2015-03-10 07:59:24RESIDENTIAL (R3) ADDITION/ALTERATION SECOND BUILDING
 REVIEW COMMENTS.
 CODE: 2010 BC.
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ROOF TILE AS SPECIFIED ON PLANS. (REPEAT COMMENT.
 NOT ADDRESSED).
  
 B) ROOF TILE ADHESIVE IF SPECIFIED BY THE DESIGNER OF
 RECORD. SEE ROOFF TILE NOA FOR LISTED ADHESIVE. (REPEAT
 COMMENT. NOT ADDRESSED).
  
 C) FLAT ROOF AS SPECIFIED ON PLANS. AND IDENTIFY
 APPROVED ASSEMBLY TO BE INSTALLED AND PROVIDE SIGNED
 AND SEALED RAS 117 CALCULATIONS IF DESIGN PRESSURES ON
 SELECTED ASSEMBLY DON'T MEET THE DESIGN PRESSURES OF
 SEC. R301 OF 2020 FBC-RESIDENTIAL. (REPEAT COMMENT. NOT
 ADDRESSED).
  
 D) COPPER ROOF AS SPECIFIED ON PLANS. (REPEAT COMMENT.
 NOT ADDRESSED).
  
 E) GARAGE DOORS SIZE AND TYPE AS SPECIFIED ON PLANS.
 (REPEAT COMMENT. NOT ADDRESSED).
  
 G) ALL WINDOW TYPES AS SPECIFIED ON PLANS. (REPEAT
 COMMENT. NOT ADDRESSED).
  
 H) ALL WINDOW MULLIONS AS SHOW ON PLANS. AND, CLEARLY
 IDENTIFY MULLION SIZE TO VERIFY DESIGN PRESSURES.
 (REPEAT COMMENT. NOT ADDRESSED).
  
 I) ALL EXTERIOR DOOR TYPES AND SIZES AS SPECIFIED ON
 PLANS. (REPEAT COMMENT. NOT ADDRESSED).
  
 J) DOORS SHOWN ON SHEET A-2 ON THE LOGGIA BETWEEN
 GARAGE AND MAIN HOUSE. (REPEAT COMMENT. NOT ADDRESSED).
  
 K) CUSTOM MAHOGANY ENTRY DOOR SIZE AND TYPE AS SHOWN ON
 PLANS. (REPEAT COMMENT. NOT ADDRESSED).
  
 L) BALCONY FLOOR ASSEMBLY SPECIFIED ON PLANS. (REPEAT
 COMMENT. NOT ADDRESSED).
  
 M) ALL STRUCTURAL CONNECTORS SPECIFIED ON THE
 STRUCTURAL PLANS AND DETAILS. THIS COMMENT WAS
 PARTIALLY ADDRESSED. ONLY THE FLORIDA PRODUCT APPROVAL
 NUMBERS WERE GIVEN ON THE ROOF TRUSS CONNECTOR SCHEDULE
 ON SHEET S-4. NEED THE FLORIDA PRODUCT APPROVAL NUMBER
 LISTED NEXT TO EACH SPECIFIED CONNECTOR IN ALL DETAILS
 AND SPECIFICATIONS SHOWN ON PLANS.
  
 N) GABLE END VENTILATION LOUVERS SHOWN ON PROPOSED
 ELEVATIONS.
  
 O) PRECAST LINTELS AS SPECIFIED ON BEAM SCHEDULE ON
 SHEET S-4.
  
 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL THE PRODUCT APPROVALS.
 SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC.
  
 3- ENERGY CALCULATIONS SUBMITTED:
 A) OWNER/AGENT O SING AND DATE BOTTOM OF FORM. SEC.
 103.2.3.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 B) CONDITIONED FLOOR AREA ON ITEM #6 DOESN'T MATCH
 PLANS. SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 C) COORDINATE ALL CEILINGS, WALLS, FLOOR INSULATION
 WITH INFORMATION SHOWN ON PLANS. SEC. 103.2.2 OF 2010
 FBC-ENERGY CONSERVATION.
  
 D) ITEM #13 SHOWS ONLY ONE HEATING SYSTEM (SYS#1). NEED
 HEATING FOR ALL HABITABLE ROOMS. SEC. R303.8 OF 2010
 FBC-RESIDENTIAL.
  
 E) REVISE TYPE OF ROOF AND ROOF MATERIALS ON PAGE 2 OF
 6 TO MATCH PLANS. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 F) REVISE ALL WALL TYPES ON PAGE 3 OF 6 TO MATCH WALL
 TYPES SHOWN PLANS. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 G) COMPLETE ALL THE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER, BUILDER, PERMIT OFFICE AND
 JURISDICTION #. SEC. 103.2.1.1.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 4) DESIGNER OF RECORD TO PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS SHOWING HOW THE R30 BUTT INSULATION IS
 GOING TO BE INSTALLED BELOW THE ROOF SHEATHING AS SHOWN
 ON PLANS. SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 5) DESIGNER OF RECORD TO PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS SHOWING COMPLIANCE WITH THE ROOF
 VENTILATION. SEC. R806 OF 2010 FBC-RESIDENTIAL.
 COORDINATE WITH THE ENERGY CALCULATIONS.
  
 6) DEMOLITION NOTES ON SHEET S-1, SHEET A-1, SHEET A-3,
 SHEET A-5:
 A) REVISE NOTE #1. THERE ARE NOT 2009 SUPPLEMENTS TO
 THE 2010 FBC. SEC. 107.2.1 CITY AMENDMENTS. (REPEAT
 COMMENT. NOT ADDRESSED).
  
 B) PROVIDE THE NAME OF THE ARCHITECT MENTIONED ON NOTE
 #4. AND PLANS NEED TO BE PROPERLY SIGNED AND SEALED AS
 REQUIRED BY CHAPTER 481 FL. ST. (REPEAT COMMENT. NOT
 ADDRESSED).
  
 7- REVISE GENERAL NOTES #1 AND #2 ON SHEET A-2. THE
 CORRECT CODE IS 2010 (NOT 20010) AND IS CITY OF WEST
 PALM BEACH (NOT TOWN). (REPEAT COMMENT. NOT ADDRESSED).
 SEC. 107.2.1 CITY AMENDMENTS.
  
 8- PROVIDE COMPLETE ENGINEER DETAILS AND SPECIFICATIONS
 FOR BEARING PARTITION TO BE REMOVED AS SPECIFIED ON
 SHEET A-1. SEC. R301 OF 2010 FBC-RESIDENTIAL AND SEC.
 107.2.1.3 CITY AMENDMENTS.
 ***NOTE: ALSO, PROVIDE COMPLETE ENGINEERING DETAILS AND
 SPECIFICATIONS INCLUDING SHORING DETAILS AND
 SPECIFICATIONS FOR INTERIOR AND EXTERIOR WALLS ON FIRST
 FLOOR TO BE DEMOLISHED. (REPEAT COMMENT. NOT
 ADDRESSED).
  
 9- EXISTING HOUSE WAS DESIGNED FOR ROOF SHINGLES.
 PROVIDE ENGINEERING ANALYSIS SHOWING THAT EXISTING
 STRUCTURE IS ADEQUATE TO TAKE THE ADDITIONAL LOAD OF
 CONCRETE ROOF TILES. SEC. 107.2.1.3 CITY AMENDMENTS.
 (REPEAT COMMENT. NOT ADDRESSED).
  
 10- SHEET A-1: STAIRWAY NOTE STATES "STAIR TO
 REMAIN/RAILING TO BE REPLACED". PROVIDE COMPLETE
 DETAILS AND SPECIFICATIONS FOR THE NEW HANDRAIL AND
 GUARDRAIL SHOWING COMPLIANCE WITH TABLE R301.5 AND SEC.
 R311.7.7 AND R312 OF 2010 FBC-RESIDENTIAL. (REPEAT
 COMMENT. NOT ADDRESSED).
  
