2015-03-12 14:32:04RESIDENTIAL (R3) ADDITION/ALTERATION SECOND MECHANICAL
 REVIEW COMMENTS
 CODE: 2010 FBC.
  
 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS. ONLY
 THE AIR SYSTEM SIZING SUMMARY WAS PROVIDED A THIS TIME.
 THE EQUIPMENT SIZING CALCULATIONS NEEDS TO BE DONE
 BASED ON THE BUILDING LOADS FOR THE DIRECTIONAL
 ORIENTATION OF THE BUILDING AS REQUIRED BY SEC. 403.6
 OF 2010 FBC-ENERGY CONSERVATION. NEED COMPLETE
 CALCULATIONS TO VERIFY BUILDING ORIENTATION.
  
 2- ITEM #13 OF THE ENERGY CALCULATIONS SHOWS ONLY ONE
 HEATING SYSTEM (SYS#1). NEED HEATING FOR ALL HABITABLE
 ROOMS. SEC. R303.8 OF 2010 FBC-RESIDENTIAL. COORDINATE
 THE EQUIPMENT SIZING CALCULATIONS AND THE ENERGY
 CALCULATIONS TO COMPLY WITH THE HEATING REQUIREMENTS OF
 SEC. R303.8.
  
 *** PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS..
 *** PLEASE REPLACE AND REMOVE ANY REVISED SHEET..
 SUBMIT OLD SHEETS FOR REFERENCE.
  