2014-12-11 07:50:41BUILDING PLAN REVIEW
 PERMIT: 14120368
 ADD: 600 S. DIXIE HWY SUITE # 705
 CONT: MOSS DEVCO INC.
 TEL: (561)644-0302
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. DEC. 11/2014
 ACTION: DENIED
  
 1) THE SUBMITTED PRODUCT ECO-ULTRA QUIET SOUND
 TRANSMITION CLASS/ RATING WAS TESTED TO THE WRONG ASTM,
 IT WAS TESTED TO ASTM E90-04. PLEASE REVIEW: 2010 FBC-B
 1207.3 STRUCTURE-BORNE SOUND. FLOOR/CEILING ASSEMBLIES
 BETWEEN DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A
 PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE
 AN IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS
 THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE
 WITH ASTM E 492.
  
 THE CORRECT FLAME SPREAD TEST WAS PROVIDED. ASTM E84.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676