 23RD STREET
 APARTMENT BUILDING
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENT.
  
 PROVIDE A SINGLE POINT OF SERVICE TO THE STRUCTURE OR
 PROVIDE JUSTIFICATION FOR THE ELECTRICAL DESIGN AS
 OUTLINED WITHIN THE NATIONAL ELECTRICAL CODE. NEC 230.2
  
 COMMON GROUNDING ELECTRODES ARE REQUIRED TO SERVE THE
 SAME BUILDING AND ALL SEPARATE SERVICES. NEC 250.58
  
 SHEET NO. E-4.00
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 FOR THE SERVICE, PANEL BOARDS AND MAIN DISCONNECTING
 MEANS ON THE ELECTRICAL PLAN. NEC 110.22
  
 PROVIDE PERMANENT IDENTIFICATION PLAQUE WHICH SHOWS THE
 LOCATION OF THE ELECTRICAL SERVICES AND MAIN
 DISCONNECTS. NEC 230.2 (E)
  
 SHEET NO. E5.00, E5.01, E5.02
  
 VERIFY THAT NOTE # 4 PROVIDING AN 800 AMPERE HORIZONTAL
 BUS IS APPLICABLE TO THE 1000 AMPERE METER CENTER #1.
 NEC 110.3
  
 PROVIDE ON THE ELECTRICAL PLAN A SAFETY LABELING
 SCHEDULE FOR FLASH PROTECTION FOR THE SERVICE, PANEL
 BOARDS AND MAIN DISCONNECTING MEANS. NEC 110.22
  
  
 NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR ALARM
 SYSTEMS, SECURITY, SITE LIGHTING, RETAIL BUILD OUT AND
 DATA SYSTEMS
  