2014-12-30 16:26:2412/30/2014
 PROJECT: SITE LIGHTING AUTOZONE
 PERMIT#: 14120391
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) SHEET E-1 IS PART OF APPLICATION #14110892 FOR THE
 RENNOVATION OF THE AUTOZONE STORE AND HAS NO BEARING ON
 THE INSTALLATION OF THE SITE LIGHTING.
  
 2) SHEET E-4 IS ALSO PART OF APPLICATION #14110892 FOR
 THE RENNOVATION OF THE AUTOZONE STORE AND HAS NO
 BEARING ON THE INSTALLATION OF THE SITE LIGHTING.
  
 3) IT APPEARS THERE IS A NEW SITE LIGHTING CIRCUIT
 PROPOSED FROM PANEL A" PROVIDE A PANEL SCHEDULE FOR
 PANEL A.
  
 4) THERE IS A SYMBOL INDICATED FOR WALL PACKS ON THE
 EXTERIOR OF THE NEW AUTOZONE ADITION. IS THIS A PART OF
 THE SITE LIGHTING SCOPE? IF SO INCLUDE THE CIRCUITRY
 THAT FEEDS THEM.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]