2015-01-20 15:10:56 | BUILDING PLAN REVIEW |
| PERMIT: 14120431 |
| ADD: 321 23RD ST. |
| PCN:74-43-43-10-19-003-0143 |
| CONT: PETROCCHI CONSTRUCTION |
| TEL: (305)495-3745 |
| |
| PARK PALM BEACH MULTIFAMILY RESIDENTIAL |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 1ST REVIEW |
| DATE:MON. JAN. 20/2015 |
| ACTION: DENIED |
| |
| 1) THE PERMIT APPLICATION LIST THE ADDRESS OF 321 23RD |
| ST./ 74-43-43-10-19-003-0143, THIS IS A SINGLE LOT, |
| THIS WILL REQUIRE MORE THAN A UNITIY OF TITLE, THIS |
| PROJECT WILL REQUIRE A REPLAT WITH A NEW PCN AND |
| POSSIBLE ADDRESS CHANGE. |
| |
| 2) THIS PROJECT IS FOR A 4 STORY BUILDING THAT |
| QUALIFIES AS A THRESHOLD BUILDING. FL S. S. 553.71(7) " |
| THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS |
| GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH |
| HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN |
| THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN |
| AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| PERSONS. |
| |
| 2A) 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A |
| (WRITTEN/ TYPED) SPECIAL INSPECTOR TO PERFORM |
| STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING PURSUANT |
| TO A STRUCTURAL INSPECTION PLAN PREPARED BY THE |
| ENGINEER OF RECORD. THE STRUCTURAL INSPECTION PLAN MUST |
| BE SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE |
| ISSUANCE OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A |
| THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL |
| INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION |
| PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE |
| ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED |
| DOCUMENTS. |
| |
| 2B) THRESHOLD BLDG, REQUIRED STATEMENT: W.P.B. |
| AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH |
| ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT |
| OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE |
| BEST OF THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE, THE |
| PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE |
| FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| FLORIDA STATUTE. |
| |
| C) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' |
| OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| MEETING THE ABOVE CRITERIA. |
| CONTACT KEN CONRAD |
| TEL: 561-805-6666 |
| E-MAIL: [email protected] |
| |
| D) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY |
| FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE SUBMITTED TO |
| KEN CONRAD BY E-MAIL. KEN CONRAD: [email protected] |
| |
| E) NOTE NO ACTION IS REQUIRED, WE ARE E-MAILING YOU THE |
| THRESHOLD INSPECTOR DOCUMENTS AND FORMS TO THIS E-MAIL |
| ADDRESS; |
| E-MAIL: [email protected] JAN. 20/2015 |
| |
| F) NOTE THIS IS A DIGITAL PLAN, AFTER PERMIT ISSUANCE, |