 11- THIS PROPERTY IS LOCATED IN FLOOD ZONE A5 WITH A
 BASE FLOOD ELEVATION OF 7"-0" . CITY ORDINANCE REQUIRES
 FINISH FLOOR ELEVATION TO BE 6" ABOVE BASE FLOOR
 ELEVATION. THE FINISH FLOOR ELEVATION SHOWN ON ALL
 PLANS DON'T MATCH. (REPEAT COMMENT) REVISE ALL OF THEM
 TO MATCH. NEED COMPLETE AND CORRECT INFORMATION TO
 VERIFY COMPLIANCE WITH FLOOD RESISTANT CONSTRUCTION
 SEC. R322 OF 2010 FBC-RESIDENTIAL.
 ***NOTE: SEE SAMANTA HILL COMMENTS ON DEMOLITION
 PERMIT. #14120500.
  
 12- PROVIDE DETAILS AND SPECIFICATIONS FOR THE FLAT
 ROOF SLOPE SHOWING COMPLIANCE WITH SEC. R905.11.1 OF
 2010 FBC-RESIDENTIAL. (REPEAT COMMENT. NOT ADDRESSED).
  
 13- DESIGNER OF RECORD TO PROVIDE
 DETAILS/SPECIFICATIONS FOR THE ROOF ASSEMBLIES,
 INCLUDING ROO TILE FASTENING AS REQUIRED BY SEC.
 107.2.1.2 CITY AMENDMENTS. IF USING SCREWS, THEN
 SPECIFY SIZE AND NUMBER OF SCREWS. (REPEAT COMMENT. NOT
 ADDRESSED).
  
 14- SHEET A-7: NEW COVERED ENTRY ROOF DOESN'T MATCH
 PROPOSED ROOF ON SHEET A-6. IT'S MISSING THE RIDGE.
 REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY
 AMENDMENTS. (REPEAT COMMENT. NOT ADDRESSED).
  
 15- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 PROPOSED ROOF VENTILATION SHOWN ON GABLE ENDS ON SHEET
 A-8. AND PROVIDE COMPLETE DETAILS AND SPECIFICATIONS
 FOR CROSS VENTILATION FOR ALL ROOFS TO SHOW COMPLIANCE
 WITH SEC. R806 OF 2010 FBC-RESIDENTIAL. (REPEAT
 COMMENT. NOT ADDRESSED).
  
 16- SECTION 2 ON SHEET A-11: REVISE THE ROOF SHEATHING
 SPECIFICATION. NEED SOLID ROOF SHEATHING OR PROVIDE
 COMPLIANCE WITH THE DESIGN AND TESTING REQUIRED BY SEC.
 R905.3.1 OF 2010 FBC-RESIDENTIAL. (REPEAT COMMENT. NOT
 ADDRESSED).
  
 17- SPECIFY CARBON MONOXIDE ALARMS FOR ALL BEDROOM
 SHOWING COMPLIANCE WITH SEC. R315 OF 2010
 FBC-RESIDENTIAL. (REPEAT COMMENT. NOT ADDRESSED).
 ***NOTE: IDENTIFY ON PLANS SPECIFIC LOCATION FOR EACH
 REQUIRED ALARM.
  
 18- PROPERTY IS LOCATED IN FLOOD ZONE A5. THE BASE
 FLOOD ELEVATION IS 7.0'. THE MIN. FINISHED FLOOR
 ELEVATION REQUIRED FOR THE NEW ADDITION, EXISTING HOUSE
 AND EQUIPMENT IS 7.6'. ELEVATION CERTIFICATES WILL BE
 REQUIRED DURING CONSTRUCTION. SEC. R322 AND SEC. AND
 CITY CODE SEC. 94-546.
 ***NOTE: DRAWINGS SUBMITTED SHOW FINSIHED FLOOR
 ELEVATION OF MAIN HOUSE @ 8.15' NGVD. PROVIDE COPY OF
 SURVEY SHOWING THE FINISHED FLOOR ELEVATIONS OF
 EXISTING AND PROPOSED STRUCTURE AND EQUIPMENT.
 COORDINATE FINISH FLOOR ELEVATIONS ON ALL PLANS.
  
 19- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 BALCONY DECK CONSTRUCTION ASSEMBLY. SEC. R301.1 OF 2010
 FBC-RESIDENTIAL. (REPEAT COMMENT. NOT ADDRESSED).
  
