2014-12-30 12:22:461) SHT.A-1.00 - ACCESSIBILITY NOTES - "NUMBER OF
 ACCESSIBLE UNITS"-PLAN NOTES - 'ALL GROUND FLOOR UNITS
 TO BE ADAPTABLE UNITS." SINCE THE BUILDING HAS AN
 ELEVATOR AND THIS MAKES ALL THE FLOORS ACCESSIBLE, ALL
 THE UNITS IN THE BUILDING SHALL BE ADAPTABLE IN
 ACCORDANCE WITH THE FEDERAL FAIR HOUSING ACT. PLEASE
 REVISE NOTE.
 2) SHT.A-1.00 -INDEX SHEET - UNDER "OCCUPANCY
 CLASSIFICATIONS" REFERENCE IS MADE TO TABLE 3-A. I
 COULD NOT FIND THIS TABLE IN THE 2010 FL. BUILDING
 CODE. CLARIFY.
 3) SHT.A-1.00 - UNDER OCCUPANT LOAD - I COUNT 263
 PERSONS NOT 253. CLARIFY.
 4) SHT.A-1.03 - THE HEIGHT OF THE GRAB BARS ABOVE THE
 FINISH FLOOR SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE, NOT TO THE CENTERLINE AS SHOWN PER
 THE 2010 FL. ACCESSIBILITY CODE SEC. 604.9.
 5) SHT. A-1.03 - THE TOILET PAPER DISPENSER SHALL BE
 LOCATED 7-9 INCHES IN FRONT OF THE WATER CLOSET
 MEASURED TO THE CENTERLINE OF THE DISPENSER PER THE FAC
 SEC.604.7.
 6) SHT.A-1.03 - FIG.30 - THE LAVATORY SHALL BE A MIN.
 OF 19 INCHES WIDE PER THE 2010 FAC SEC.604.8.1.6. THE
 PLAN SHOWS THE LAVATORY AS 18 INCHES WIDE.
 7) SHT. A-1.03 - THE SIDE GRAB BARS IN THE TOILET STALL
 DETAIL ARE SHOWN AS 40". THE MINIMUM LENGTH SHALL BE
 42" PER THE 2010 FAC SEC.604.5.1.
 8) SHT. A-1.03 - THE CLEAR FLOOR SPACE FOR WATER
 CLOSETS IS 60 INCHES MINIMUM MEASURED PERPENDICULAR
 FROM THE SIDE WALL AND 56 INCHES MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL PER THE 2010 FAC
 SEC.604.3.1. FIGURE 28 DOES NOT COMPLY.
 9) SHT. A-1.03 -SHOWS THE TOILET STALL AS BEING 6'-10"
 WIDE. THIS IS NOT WIDE ENOUGH TO MEET THE ACCESSIBILITY
 CODE. IT SHOULD BE A MINIMUM OF 85 INCHES. 86 INCHES
 ALLOWS FOR CONSTRUCTION TOLERANCES.
 10) SHT.A1.04 REFERS TO THE 2010 FBC, THE 1998 FAIR
 HOUSING ACT, ICC/ANSI A117.1 & THE UNIFORM FEDERAL
 ACCESSIBILITY STANDARDS. WHICH DOCUMENT ARE YOU USING
 FOR THE ACCESSIBLE DESIGN OF THIS BUILDING? THE FAIR
 HOUSING ACT SHOULD BE THE GOVERNING STANDARD.DELETE THE
 DETAILS THAT DO NOT APPLY AND SUBMIT THE DETAILS FOR
 GRAB BARS, BACKING ETC. FOR THE FAIR HOUSING ACT.
 11) SHT. A-2.00 - NOTE #1 REFERS TO CHAPT. 11 OF THE
 INTERNATIONAL BUILDING CODE FOR HANDICAP ACCESSIBILITY
 REQUIREMENTS.THE EXTERIOR SITE ELEMENTS THAT APPLY TO
 THE DWELLING UNITS SHALL COMPLY WITH THE FAIR HOUSING
 ACT AND THE NON-RESIDENTIAL ELEMENTS SHALL COMPLY WITH
 THE FL. ACCESSIBILITY CODE.
 12) SHT. A-3.41- RESTROOMS # 1,2,3 AND THE MEN'S AND
 WOMEN'S SHOWS THE DOOR SWINGING INTO THE CLEAR FLOOR
 SPACE FOR THE LAVATORY AND WATER CLOSET. DOORS SHALL
 NOT SWING INTO THE CLEAR FLOOR SPACE REQUIRED FOR ANY
 FIXTURE. SEE FAC SEC.603.2.3 (2) FOR EXCEPTION. SHOW
 THE REQUIRED CLEAR FLOOR SPACE LOCATED OUTSIDE THE
 SWING OF THE DOOR.
 13) SHT.A-3.10 - PLEASE EXPLAIN NOTE #7 WHERE IT STATES
 "ADAPTABLE UNITS SHALL BE DESIGNED AS TYPE "B" UNITS
 WITH OPTION "A" FOR TOILET AND BATHING ROOM..
 14) SHT. A-3.10 - GENERAL NOTE #9 - M.R. DRYWALL IS NOT
 PERMITTED IN WET AREAS PER THE 2010 FBC SEC.2509.3.
 15) SHT.A-3.10 - DETAIL 10 - THE DOOR SWINGS INTO THE
 CLEAR FLOOR SPACE FOR THE LAVATORY. A 30 INCH BY 48
 INCH CLEAR FLOOR SPACE IS REQUIRED OUTSIDE THE SWING OF
 THE DOOR FOR MANEUVERING SPACE PER THE FHA GUIDELINES.
 16) SHT.A-3.21 - DETAIL 12 - THE DOOR SWINGS INTO THE
 CLEAR FLOOR SPACE FOR THE LAVATORY. A 30 INCH BY 48
 INCH CLEAR FLOOR SPACE IS REQUIRED OUTSIDE THE SWING OF
 THE DOOR FOR MANEUVERING SPACE PER THE FHA GUIDELINES.
 17) SHT. A-4.11 - GENERAL NOTE # 9 REFERS TO SHT.
 A-0.02 FOR ACCESSIBILITY DETAILS. THERE IS NO SUCH
 SHEET IN THE DOCUMENTS. CLARIFY.
 18) SUBMIT A RISER DRAWING FOR THE CONDENSATE SYSTEM
 AND FOR THE PAN DRAINS AND WATER HEATER RELIEF LINES.
 WPB AMEND. TO 2010 FBC SEDC.107.2.1.
 19) SHTS. P-3.00,P-3.01, P-3.02 - THE WASTE STACK VENT
 FOR THE KITCHEN SINKS SHALL BE 3 INCHES PER THE 2010
 FL. PLUMBING CODE SEC.910.3.
 20) SHTS.P-3.00, 301, 302, 303, 304 - SIZE ALL DRAINAGE
 SECTIONS OF RISER #1 FOR THE BATHROOM GROUP AND ALSO
 THE VENT FROM THE LAVATORY.
 21) SHT. 4.00 - INDICATE THE MINIMUM CONCRETE COVER OF
 THE PIPING AT THE DETAIL AT BEAMS.
 22) SUBMIT A COMPLETE GAS RISER DIAGRAM SHOWING THE GAS
 PSI, THE TYPE OF PIPE MATERIAL, THE TOTAL DISTANCE FROM
 THE GAS METER TO THE MOST REMOTE OUTLET, THE LENGTH
 DIMENSIONS OF ALL SECTIONS OF PIPE. WPB AMEND. TO 2010
 FBC SEC.107.3.5.1.5.
 23) SUBMIT A SANITARY RISER DIAGRAM FOR THE UNDERGROUND
 COLLECTION SYSTEM. WPB AMEND. TO 2010 FBC
 SEC.107.3.5.1.3.
 24) SUBMIT CALCULATIONS FOR THE STORM DRAINAGE.
 INDICATE THE SQUARE FOOTAGE NOF THE ROOF DRAINED BY
 EACH SCUPPER AND DOWNSPOUT. SCUPPERS SHALL BE SIZED PER
 THE 2010 FPC SEC. 1106.7 AND TABLE 1106.7. DOWNSPOUTS
 SHALL BE SIZED PER 2010 FPC TABLE 1106.2 (2).
 25) ONE HALF OF THE AREA OF ANY VERTICAL WALL THAT
 DIVERTS RAINWATER TO THE ROOF SHALL BE ADDED TO THE
 PROJECTED ROOF AREA PER 2010 FPC SEC. 1106.4.
 26) ALL HOSE BIBBS SHALL HAVE SHUTOFF VALVES PER 2010
 FPC SEC.606.2 (2).
 27) THE PLUMBING PLANS HAVE A NOTE THAT STATES " REFER
 TO BUILDING PLANS FOR FIRST FLOOR PIPING." CLARIFY.
 28) INDICATE ON THE PLANS IF THE ELEVATORS ARE OPERATED
 BY A HYDRAULIC SHAFT OR TRACTION TYPE UNITS. IF THEY
 ARE HYDRAULIC SHAFT TYPE, AN OIL/WATER SEPARATOR WILL
 BE REQUIRED FOR THE ELEVATOR SUMP PIT DISCHARGE. 2010
 FPC SEC.1003.4.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692