2014-12-11 16:43:50BUILDING PROVISO:
 3RD FLOOR WORK OVER 50 % OF LEASEABLE FLOOR AREA OF
 FLOOR PLATE WILL NEED TO SHOW CODE
 COMPLIANCE WITH 2010 FL EXISTING BLDG CODE 703.2.2 .
 703.2.2 SUPPLEMENTAL SHAFT AND FLOOR OPENING ENCLOSURE
 REQUIREMENTS.
 WHERE THE WORK AREA ON ANY FLOOR EXCEEDS 50 PERCENT OF
 THAT FLOOR AREA, THE ENCLOSURE
 REQUIREMENTS OF SECTION 703.2 SHALL APPLY TO VERTICAL
 OPENINGS OTHER THAN STAIRWAYS THROUGHOUT THE FLOOR.
 2010 FBC-B 708.14.1 ELEVATOR LOBBIES OR EXCEPTIONS.
 EXCEPION #6
 ENCLOSED ELEVATOR LOBBIES ARE NOT REQUIRED WHERE THE
 ELEVATOR HOISTWAY IS PRESSURIZED IN ACCORDANCE WITH
 SECTION 708.14.2.
  
 NOTE: PERMIT # 14090238 IS FOR THE PRESSURIZATION OF
 ELEVATOR SHAFTS.
  