2014-12-30 12:22:46 | 1) SHT.A-1.00 - ACCESSIBILITY NOTES - "NUMBER OF |
| ACCESSIBLE UNITS"-PLAN NOTES - 'ALL GROUND FLOOR UNITS |
| TO BE ADAPTABLE UNITS." SINCE THE BUILDING HAS AN |
| ELEVATOR AND THIS MAKES ALL THE FLOORS ACCESSIBLE, ALL |
| THE UNITS IN THE BUILDING SHALL BE ADAPTABLE IN |
| ACCORDANCE WITH THE FEDERAL FAIR HOUSING ACT. PLEASE |
| REVISE NOTE. |
| 2) SHT.A-1.00 -INDEX SHEET - UNDER "OCCUPANCY |
| CLASSIFICATIONS" REFERENCE IS MADE TO TABLE 3-A. I |
| COULD NOT FIND THIS TABLE IN THE 2010 FL. BUILDING |
| CODE. CLARIFY. |
| 3) SHT.A-1.00 - UNDER OCCUPANT LOAD - I COUNT 263 |
| PERSONS NOT 253. CLARIFY. |
| 4) SHT.A-1.03 - THE HEIGHT OF THE GRAB BARS ABOVE THE |
| FINISH FLOOR SHALL BE MEASURED TO THE TOP OF THE |
| GRIPPING SURFACE, NOT TO THE CENTERLINE AS SHOWN PER |
| THE 2010 FL. ACCESSIBILITY CODE SEC. 604.9. |
| 5) SHT. A-1.03 - THE TOILET PAPER DISPENSER SHALL BE |
| LOCATED 7-9 INCHES IN FRONT OF THE WATER CLOSET |
| MEASURED TO THE CENTERLINE OF THE DISPENSER PER THE FAC |
| SEC.604.7. |
| 6) SHT.A-1.03 - FIG.30 - THE LAVATORY SHALL BE A MIN. |
| OF 19 INCHES WIDE PER THE 2010 FAC SEC.604.8.1.6. THE |
| PLAN SHOWS THE LAVATORY AS 18 INCHES WIDE. |
| 7) SHT. A-1.03 - THE SIDE GRAB BARS IN THE TOILET STALL |
| DETAIL ARE SHOWN AS 40". THE MINIMUM LENGTH SHALL BE |
| 42" PER THE 2010 FAC SEC.604.5.1. |
| 8) SHT. A-1.03 - THE CLEAR FLOOR SPACE FOR WATER |
| CLOSETS IS 60 INCHES MINIMUM MEASURED PERPENDICULAR |
| FROM THE SIDE WALL AND 56 INCHES MINIMUM MEASURED |
| PERPENDICULAR FROM THE REAR WALL PER THE 2010 FAC |
| SEC.604.3.1. FIGURE 28 DOES NOT COMPLY. |
| 9) SHT. A-1.03 -SHOWS THE TOILET STALL AS BEING 6'-10" |
| WIDE. THIS IS NOT WIDE ENOUGH TO MEET THE ACCESSIBILITY |
| CODE. IT SHOULD BE A MINIMUM OF 85 INCHES. 86 INCHES |
| ALLOWS FOR CONSTRUCTION TOLERANCES. |
| 10) SHT.A1.04 REFERS TO THE 2010 FBC, THE 1998 FAIR |
| HOUSING ACT, ICC/ANSI A117.1 & THE UNIFORM FEDERAL |
| ACCESSIBILITY STANDARDS. WHICH DOCUMENT ARE YOU USING |
| FOR THE ACCESSIBLE DESIGN OF THIS BUILDING? THE FAIR |
| HOUSING ACT SHOULD BE THE GOVERNING STANDARD.DELETE THE |
| DETAILS THAT DO NOT APPLY AND SUBMIT THE DETAILS FOR |
| GRAB BARS, BACKING ETC. FOR THE FAIR HOUSING ACT. |
| 11) SHT. A-2.00 - NOTE #1 REFERS TO CHAPT. 11 OF THE |
| INTERNATIONAL BUILDING CODE FOR HANDICAP ACCESSIBILITY |
| REQUIREMENTS.THE EXTERIOR SITE ELEMENTS THAT APPLY TO |
| THE DWELLING UNITS SHALL COMPLY WITH THE FAIR HOUSING |
| ACT AND THE NON-RESIDENTIAL ELEMENTS SHALL COMPLY WITH |
| THE FL. ACCESSIBILITY CODE. |
| 12) SHT. A-3.41- RESTROOMS # 1,2,3 AND THE MEN'S AND |
| WOMEN'S SHOWS THE DOOR SWINGING INTO THE CLEAR FLOOR |
| SPACE FOR THE LAVATORY AND WATER CLOSET. DOORS SHALL |
| NOT SWING INTO THE CLEAR FLOOR SPACE REQUIRED FOR ANY |
| FIXTURE. SEE FAC SEC.603.2.3 (2) FOR EXCEPTION. SHOW |
