Plan Review Notes
Plan Review Notes For Permit 14120241
Permit Number 14120241
Review Stop P
Sequence Number 1
Notes
Date Text
2014-12-18 05:38:221) SUBMIT 2 COPIES OF MANUF. SPEC SHEETS/INSTALLATION
 MANUAL FOR THE STANCOR EFLUENT PUMP SYSTEM. WPB AMEND.
 TO 2010 FBC SEC. 107.2.1.
 2) SUBMIT MANUF. SPEC SHEETS FOR THE EEMAX
 INSTANTANEOUS WATER HEATER.WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
 3) THE CONNECTION OF THE ELEVATOR SUMP TO THE BUILDING
 DRAINAGE SYSTEM SHALL BE BY INDIRECT WASTE PER THE 2010
 FL. PLOBG. CODE SEC. 301.6.
  