Notes |
Date |
Text |
2014-12-10 16:19:17 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PROVISO: | | | | VENT PIPE APPEARS TO BREECH THE GENERATOR ROOM RATED | | WALL. CONFIRM THAT THE WALL IS RATED WHICH REQUIRES A | | FIRE DAMPER. ADDITIONALLY, PROVIDE A U.L. RATING | | LISTING TO PROTECT THE AREA AROUND THE VENT ON EACH | | SISE OF THE WALL. | | | | SEPARATE SHOP DRAWING ARE REQUIRED FOR THE PRE-ACTION | | SYSTEM. |
|