Plan Review Notes
Plan Review Notes For Permit 14120391
Permit Number 14120391
Review Stop B
Sequence Number 1
Notes
Date Text
2015-01-07 12:41:19****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. LIGHT POLE CALCULATIONS USE RISK CATEGORY II,
 160MPH. RISK CATEGORY I IS TO BE A MINIMUM OF 150MPH,
 RISK CATEGORY II AT THIS LOCATION IS 169MPH (170MPH IS
 "WORST CASE" FOR THIS JURISDICTION). PLEASE REVISE
 CALCS; 160MPH IS ACCEPTABLE BUT MUST STATE RISK
 CATEGORY 1.
  
 2. THE ENGINEER'S SEAL (DANNY EUGENE DOSS, PE) ON
 SHEETS SL1, P1.0 (AND ANY OTHER APPLICABLE SHEETS) USE
 AN EXPIRED SEAL ("CERTIFICATE" RATHER THAN "LICENSE"),
 FAC61G15-23, PLEASE CORRECT.
  
 3. ENGINEERING FOR FIXTURES CAN BE PROVIDED NOW OR WILL
 BE REQUIRED AT INSPECTION, FBC 1609.
  