2015-01-05 10:33:38 | RESIDENTIAL (R3) ADDITION/ALTERATION, BUILDING REVIEW |
| COMMENTS |
| CODE: 2010 FBC. |
| |
| 1- AFTER PLANS ARE REVISED BRING THEM TO PALM BEACH |
| COUNTY (2300 N. JOG RD.) TO VERIFY IF IMPACT FEES ARE |
| DUE. BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID |
| RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF |
| THE UNIFIED LAND DEVELOPMENT CODE. |
| |
| 2- NO STRUCTURAL DRAWINGS WERE SUBMITTED. PROVIDE |
| COMPLETE SET OF STRUCTURAL DRAWINGS AS REQUIRED BY SEC. |
| 107.3.5.3 (5) OF CITY AMENDMENTS TO FBC. |
| |
| 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| DCA RULE 9N-3 FOR: |
| A) ROOF TILE AS SPECIFIED ON PLANS. |
| |
| B) ROOF TILE ADHESIVE IF SPECIFIED BY THE DESIGNER OF |
| RECORD. SEE ROOF TILE NOA FOR LISTED ADHESIVE. |
| |
| C) FLAT ROOF AS SPECIFIED ON PLANS. AND IDENTIFY |
| APPROVED ASSEMBLY TO BE INSTALLED AND PROVIDE SIGNED |
| AND SEALED RAS 117 CALCULATIONS IF DESIGN PRESSURES ON |
| SELECTED ASSEMBLY DON'T MEET THE DESIGN PRESSURES OF |
| SEC. R301 OF 2020 FBC-RESIDENTIAL. |
| |
| D) COPPER ROOF AS SPECIFIED ON PLANS. |
| |
| E) ALL STRUCTURAL CONNECTORS SPECIFIED ON THE |
| STRUCTURAL PLANS AND DETAILS. |
| |
| F) GARAGE DOORS SIZE AND TYPE AS SPECIFIED ON PLANS. |
| |
| G) ALL WINDOW TYPES AS SPECIFIED ON PLANS. |
| |
| H) ALL WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY |
| IDENTIFY MULLION SIZE TO VERIFY DESIGN PRESSURES. |
| |
| I) ALL EXTERIOR DOOR TYPES AND SIZES AS SPECIFIED ON |
| PLANS. |
| |
| J) DOORS SHOWN ON SHEET A-2 ON THE LOGGIA BETWEEN |
| GARAGE AND MAIN HOUSE. |
| |
| K) CUSTOM MAHOGANY ENTRY DOOR SIZE AND TYPE AS SHOWN ON |
| PLANS. |
| |
| L) BALCONY FLOOR ASSEMBLY SPECIFIED ON PLANS. |
| |
| 4- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| ALL THE PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 |
| OF CITY AMENDMENTS TO FBC. |
| |
| 5- PROVIDE ENERGY CALCULATIONS. SEC. 101.4.3 OF 2010 |
| FBC-ENERGY CONSERVATION. AND, COORDINATE INFORMATION ON |
| ENERGY CALCULATIONS WITH ALL INFORMATION SHOWN ON |
| PLANS. |
| |
| 6- DEMOLITION NOTES ON SHEET S-1, SHEET A-1, SHEET A-3, |
| SHEET A-5: |
| A) REVISE NOTE #1. THERE ARE NOT 2009 SUPPLEMENTS TO |
| THE 2010 FBC. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| B) PROVIDE THE NAME OF THE ARCHITECT MENTIONED ON NOTE |
| #4. AND PLANS NEED TO BE PROPERLY SIGNED AND SEALED AS |
| REQUIRED BY CHAPTER 481 FL. ST. |
| |
| ***NOTE: ALSO REVISE GENERAL NOTES #1 AND #2 ON SHEET |
| A-2. THE CORRECT CODE IS 2010 (NOT 20010) AND IS CITY |
| OF WEST PALM BEACH (NOT TOWN). |
| |
| 7- PROVIDE COMPLETE ENGINEERING ANALYSIS FOR THE |
| CONSTRUCTION OF THE NEW COVERED LOGGIA TO BE SUPPORTED |
| BY THE EDGE OF THE EXISTING POOL. SEC. R301.1 OF 2010 |
| FBC-RESIDENTIAL AND SEC. 107.2.1.3 OF CITY AMENDMENTS |
| TO FBC. |
| |
| 8- PROVIDE COMPLETE ENGINEER DETAILS AND SPECIFICATIONS |
| FOR BEARING PARTITION TO BE REMOVED AS SPECIFIED ON |
| SHEET A-1. SEC. R301 OF 2010 FBC-RESIDENTIAL AND SEC. |
| 107.2.1.3 CITY AMENDMENTS. |
| ***NOTE: ALSO, PROVIDE COMPLETE ENGINEERING DETAILS AND |
| SPECIFICATIONS INCLUDING SHORING DETAILS AND |
| SPECIFICATIONS FOR INTERIOR AND EXTERIOR WALLS ON FIRST |
| FLOOR TO BE DEMOLISHED. |
| |
| 9- PROVIDE ENGINEERING ANALYSIS SHOWING THAT EXISTING |
| STRUCTURE IS ADEQUATE TO TAKE THE ADDITIONAL LOAD OF |
| CONCRETE ROOF TILES. SEC. 107.2.1.3 CITY AMENDMENTS. |
| |
| 10- SHEET A-1: STAIRWAY NOTE STATES "STAIR TO |
| REMAIN/RAILING TO BE REPLACED". PROVIDE COMPLETE |
| DETAILS AND SPECIFICATIONS FOR THE NEW HANDRAIL AND |
| GUARDRAIL SHOWING COMPLIANCE WITH TABLE R301.5 AND SEC. |
| R311.7.7 AND R312 OF 2010 FBC-RESIDENTIAL. |
| |
| 11- SHEET A-2, SHEET A-3 AND SHEET A-5. CLARIFY FINISH |
| FLOOR ELEVATION GIVEN FOR THE EXISTING GARAGE: 10'-1" |
| AND 10.1' ???. SEC. 107.2.1 CITY AMENDMENTS. AND |
| COORDINATE THE FINISH FLOOR ELEVATION FOR MAIN HOUSE, |
| LOGGIA AND EXISTING GARAGE IN ALL DRAWINGS TO MATCH. |
| |
| 12- PROVIDE DETAILS AND SPECIFICATIONS FOR FLAT ROOF |
| DRAINAGE TO SHOW COMPLIANCE WITH SEC. R903.4 OF 2010 |
| FBC-RESIDENTIAL. |
| |
| 13- PROVIDE DETAILS AND SPECIFICATIONS FOR THE FLAT |
| ROOF SLOPE SHOWING COMPLIANCE WITH SEC. R905.11.1 OF |
| 2010 FBC-RESIDENTIAL. |
| |
| 14- DESIGNER OF RECORD TO PROVIDE |
| DETAILS/SPECIFICATIONS FOR THE ROOF ASSEMBLIES, |
| INCLUDING ROO TILE FASTENING AS REQUIRED BY SEC. |
| 107.2.1.2 CITY AMENDMENTS. IF USING SCREWS, THEN |
| SPECIFY SIZE AND NUMBER OF SCREWS. |
| |
| 15- SHEET A-7: NEW COVERED ENTRY ROOF DOESN'T MATCH |
| PROPOSED ROOF ON SHEET A-6. IT'S MISSING THE RIDGE. |
| REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| 16- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| PROPOSED ROOF VENTILATION SHOWN ON GABLE ENDS ON SHEET |
| A-8. AND PROVIDE COMPLETE DETAILS AND SPECIFICATIONS |
| FOR CROSS VENTILATION FOR ALL ROOFS TO SHOW COMPLIANCE |
| WITH SEC. R806 OF 2010 FBC-RESIDENTIAL. |
| |
| 17- SECTION 2 ON SHEET A-11: REVISE THE ROOF SHEATHING |
| SPECIFICATION. NEED SOLID ROOF SHEATHING OR PROVIDE |
| COMPLIANCE WITH THE DESIGN AND TESTING REQUIRED BY SEC. |
| R905.3.1 OF 2010 FBC-RESIDENTIAL. |
| |
| 18- SPECIFY CARBON MONOXIDE ALARMS FOR ALL BEDROOM |
| SHOWING COMPLIANCE WITH SEC. R315 OF 2010 |
| FBC-RESIDENTIAL. |
| |
| 19- PROPERTY IS LOCATED IN FLOOD ZONE A5. THE BASE |
| FLOOD ELEVATION IS 7.0'. THE MIN. FINISHED FLOOR |
| ELEVATION REQUIRED FOR THE NEW ADDITION, EXISTING HOUSE |
| AND EQUIPMENT IS 7.6'. ELEVATION CERTIFICATES WILL BE |
| REQUIRED DURING CONSTRUCTION. SEC. R322 AND SEC. AND |
| CITY CODE SEC. 94-546. |
| ***NOTE: DRAWINGS SUBMITTED SHOW FINSIHED FLOOR |
| ELEVATION OF MAIN HOUSE @ 8.15' NGVD. PROVIDE COPY OF |
| SURVEY SHOWING THE FINISHED FLOOR ELEVATIONS OF |
| EXISTING AND PROPOSED STRUCTURE AND EQUIPMENT. |
| |
| 20- PROVIDE THE NAME IN ALL SHEETS OF THE PERSON |
| RESPONSIBLE FOR THE DESIGN AS REQUIRED BY SEC. 107.2.1 |
| CITY AMENDMENTS. |
| |
| 21- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| BALCONY DECK CONSTRUCTION ASSEMBLY. SEC. R301.1 OF 2010 |
| FBC-RESIDENTIAL. |
| |
| 22- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| BALCONY GUARDRAILS SHOWING COMPLIANCE WITH THE LIVE |
| LOADS OF TABLE R301.5 AND REQUIREMENTS OF SEC. R312 OF |
| 2010 FBC-RESIDENTIAL. |
| |
| 23- PROVIDE COMPLETE INFORMATION FOR POOL ALTERATION |
| UNDER A SEPARATE PERMIT. SEC. 105.1 CITY AMENDMENTS. |
| |
| 24- PROVIDE COMPLETE MANUFACTURER SPECIFICATIONS FOR |
| THE FIREROCK NON VENTED FIREPLACE SHOWING COMPLIANCE |
| WITH TESTING IN ACCORDANCE WITH UL 127 AS REQUIRED BY |
| SEC. R1004 OF 2010 FBC-RESIDENTIAL. |
| ***NOTE: DESIGNER OF RECORD TO REVIEW AND APPROVE SPECS |
| PRIOR TO SUBMITTAL. |
| |
| *** PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS.. |
| *** PLEASE REPLACE AND REMOVE ANY REVISED SHEET. |
| |