDE |
| IS THE REQUIREMENTS OF THE CODE FOR THE ENGINEER TO |
| FOLLOW. |
| 2010 FBC-B 1607.7.1 HANDRAILS AND GUARDS. |
| 1607.7.1.1 CONCENTRATED LOAD. |
| 1607.7.1.2 COMPONENTS. |
| 20) 2ND REQUEST. THE NEW NOTES QUOTE THE CODE SECTION, |
| THEY DO NOT GIVE THE FABRICATOR TO WHICH DESIGN |
| CRITERIA YOU ARE SPECIFYING FOR THESE ELEMENTS ON YOUR |
| BUILDING. THE DESIGNER OF RECORD HAS LISTED THE CODE |
| SECTION ON THIS SHEET, NOT THE DESIGN PARAMETERS. 2010 |
| WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION 107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. SUCH INFORMATION SHALL BE |
| SPECIFIC, |
| AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE |
| OR IN PART, NOR SHALL THE TERM "LEGAL" OR |
| ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| INFORMATION. |
| |
| 1ST REVIEW COMMENT. PAGE 44/ A-7.02 & S-7.04 VARIOUS |
| DETAILS AND DESIGN ARE SHOWN FOR CANOPY AND AWNINGS, |
| THERE IS NO ATTACHMENT INFORMATION NOR IS THERE A |
| PROPOSED WIND DESIGN PARAMETERS FOR THE SPECIALTY |
| ENGINEER TO DESIGN. FBC-B 3105. |
| 21)2ND REQUEST, ENERGY CALCULATIONS DATED 12/09/2014. |
| PAGE 45/A-7.03 INDICATES AN INSULATION NOTE WAS ADDED |
| BUT WHERE? PAGE 45/ A-7.03 ROOF DETAILS NOR THE ENERGY |
| CALCULATIONS PROVIDE WHAT THE MINIMUM ROOF INSULATION |
| IS THAT IS REQUIRED. NOTE THE ENERGY FORMS ARE NOT |
| CORRECT, THE FRONT PAGE IS FOR A 1 STORY BUILDING, |
| PAGES 33-34 BOTH SHOW A VALUE OF R-21.2 PLEASE PROVIDE |
| HOW CODE COMPLIANCE WILL BE ACHIEVED. WHOLE BUILDING |
| METHOD FL ENERGY 506.2.1. |
| |
| 22) SEMI ?COMPLIED. PAGE 53/ S1.01 ROOF ZONES 1, 2 & 3 |
| THE PRESSURES ARE LOW FOR A MEAN ROOF HEIGHT OF 48 FT. |
| WITH A EXPOSURE D COEFFICIENT. PAGE 47/ S 1.01 WALL |
| PRESSURES OK ARE TAKEN AT THE PARAPET HEIGHT OF 54 FT. |
| ELEVATION. |
| |
| 23) 2ND REQUEST. ARCHITECTS RESPONSE NOTE STATE SEE |
| STRUCTURAL ENGINEERS NOTES FOR 22 & 23. THERE WAS NO |
| RESPONSE TO COMMENT # 23. CELCORE LIGHTWEIGHT |
| INSULATING CONCRETE NOA 13-0307.02 CIRCLE THE |
| SUB-SYSTEM THAT IS TO BE USED ON THIS PROJECT AND THE |
| ASSOCIATED PRESSURES. 107.2.1.3 ADDITIONAL INFORMATION |
| IS REQUIRED. 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY |
| THE CODE, THE CONSTRUCTION DOCUMENTS SHALL |
| ILLUSTRATE, DESCRIBE AND DELINEATE THE TYPE OF ROOFING |
| SYSTEM, MATERIALS, FASTENING REQUIREMENTS, FLASHING |
| REQUIREMENTS AND WIND RESISTANCE RATING THAT ARE |
| REQUIRED TO BE INSTALLED. PRODUCT EVALUATION AND |
| INSTALLATION SHALL INDICATE COMPLIANCE WITH THE WIND |
| CRITERIA REQUIRED FOR THE SPECIFIC SITE OR A STATEMENT |
| BY AN ARCHITECT OR ENGINEER FOR THE SPECIFIC SITE MUST |
| BE SUBMITTED WITH THE CONSTRUCTION DOCUMENTS. |
| |
| 24-27) DEFERRED SUBMITTALS. 107.3.4.2 DEFERRED |
| SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, DEFERRED |
| SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN |
| THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION |
| AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL |
| WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL |
| ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING |
| OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS |
| ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE |
| BUILDING OFFICIAL. |
| DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| OFFICIAL. |
| |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B) WINDOWS |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES |
| (E) SHUTTERS |
| (F) SKYLIGHTS |
| (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| STANDS |
| |
| 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| |
| |
| 28) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. FOR DIGITAL |
| PLANS, YOU WILL NEED TO PRINT THE CODE SUMMARY SHEET |
| AND FLOOR PLANS TO SUBMIT TO THE COUNTY FOR REVIEW. WE |
| WILL NEED THE STAMPED SHEET AND THE RECEIPT. PLEASE |
| CALL (561)233-5025 FOR MORE INFORMATION. |
| |
| 29) FOR DIGITAL REVIEW PLEASE SUBMIT A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO |
| HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA |
| TUS.ASPX FOR PERMIT STATUS. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |
| |
| |
| |