Plan Review Notes For Permit 14120262 |
Permit Number |
14120262 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-02-18 10:48:16 | 1) THE ARCHITECTURAL PLANS SHALL BE SIGNED & SEALED PER | | THE FL. ADMINISTRATIVE CODE RULE 61G1-16.001. | | 2) SUBMIT MANUFACTURER'S SPECICATIONS FOR ALL THE GAS | | EQUIPMENT/APPLIANCES. APPLIANCES SHALL BE LISTED AND | | LABELED PER THE 2010 FBCR SEC.G2404.3. | | 3) THE 2" PE PIPE FOR THE FUTURE GENERATOR AND THE TWO | | TANKLESS WATER HEATERS IS UNDERSIZED. TABLE G2413.4 (7) | | LIMITS THE 2" PE PIPE AT 90 FEET TO 1,040,000 BTU'S. | | THE LOAD ON THIS LINE WILL BE 1, 151, 225. THIS LINE | | WOULD HAVE TO BE A 2 PSI SYSTEM TO WORK. | | 4) SHOW THE LENGTH OF EACH SECTION OF GAS PIPE. WWPB | | AMEND. TO 2010 FBC SEC. 107.2.1. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|