2015-01-07 14:40:311/7/2015
 PROJECT: #RD FL SPEC SUITE
 PERMIT#: 14120246
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) INDICATE ON THE PLAN THE RELOCATION OF RADIENT HEAT
 PANELS CIRCUITRY AS WELL AS THE REQUIRED CIRCUITRY AND
 DISCONNECTS FOR THE INSTALLATION OF VAV BOXES SHOWN ON
 MECHANICAL PLANS.
  
 2) PROVIDE REVISED ELECTRICAL CIRCUIT DIRECTORY TO
 IDENTIFY ANY MODIFICATION OF EXISTING CIRCUITRY AND
 ADDITION OF ANY NEW CIRCUITRY REQUIRED FOR INSTALLATION
 OF NEW EQUIPMENT. EVERY CIRCUIT AND CIRCUIT
 MODIFICATION SHALL BE LEGIBLY IDENTIFIED AS TO ITS
 CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. NEC 408.4
  
 3) PROVIDE A LOAD CALCULATION TO TAKE INTO
 CONSIDERATION THE ADDITION OR INSTALLATION OF ANY NEW
 CIRCUITRY. NEC 220
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]