| THE PERMIT LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND |
| BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO |
| SETS OF PLANS WILL NEED TO BE PRINTED IN COLLOR, (1) |
| FOR THE THRESHOLD INSPECTOR, THE OTHER FOR THE MEP |
| INSPECTORS. |
| |
| G) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR |
| IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE |
| INSPECTIONS. |
| |
| H) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES |
| FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER |
| HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE |
| MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR |
| WALLS AND CEILINGS. |
| |
| 3) THE PERMIT VALUATION OF $8,500,000.00 IS LOW |
| COMPARED TO THE CALCULATED VALUE FROM THE ICC BUILDING |
| VALUATION DATA AUGUST 2014 USING THESE TABLES THE |
| CALCULATED VALUE OF $9,855,203.00. |
| |
| 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION 108.3* BUILDING PERMIT |
| VALUATION. |
| IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED |
| DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS |
| FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| CONGRESS. |
| |
| 4) PLEASE NOTE UNDER THE FOLDER SUPPORTING DOCUMENTS, |
| MISSING WAS THE SOILS REPORT PREPARED BY ARDAMIN FILE |
| 03-2310 02/06/04. 2010 FBC-B |
| 1803.5.2 QUESTIONABLE SOIL. WHERE THE CLASSIFICATION, |
| STRENGTH OR COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR |
| WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED |
| IN THIS CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE |
| PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION |
| BE CONDUCTED. |
| |
| 5) PAGE 003/ A-1.00 CODE SUMMARY SHEET: |
| 5A) BUILDING CODES THE FLORIDA BUUILDING CODE |
| ACCESSIBILITY IS ITS OWN CODE BOOK NOT CHAPTER 11 AS IN |
| THE ICC. |
| 5B) OCCUPANCY CLASSIFICATION CHAPTER 3 & TABLE 3-A, |
| THERE IS NO TABLE 3-A IN THE 2010 FBC-B. |
| 5C) OCCUPANCY CLASSIFICATION LIST RETAIL TO BE COVERED |
| UNDER 311.3 THE SAME AS OPEN GARAGES PLEASE SEE FBC-B |
| 304.1. |
| 5D) ALLOWABLE EXTERIOR OPENINGS CAN NOT BE VARIFIED, |
| THE PROPERTY LINES HAVE NOT BEEN PROVIDED AND THE |
| DISTANCE AWAY FROM THE PROPERTY LINE. FBC-B TABLE 602 |
| EXTERIOR FIRE RATINGS AND TABLE 705.8 ALLOWABLE |
| OPENINGS. |
| |
| 6) PAGE 004/ A-1.01 (NOTE K)/ 008- A-1.05 ON BOTH |
| SHEETS THERE ARE NOTES TO COMPLY WITH 1207.2 AIR-BORNE |
| SOUND AND 1207.3 STRUCTURE BORNE SOUND. IN NEITHER CASE |
| HAS TESTING REPORTS SUBMITTED PROVIDING CODE |
| COMPLIANCE. PAGE 008 HAD A NOT OF REPORT NGC7005033 BUT |
| NOT SUBMITTED. |
| |
| 7) PAGE 005/ A-1.02 OCCUPANCY & EGRESS PLAN / FIRE WALL |
| SEPARATION. |
| 7A)GROUND FLOOR EGRESS PLAN. BLDG. AREA (2) THE TYPICAL |
| FLOOR PLAN SOUTH VERTICAL EXIT STAIR (2 HOUR RATED |
| STAIR ENCLOSURE EMPTIES INTO A EXIT PASAGEWAY (1023.1) |
| NOT A EGRESS CORRIDOR. WHEN YOU ENTER A VERTICAL EXIT, |
| YOU HAVE TO CONTINUE THAT LEVEL OF PROTECTION THROUGH |
| TO THE EXIT DISCHARGE. 1023.5 OPENINGS AND |
| PENETRATIONS.EXCEPT AS PERMITTED IN SECTION 402.4.6, |
| OPENINGS IN EXIT PASSAGEWAYS OTHER THAN EXTERIOR |
| OPENINGS SHALL BE LIMITED TO THOSE NECESSARY FOR EXIT |
| ACCESS TO THE EXIT PASSAGEWAY FROM NORMALLY OCCUPIED |
| SPACES AND FOR EGRESS FROM THE EXIT PASSAGEWAY. |
| WHERE AN EXIT ENCLOSURE IS EXTENDED TO AN EXIT |
| DISCHARGE OR A PUBLIC WAY BY AN EXIT PASSAGEWAY, THE |
| EXIT PASSAGEWAY SHALL ALSO COMPLY WITH SECTION |
| 1022.2.1. |
| ELEVATORS SHALL NOT OPEN INTO AN EXIT PASSAGEWAY. |
| |
| 402.4.6 SERVICE AREAS FRONTING ON EXIT PASSAGEWAYS. |
| MECHANICAL ROOMS, ELECTRICAL ROOMS, BUILDING SERVICE |
| AREAS AND SERVICE ELEVATORS ARE PERMITTED TO OPEN |
| DIRECTLY INTO EXIT PASSAGEWAYS, PROVIDED THE EXIT |
| PASSAGEWAY IS SEPARATED FROM SUCH ROOMS WITH NOT LESS |
| THAN 1-HOUR FIRE BARRIERS CONSTRUCTED IN ACCORDANCE |
| WITH SECTION 707 OR HORIZONTAL ASSEMBLIES CONSTRUCTED |
| IN ACCORDANCE WITH SECTION 712, OR BOTH. THE MINIMUM |
| FIRE PROTECTION RATING OF OPENINGS IN THE FIRE BARRIERS |
| SHALL BE 1 HOUR. |
| SUCH ROOMS OR AREAS SHALL BE PROTECTED BY AN APPROVED |
| SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| WITH SECTION 903; HOWEVER, THE EXCEPTION IN NFPA 13, |
| STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS, |
| THAT PERMIT THE OMISSION OF SPRINKLERS FROM SUCH ROOMS |
| SHALL NOT BE PERMITTED. |
| |
| PLEASE ALSO NOTE THAT WITH OPENING 208 BEING GATE THIS |
| WILL BE REQUIRED TO BE THE EXIT DOOR WITH CLOSER, THE |
| DOOR WITH A CLOSER AND LATCH WILL REQUIRE ACLEAR FLOOR |
| SPACE SEE ACCESS. CODE FIGURE 404.2.4.1 (C). |
| |
| 7B) GROUND FLOOR EGRESS PLAN. THE INTERIOR SIDE OF THE |
| LOT LINE IS NOT SHOWN NOR IS THE WEST PROPERTY LINE NOT |
| SHOWN. THE POOL AND SUN DECK SHOWS (2) MEANS OF EGRESS |
| FROM THE POOL BUT THE PLANS DO NOT SHOW HOW EGRESS TO |
| THE PUBLIC WAY WILL BE COMPLIED WITH. PLEASE PROVIDE |
| THE DISTANCE FROM THE BUILDING TO THE LOT LINE. THE |
| WEST VERTICAL EXIT ALSO EMPTIES TO THE SIDE CLOSEST TO |
| THE PROPERTY LINE PLEASE PROVIDE COMPLIANCE WITH FBC-B |
| 1027.2-1027.6. |
| |
| 7C) CLUBHOUSE EGRESS PLAN. PLEASE NOTE THERE ARE |
| VARIOUS ROOMS THAT ARE NOT IDENTIFIED ON THIS PLAN, |
| USE, SQ. FOOTAGE AND OCCUPANCY LOADS CAN NOT BE |
| CONFIRMED. 107.3.5.1 MINIUMUM CRITERIA FOR COMMERCIAL |
| BUILDING PLAN REVIEW. |
| |
| 7D) THE FITNESS CENTER SHOWS THE MEANS OF EGRESS GOING |
| THROUGH INTO THE 3 HR RATED VERTICAL EXIT, SHEET A-6.01 |
| STAIR PLAN # 2 IST FLOOR, PLEASE |
| PROVIDE THE HEAD ROOM FROM THE 1ST FLOOR SLAB TO THE |
