Plan Review Notes For Permit 14120431 |
Permit Number |
14120431 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-01-30 14:53:05 | 14120431 | | 23RD STREET | | APARTMENT BUILDING | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | REVIEW COMMENT. | | | | PROVIDE A SINGLE POINT OF SERVICE TO THE STRUCTURE OR | | PROVIDE JUSTIFICATION FOR THE ELECTRICAL DESIGN AS | | OUTLINED WITHIN THE NATIONAL ELECTRICAL CODE. NEC 230.2 | | | | COMMON GROUNDING ELECTRODES ARE REQUIRED TO SERVE THE | | SAME BUILDING AND ALL SEPARATE SERVICES. NEC 250.58 | | | | SHEET NO. E-4.00 | | | | PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION | | FOR THE SERVICE, PANEL BOARDS AND MAIN DISCONNECTING | | MEANS ON THE ELECTRICAL PLAN. NEC 110.22 | | | | PROVIDE PERMANENT IDENTIFICATION PLAQUE WHICH SHOWS THE | | LOCATION OF THE ELECTRICAL SERVICES AND MAIN | | DISCONNECTS. NEC 230.2 (E) | | | | SHEET NO. E5.00, E5.01, E5.02 | | | | VERIFY THAT NOTE # 4 PROVIDING AN 800 AMPERE HORIZONTAL | | BUS IS APPLICABLE TO THE 1000 AMPERE METER CENTER #1. | | NEC 110.3 | | | | PROVIDE ON THE ELECTRICAL PLAN A SAFETY LABELING | | SCHEDULE FOR FLASH PROTECTION FOR THE SERVICE, PANEL | | BOARDS AND MAIN DISCONNECTING MEANS. NEC 110.22 | | | | | | NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR ALARM | | SYSTEMS, SECURITY, SITE LIGHTING, RETAIL BUILD OUT AND | | DATA SYSTEMS | | | | ROBERT LECKY, CBO | | ELECTRICAL PLANS REVIEW | | 561-373-3701 | | [email protected] | | |
|