2015-02-18 10:48:161) THE ARCHITECTURAL PLANS SHALL BE SIGNED & SEALED PER
 THE FL. ADMINISTRATIVE CODE RULE 61G1-16.001.
 2) SUBMIT MANUFACTURER'S SPECICATIONS FOR ALL THE GAS
 EQUIPMENT/APPLIANCES. APPLIANCES SHALL BE LISTED AND
 LABELED PER THE 2010 FBCR SEC.G2404.3.
 3) THE 2" PE PIPE FOR THE FUTURE GENERATOR AND THE TWO
 TANKLESS WATER HEATERS IS UNDERSIZED. TABLE G2413.4 (7)
 LIMITS THE 2" PE PIPE AT 90 FEET TO 1,040,000 BTU'S.
 THE LOAD ON THIS LINE WILL BE 1, 151, 225. THIS LINE
 WOULD HAVE TO BE A 2 PSI SYSTEM TO WORK.
 4) SHOW THE LENGTH OF EACH SECTION OF GAS PIPE. WWPB
 AMEND. TO 2010 FBC SEC. 107.2.1.
  