| MID-LANDING AS PART OF A MEANS OF EGRESS MINIMUM HEAD |
| ROOM FBC-B 1208.2. 1006.3.9 |
| SIGNS INSTALLED AS PROJECTIONS FROM A WALL OR CEILING |
| WITHIN THE MEANS OF EGRESS SHALL PROVIDE VERTICAL |
| CLEARANCE NO LESS THAN 80 INCHES (2134 MM) FROM THE |
| WALKING SURFACE. |
| |
| 7E) PLEASE REVIEW RETAIL SUITES 200, 300 & 400 ALL ARE |
| FIGURED AT 200 FT/ OCC. 1ST FLOOR RETAIL IS FIRURED AT |
| 30 SQ. FT./ OCC. FBC-B TABLE 1004.1.1. |
| |
| 7F) THE MULTI-PURPOSE ROOM IS MISSING FROM THE 1ST |
| FLOOR OCCUPANCY LOAD TABLE FBC-B TABLE 1004.1.1. |
| |
| 7G) THE CLUBHOUSE/ LEASING ROOM IS NOT DEFINED AS TO |
| LOCATION SHEET A-4.11 DOES NOT REFERANCE SUCH AREA. |
| 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 7H) THE RETAIL SPACE WITH 1050 SQ. FT. /30= 52 |
| OCCUPANTS, DOOR 103 WILL NEED TO SWING IN THE DIRECTION |
| OF EGRESS TRAVEL. FBC-B 1008.1.2. |
| |
| 8) PAGE 13/ A-2.00 ARCHITECTURAL SITE REFERENCE PLAN: |
| 8A) IT APPEARS THERE IS A DISCREPANCY IN THE 1ST FLOOR |
| UNIT DESIGN, THE GRAPH SHOWS UNIT TYPES ON THE FIRST |
| FLOOR AS RESIDENTIAL UNITS WHERE AS THE LOWER RIGHT |
| PORTION OF THE PAGE SHOWS (3) RETAIL UNITS. 107.2.1.3 |
| ADDITIONAL INFORMATION REQUIRED, DISCREPANCY IN PLANS. |
| |
| 9) PAGE 42/ A-6.20 : |
| 9A) TRASH ROOM 2ND THROUGH THE 4TH FLOOR SHOW THE WHOLE |
| OF THE TRASH ROOM/ ENCLOSRE AS BEING WITHIN THE 2 HOUR |
| RATING FOR A SHAFT. DETAIL # 6 LABELS THE REFUSE CHUTE |
| ITSELF AS THE SHAFT, THIS IS JUST THE TRASH CHUTE |
| ITSELF. |
| |
| FBC-B 708.13.1 REFUSE AND LAUNDRY CHUTE ENCLOSURES. A |
| SHAFT ENCLOSURE CONTAINING A REFUSE OR LAUNDRY CHUTE |
| SHALL NOT BE USED FOR ANY OTHER PURPOSE AND SHALL BE |
| ENCLOSED IN ACCORDANCE WITH SECTION 708.4. OPENINGS |
| INTO THE SHAFT, INCLUDING THOSE FROM ACCESS ROOMS AND |
| TERMINATION ROOMS, SHALL BE PROTECTED IN ACCORDANCE |
| WITH THIS SECTION AND SECTION 715. OPENINGS INTO CHUTES |
| SHALL NOT BE LOCATED IN CORRIDORS. DOORS SHALL BE SELF- |
| OR AUTOMATIC-CLOSING UPON THE ACTUATION OF A SMOKE |
| DETECTOR IN ACCORDANCE WITH SECTION 715.4.8.3, EXCEPT |
| THAT HEAT-ACTIVATED CLOSING DEVICES SHALL BE PERMITTED |
| BETWEEN THE SHAFT AND THE TERMINATION ROOM. |
| |
| 9B) WITH THE CORRECTED SHAFT THE ACCESS ROOM THAT LEADS |
| FROM THE CORRIDOR TO THE REFUSE SHUTE, THIS AREA WILL |
| NEED TO COMPLY WITH 708.13.3 A 1 HOUR FIRE BARRIER WITH |
| 3/4 HR DOOR SELF CLOSING OR AUTOMATIC CLOSING UPON THE |
| DETECTION OF SMOKE IN ACCORDANCE WITH SECTION |
| 715.4.8.3. |
| |
| 9C) DETAIL # 6 FOR THE TRASH COLLECTION ROOM FAILS TO |
| PROVIDE A FIRE RATING AT THE BOTTOM OF THE SHAFT, (2ND |
| FLOOR LEVEL). SEE FBC-B 708.11 ENCLOSURE AT THE BOTTOM. |
| NOTE THAT THE 3 HOUR FIRE RATED WALLS WOULD MEET THE |
| FIRE RATINGS REQUIRED, ONLY 2 HRS REQUIRED BUT THE |
| OPENING PROTECTIVES WOULD THEN NEED TO BE 1 1/2 HOUR |
| FIRE RATING PER TABLE 715.4. |
| |
| 10) PAGE 40 - 41/ A-8.10- A-8.11 NEITHER ELEVATOR SHOWS |
| COMPLIANCE WITH THE AMBULANCE STRETCHER |
| REQUIREMENTSFBC-B 3002.4. THE ELEVATOR CAR SHALL BE OF |
| SUCH A SIZE AND ARRANGEMENT TO ACCOMMODATE AN AMBULANCE |
| STRETCHER 24 INCHES BY 76 INCHES (610 MM BY 1950 MM) |
| WITH NOT LESS THAN 5-INCH (127 MM) RADIUS CORNERS, IN |
| THE HORIZONTAL, OPEN POSITION AND SHALL BE IDENTIFIED |
| BY THE INTERNATIONAL SYMBOL FOR EMERGENCY MEDICAL |
| SERVICES (STAR OF LIFE). THE SYMBOL SHALL NOT BE LESS |
| THAN 3 INCHES (76 MM) HIGH AND SHALL BE PLACED INSIDE |
| ON BOTH SIDES OF THE HOISTWAY DOOR FRAME. |
| |
| 11) PAGE 25 / A-4.12 THIS COMMENT IS COMMON FOR THE 2ND |
| FLOOR THRU 4TH FLOOR. DETAIL # 4 DOOR # 209 ON THE DOOR |
| SCHEDULE IS INDICATED AS A 45 MINUTE REATED DOOR, |
| PLEASE REVIEW FBC-B 509.5 A FIRE-RESISTANCE RATING OF |
| NOT LESS THAN 3 HOURS AND THE FLOOR AREA IS SUBDIVIDED |
| BY 2-HOUR FIRE-RESISTANCE-RATED FIRE WALLS INTO AREAS |
| OF NOT MORE THAN 3,000 SQUARE FEET . OPENING |
| PROTECTIVES 715.4 2HR FIRE WALL/ 1 1/2 OPENING |
| PROTECTIVES. |
| |
| 12) PAGE 16/ A-3.10. THIS SHEET IS ACTUALLY A-3.41 , |
| SHOULD BE PAGE 23, OUT OF ORDER OF THE INDEX.THE NEXT6 |
| SHEETS ARE NOW OUT OF ORDER TO THE INDEX OF SHEETS. |
| |
| 13 PAGE 17/ A-3.10 THE EXIT ACCESS WALL COMMON TO THIS |
| UNIT HAS A WALL TAG # 21 THIS WALL DOES NOT INDICATE |
| COMPLIANCE WITH FBC-B 1207.2 AIR-BORNE SOUND. WALLS, |
| PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION ASSEMBLIES |
| FOR PIPING; ELECTRICAL DEVICES; RECESSED CABINETS; |
| BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR EXHAUST |
| DUCTS SHALL BE SEALED, LINED, INSULATED OR OTHERWISE |
| TREATED TO MAINTAIN THE REQUIRED RATINGS. THIS |
| REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT ENTRANCE |
| DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT FITTING TO |
| THE FRAME AND SILL. |
| |
| 13) PAGE 18/ A-3.11 THE EXIT ACCESS WALL COMMON TO THIS |
| UNIT HAS A WALL TAG # 21 THIS WALL DOES NOT INDICATE |
| COMPLIANCE WITH FBC-B 1207.2 AIR-BORNE SOUND. WALLS, |
| PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION ASSEMBLIES |
| FOR PIPING; ELECTRICAL DEVICES; RECESSED CABINETS; |
| BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR EXHAUST |
| DUCTS SHALL BE SEALED, LINED, INSULATED OR OTHERWISE |
| TREATED TO MAINTAIN THE REQUIRED RATINGS. THIS |
| REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT ENTRANCE |
| DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT FITTING TO |
| THE FRAME AND SILL. |
| |
| 14A) PAGE 19/ A3.12 THE BATHROOM WALL NEXT TO THE |
| GARDEN TUB DOES NOT HAVE A WALL IDENTIFICATION TAG, |
| SHOW COMPLIANCE WITH FBC-B 1207.2 AIR-BORNE SOUND. |
| |
| 14B) PAGE 19/ A3.12 THE KITCHEN WALL NEXT TO THE SINK |
| HAS A WALL IDENTIFICATION TAG OF 33, THIS WALL DOES NOT |
| HAVE ANY SOUND RATING, SHOW COMPLIANCE WITH FBC-B |
| 1207.2 AIR-BORNE SOUND. |
| |
| 15) PAGE 20/ A3.20 THE EXIT ACCESS WALL COMMON TO THIS |
| UNIT HAS A WALL TAG # 21 THIS WALL DOES NOT INDICATE |
| COMPLIANCE WITH FBC-B 1207.2 AIR-BORNE SOUND. |
| |
| 16A) A3.21 THE EXIT ACCESS WALL COMMON TO THIS UNIT HAS |
| A WALL TAG # 21 THIS WALL DOES NOT INDICATE COMPLIANCE |
| WITH FBC-B 1207.2 AIR-BORNE SOUND. |
| |
| 16B) MASTER BATH GARDEN TUB WALL THAT BACKS UP TO |
| SHAFT, NO SHAFT IS SHOWN WALL TAG# 30 , WALL TYPE 30 |
| DOES NOT PROVIDE COMPLIANCE WITH FBC-B 1207.2 AIR-BORNE |
| SOUND. |
| |
| 17) A3.22 WALL TAGS 33 & 35, BOTH OF THESE WALLS DO NOT |
| PROVIDE COMPLIANCE WITH FBC-B 1207.2 AIR-BORNE SOUND. |
| |
| 18) PAGE 25, A4.12 HVAC SHAFT, THIS COMMENT STANDS FOR |
| ALL FLOORS, WALL TAG # 30 DOES NOT SHOW COMPLIANCE WITH |
| FBC-B 1207.2 AIR-BORNE SOUND. |
| |
| 19) PAGE 43/ A7.01 GUARD RAILINGS FOR BALCONIES. |
| DETAILS 3, 10 & 11 SHOW GUARD RAIL ATTACHMENT TO THE |
| STRUCTURE WITH EXSPANSION BOLTS. THERE IS A NOTE ON THE |
| PLANS THAT THE CONNECTION DETAILS ARE TO BE DESIGNED BY |
| A ENGINEER LICENSED IN THE STATE OF FLORIDA. WHAT THE |
| DESIGNER OF RECORD FAILED TO PROVIDE IS THE |
| REQUIREMENTS OF THE CODE FOR THE ENGINEER TO FOLLOW. |
| 2010 FBC-B 1607.7.1 HANDRAILS AND GUARDS. |
| 1607.7.1.1 CONCENTRATED LOAD. |
| 1607.7.1.2 COMPONENTS. |
| |
| 20) PAGE 44/ A-7.02 & S-7.04 VARIOUS DETAILS AND DESIGN |
| ARE SHOWN FOR CANOPY AND AWNINGS, THERE IS NO |
| ATTACHMENT INFORMATION NOR IS THERE A PROPOSED WIND |
| DESIGN PARAMETERS FOR THE SPECIALTY ENGINEER TO DESIGN. |
| FBC-B 3105. |
| |
| 21) PAGE 45/ A-7.03 ROOF DETAILS NOR THE ENERGY |
| CALCULATIONS PROVIDE WHAT THE MINIMUM ROOF INSULATION |
| IS THAT IS REQUIRED. NOTE THE ENERGY FORMS ARE NOT |
| CORRECT, THE FRONT PAGE IS FOR A 1 STORY BUILDING, |
| PAGES 33-34 BOTH SHOW A VALUE OF R-21.2 PLEASE PROVIDE |
| HOW CODE COMPLIANCE WITLL BE ACHIEVED. WHOLE BUILDING |
| METHOD FL ENERGY 506.2.1. |
| |
| 22) PAGE 49/ S1.01 THE GENERAL NOTE # 3 PROVIDES THE |
| WIND DESIGN CRITERIA BUT DOES NOT EXPLAIN MORE THAN |
| COMPONENTS AND CLADDING (VASD) +54.14/ -70.75 PSF. THIS |
| PRESSURE DOES NOT INDICATE FOR WHAT SQ. FT. THIS |
| DESIGNED FOR, NOR DOES IT PROVIDE FOR WHAT ZONE, ROOF |
| OR WALL. |
| PLEASE PROVIDE A VULT AND VASD SCHEDULE FOR ZONES, 1, |
| 2, 3, 4 & 5 FOR 10 SQ. FT., 20 SQ. FT, 50 SQ. FT. & 100 |
| SQ. FT. THE TABLES IN THE CODE BOOKS ARE NOT GOOD ABOVE |
| 60 FT. FBC-B TABLE 1609.6.2./ COMPONENTS AND CLADDING |
| 1709.6.4.4.1. |
| NOTE WITHOUT THIS INFORMATION THE SUBMITTED PRODUCT |
| APPROVALS CAN NOT BE REVIEWED FOR CODE COMPLIANCE. |