| THE REQUIRED CLEAR FLOOR SPACE LOCATED OUTSIDE THE |
| SWING OF THE DOOR. |
| 13) SHT.A-3.10 - PLEASE EXPLAIN NOTE #7 WHERE IT STATES |
| "ADAPTABLE UNITS SHALL BE DESIGNED AS TYPE "B" UNITS |
| WITH OPTION "A" FOR TOILET AND BATHING ROOM.. |
| 14) SHT. A-3.10 - GENERAL NOTE #9 - M.R. DRYWALL IS NOT |
| PERMITTED IN WET AREAS PER THE 2010 FBC SEC.2509.3. |
| 15) SHT.A-3.10 - DETAIL 10 - THE DOOR SWINGS INTO THE |
| CLEAR FLOOR SPACE FOR THE LAVATORY. A 30 INCH BY 48 |
| INCH CLEAR FLOOR SPACE IS REQUIRED OUTSIDE THE SWING OF |
| THE DOOR FOR MANEUVERING SPACE PER THE FHA GUIDELINES. |
| 16) SHT.A-3.21 - DETAIL 12 - THE DOOR SWINGS INTO THE |
| CLEAR FLOOR SPACE FOR THE LAVATORY. A 30 INCH BY 48 |
| INCH CLEAR FLOOR SPACE IS REQUIRED OUTSIDE THE SWING OF |
| THE DOOR FOR MANEUVERING SPACE PER THE FHA GUIDELINES. |
| 17) SHT. A-4.11 - GENERAL NOTE # 9 REFERS TO SHT. |
| A-0.02 FOR ACCESSIBILITY DETAILS. THERE IS NO SUCH |
| SHEET IN THE DOCUMENTS. CLARIFY. |
| 18) SUBMIT A RISER DRAWING FOR THE CONDENSATE SYSTEM |
| AND FOR THE PAN DRAINS AND WATER HEATER RELIEF LINES. |
| WPB AMEND. TO 2010 FBC SEDC.107.2.1. |
| 19) SHTS. P-3.00,P-3.01, P-3.02 - THE WASTE STACK VENT |
| FOR THE KITCHEN SINKS SHALL BE 3 INCHES PER THE 2010 |
| FL. PLUMBING CODE SEC.910.3. |
| 20) SHTS.P-3.00, 301, 302, 303, 304 - SIZE ALL DRAINAGE |
| SECTIONS OF RISER #1 FOR THE BATHROOM GROUP AND ALSO |
| THE VENT FROM THE LAVATORY. |
| 21) SHT. 4.00 - INDICATE THE MINIMUM CONCRETE COVER OF |
| THE PIPING AT THE DETAIL AT BEAMS. |
| 22) SUBMIT A COMPLETE GAS RISER DIAGRAM SHOWING THE GAS |
| PSI, THE TYPE OF PIPE MATERIAL, THE TOTAL DISTANCE FROM |
| THE GAS METER TO THE MOST REMOTE OUTLET, THE LENGTH |
| DIMENSIONS OF ALL SECTIONS OF PIPE. WPB AMEND. TO 2010 |
| FBC SEC.107.3.5.1.5. |
| 23) SUBMIT A SANITARY RISER DIAGRAM FOR THE UNDERGROUND |
| COLLECTION SYSTEM. WPB AMEND. TO 2010 FBC |
| SEC.107.3.5.1.3. |
| 24) SUBMIT CALCULATIONS FOR THE STORM DRAINAGE. |
| INDICATE THE SQUARE FOOTAGE NOF THE ROOF DRAINED BY |
| EACH SCUPPER AND DOWNSPOUT. SCUPPERS SHALL BE SIZED PER |
| THE 2010 FPC SEC. 1106.7 AND TABLE 1106.7. DOWNSPOUTS |
| SHALL BE SIZED PER 2010 FPC TABLE 1106.2 (2). |
| 25) ONE HALF OF THE AREA OF ANY VERTICAL WALL THAT |
| DIVERTS RAINWATER TO THE ROOF SHALL BE ADDED TO THE |
| PROJECTED ROOF AREA PER 2010 FPC SEC. 1106.4. |
| 26) ALL HOSE BIBBS SHALL HAVE SHUTOFF VALVES PER 2010 |
| FPC SEC.606.2 (2). |
| 27) THE PLUMBING PLANS HAVE A NOTE THAT STATES " REFER |
| TO BUILDING PLANS FOR FIRST FLOOR PIPING." CLARIFY. |
| 28) INDICATE ON THE PLANS IF THE ELEVATORS ARE OPERATED |
| BY A HYDRAULIC SHAFT OR TRACTION TYPE UNITS. IF THEY |
| ARE HYDRAULIC SHAFT TYPE, AN OIL/WATER SEPARATOR WILL |
| BE REQUIRED FOR THE ELEVATOR SUMP PIT DISCHARGE. 2010 |
| FPC SEC.1003.4. |
| |
| PLUMBING PLAN REVIEW |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |