Date |
Text |
2015-01-06 11:04:07 | 1ST REVIEW: FBC 2010 |
| |
| THE SUBMITTAL DOCUMENTS ARE A PHOTO COPY OF A PLAN FROM |
| 1977 AND WITHIN THE TITLE BLOCK RALPH S. MOE JR, IS |
| INDICATED AS THE ARCHITECT. USE OF THIS DRAWING IS NOT |
| CONSISTANT WITH FBC-107.1 GENERAL OR FAC 61G1-16.004. |
| ADDITIONALLY, THE SKETCH UPON THE DRAWING INDICATES TWO |
| SEPARATE UNITS ARE TO BE CREATED WHERE ONE UNIT |
| PERVIOUSLY WAS. THE DRAWING IS INADEQUATE TO DETERMINE |
| THE INTENT OF THE IMPROVENEMT AND IF THE EXISTING |
| ELECTRICAL, MECHANICAL, AND LIFE SAFTEY SYSTEMS ARE |
| ADEQUATE. |
| |
| |
| FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS |
| SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING |
| OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND |
| SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, |
| AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE |
| OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS |
| EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS |
| AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE |
| OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO |
| SECTION 107.3.5). |
| |
| |
| STEVEN KENNEDY, CBO |
| CHIEF PLANS EXAMINER |