2015-03-07 17:38:04****PROVISO****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 CONTRACTOR HAS ELECTED NOT TO SUBMIT FIXTURE CALCS
 DURING PLAN REVIEW.
  
 CONTRACTOR TO PROVIDE FIXTURE CALCS AT INSPECTION.
 SUBJECT TO FIELD INSPECTOR'S DISCRETION, A REVISION
 (WITH FEES) MAY BE REQUIRED. IF THIS IS NOT ACCEPTABLE
 TO THE CONTRACTOR, HE SHOULD NOT PICK UP THE PERMIT AND
 SHOULD RESUBMIT WITH FIXTURE CALCS.
  
 PER ENGINEER'S CALCS:
  
 FIXTURE TO BE MOUNTED AT 25' ABOVE BOTTOM OF BASE PLATE
 OR TRANSFORMER PLATE
 FIXTURE EPA NOT TO EXCEED 2.4 SF
 FIXTURE WEIGHT NOT TO EXCEED 54#
  
  
  