| |
| 23) CELCORE LIGHTWEIGHT INSULATING CONCRETE NOA |
| 13-0307.02 CIRCLE THE SUS-SYSTEM THAT IS TO BE USED ON |
| THIS PROJECT AND THE ASSOCIATED PRESSURES. 107.2.1.3 |
| ADDITIONAL INFORMATION IS REQUIRED. 107.2.1.2 FOR ROOF |
| ASSEMBLIES REQUIRED BY THE CODE, THE CONSTRUCTION |
| DOCUMENTS SHALL |
| ILLUSTRATE, DESCRIBE AND DELINEATE THE TYPE OF ROOFING |
| SYSTEM, MATERIALS, FASTENING REQUIREMENTS, FLASHING |
| REQUIREMENTS AND WIND RESISTANCE RATING THAT ARE |
| REQUIRED TO BE INSTALLED. PRODUCT EVALUATION AND |
| INSTALLATION SHALL INDICATE COMPLIANCE WITH THE WIND |
| CRITERIA REQUIRED FOR THE SPECIFIC SITE OR A STATEMENT |
| BY AN ARCHITECT OR ENGINEER FOR THE SPECIFIC SITE MUST |
| BE SUBMITTED WITH THE CONSTRUCTION DOCUMENTS. |
| |
| 24) JOHNS MANVILLE NOA 13-0129.20 MODIFIED OVER |
| CONCRETE DECK, CIRCLE WHICH SUB-SYSTEM IS TO BE |
| INSTALLED ON THIS PROJECT, PLEASE NOTE THE DESIGN |
| PRESSURES AND IF LIMITATION 7 OR 9 APPLIES. LIMITATION |
| 7 MAY REQUIRE CALCULATIONS FROM A DESIGN PROFESSIONAL. |
| |
| 25) ALL GLAZED OPENINGS BOTH WINDOWS AND DOORS AND |
| MULLIONS CIRCLE THE TYPE OF GLAZING TO BE INSTALLED, |
| WIDTH, HEIGHT AND ASSOCATED PRESSURES FOR REVIEW. |
| 107.2.1.3 |
| |
| 26) NYSTROM ROOF HATCH NOA 12-0320.30 GOOD FOR +/- |
| 100PSF VASD. SHEET A-6.00 IT APPEARS THERE IS OVER A |
| 3'-0" PARAPET ELIMINATING ZONE 3, THIS UNITWILL NEED TO |
| MEET THE ROOF ZONE PRESSURES FOR ROOF ZONE 3 WILL BE |
| REVIEWED ONCE PRESSURES ARE PROVIED. |
| |
| 27A) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| |
| 27B) THE PRODUCT APPROVALS THAT MAKE UP THE ENVELOPE OF |
| THE BUILDING IF THE CONTRACTOR OR DESIGN PROFESSIONAL |
| ELECT CAN BE A NO FEE DEFERRAL. THIS DOES ALLOW THE |
| CONTRACTOR TO BID OUT THE PROJECT AND SUBMIT THE ACTUAL |
| PRODUCTS THAT WILL BE INSTALLED ON THEIRE PROJECT. A |
| WRITTEN RESPONCE WILL BE REQUIRED IF THIS OPTION IS |
| DESIRED. |
| 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS |
| SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| FOR REVIEW BY THE BUILDING OFFICIAL. |
| DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| SUBMITTAL DOCUMENTS HAVE |
| BEEN APPROVED BY THE BUILDING OFFICIAL. |
| |
| 28) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. FOR DIGITAL |
| PLANS, YOU WILL NEED TO PRINT THE CODE SUMMARY SHEET |
| AND FLOOR PLANS TO SUBMIT TO THE COUNTY FOR REVIEW.WE |
| WILL NEED THE STAMPED SHEET AND THE RECEIPT. PLEASE |
| CALL (561)233-5025 FOR MORE INFORMATION. |
| |
| 29) FOR DIGITAL REVIEW PLEASE SUBMIT A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| |
| TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO |
| HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA |
| TUS.ASPX FOR PERMIT STATUS. |
| |
| JAMES A. WITMER CBO |