 20- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 BALCONY GUARDRAILS SHOWING COMPLIANCE WITH THE LIVE
 LOADS OF TABLE R301.5 AND REQUIREMENTS OF SEC. R312 OF
 2010 FBC-RESIDENTIAL. (REPEAT COMMENT. NOT ADDRESSED).
 ***NOTE: DIMENSIONS SHOWN ON BALCONY DETAIL C/A-13
 DON'T COMPLY WITH SEC. R312.
  
 21- PROVIDE COMPLETE MANUFACTURER SPECIFICATIONS FOR
 THE FIREROCK NON VENTED FIREPLACE SHOWING COMPLIANCE
 WITH TESTING IN ACCORDANCE WITH UL 127 AS REQUIRED BY
 SEC. R1004 OF 2010 FBC-RESIDENTIAL.
 ***NOTE: DESIGNER OF RECORD TO REVIEW AND APPROVE SPECS
 PRIOR TO SUBMITTAL. (REPEAT COMMENT. NOT ADDRESSED).
  
 22- NEW COMMENT: ARCHITECTURAL PLANS AND ENGINEER PLANS
 DON'T MATCH. FOR EXAMPLE ROOF OVER PROPOSED LOGGIA IS
 DIFFERENT. REVISE AND COORDINATE ALL PLANS AS REQUIRED
 TO MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 23- NEW COMMENT: NEW ENGINEER'S DRAWINGS SHOW GARAGE
 WITH A FINISHED FLOOR ELEVATION OF 6'-10". THE MINI.
 FINISHED FLOOR ELEVATION REQUIRED IS 7'-6". OTHERWISE
 SHOW COMPLIANCE WITH THE REQUIREMENTS OF FLOOD
 -RESISTANT CONSTRUCTION OF SEC. R322 OF 2010
 FBC-RESIDENTIAL.
  
 24- ENGINEER TO PROVIDE COMPLETE SECTION/DETAIL THRU
 THE PROPOSED LOGGIA COLUMN FOOTINGS AND STEPS AND AND
 EXISTING POOL. SEC. 107.2.1 CITY AMENDMENTS.
  
 25- SHEET S-4:
 A) WIND LOAD SCHEDULE TABLE:
 (1) WHAT'S (4:12). IS THIS THE ROOF PITCH?. IF SO, IT
 DOESN'T MATCH ARCHITECTURAL PLANS. REVISE AS REQUIRED
 TO MATCH. SEC. 107.2.1 CITY AMENDMENTS.
 (2) REVISE THE ROOF WIND LOADS. THEY DON'T CORRESPOND
 TO EXPOSURE "D" ACCORDING TO THE MEAN ROO HEIGHT OF THE
 HOUSE. SEC. R301 OF 2010 FBC_RESIDENTIAL.
 (3) REVISE THE WALL WIND LOADS. WHY THE TRIBUTARY AREA
 IS 50S.F.?. REVISE TRIBUTARY AEA AS REQUIRED BY
 FOOTNOTES ON TABLE R301.2(2) OF 2010 FBC-RESIDENTIAL.
 REVISE THE DESIGN PRESSURES ON SHEET S-5 ACCORDINGLY.
 (4) ROOF ZONE #3 IDENTIFIED ON THE PLAN SKETCH IS
 WRONG. SEE FIGURE R301.2(7) OF 2010 FBC-RESIDENTIAL AND
 REVISE AS REQUIRED.
  
  
 B) DESIGN LOAD SCHEDULE. CLEARLY SPECIFY ALL LIVE AN
 DEAD LOADS, INCLUDING THE ATTIC LIVE LOAD AS REQUIRED
 BY FOOTNOTES ON TABLE R301.5 OF 2010 GBC-RESIDENTIAL.
  
 *** PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS..
 *** PLEASE REPLACE AND REMOVE ANY REVISED SHEET..
 SUBMIT OLD SHEETS FOR REFERENCE.
  
 (NOTE: SEE SAMANTHA'S COMMENTS ON DEMOLITION PERMIT
 #14120500).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT