| PROJECT: SITE LIGHTING AUTOZONE |
| PERMIT#: 14120391 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| 1) SHEET E-1 IS PART OF APPLICATION #14110892 FOR THE |
| RENNOVATION OF THE AUTOZONE STORE AND HAS NO BEARING ON |
| THE INSTALLATION OF THE SITE LIGHTING. |
| |
| 2) SHEET E-4 IS ALSO PART OF APPLICATION #14110892 FOR |
| THE RENNOVATION OF THE AUTOZONE STORE AND HAS NO |
| BEARING ON THE INSTALLATION OF THE SITE LIGHTING. |
| |
| 3) IT APPEARS THERE IS A NEW SITE LIGHTING CIRCUIT |
| PROPOSED FROM PANEL A" PROVIDE A PANEL SCHEDULE FOR |
| PANEL A. |
| |
| 4) THERE IS A SYMBOL INDICATED FOR WALL PACKS ON THE |
| EXTERIOR OF THE NEW AUTOZONE ADITION. IS THIS A PART OF |
| THE SITE LIGHTING SCOPE? IF SO INCLUDE THE CIRCUITRY |
| THAT FEEDS THEM. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |