Plan Review Notes
Plan Review Notes For Permit 14120261
Permit Number 14120261
Review Stop G
Sequence Number 1
Notes
Date Text
2014-12-10 12:04:061) SUBMIT MANUFACTURER SPECIFICATION SHEETS FOR ALL GAS
 EQUIPMENT. ALL EQUIPMENT SHALL BE LISTED AND LABELED
 PER THE 2010 FL. GAS CODE SEC. 301.3. THIS INFORMATION
 WAS REQUESTED AT THE INTERIOR BUILDOUT REVIEW AND WAS
 NEVER SUBMITTED.
 2) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE
 MOST REMOTE OUTLET.
 3) I AM THOROUGHLY CONFUSED REGARDING THE GAS PIPING
 PRESSURE TABLE THAT WAS SUBMITTED ON THE GAS PLANS.I
 DON'T UNDERSTAND THE TABLE.THE TABLE HAS A COLUMN THAT
 LISTS "SECTION A, B, C", ETC.YET THESES SECTIONS ARE
 NOT SHOWN ON THE GAS PIPING DRAWING. CLARIFY AS TO HOW
 THIS SIZING TABLE MEETS THE INTENT OF THE 2010 FGC
 SEC.402.3.
 4) THE SECTION OF PIPE THAT CROSSES THE CEILING IS
 SIZED AS 1 1/2" WHICH COMPLIES WITH THE GAS CODE BUT
 REDUCES TO 1 1/4" AT A 90 DEGREE TURN.THIS SECTION IS
 STILL UNDER SIZED. IT MUST REMAIN 1 1/2" TO THE FIRST
 BRANCH AND THEN CAN BE REDUCED AFTER THE FIRST
 APPLIANCE.FGC 402.4.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  