Plan Review Notes For Permit 14120199 |
Permit Number |
14120199 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2014-12-05 18:01:19 | ****CORRECTIONS**** | | COURTESY REVIEW, INFORMATION PROVIDED BY EMAIL | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 | | [email protected] | | | | FBC FLORIDA BUILDING CODE 2010 | | | | TWO COMPLETE COLLATED SETS OF ALL DOCUMENTS REQUIRED | | | | 1. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. | | | | SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM | | E 84 OR UL 723. | | | | THE TWO SOUND TESTS PROVIDED ARE COMPLIANT WITH FBC | | 1207. | | | | NO FLAME SPREAD TEST WAS PROVIDED. PLEASE CONTACT THE | | MANUFACTURER TO SEE IF THIS PRODUCT (ECO SILENCER) IS | | THE SAME AS OTHER PRODUCTS WITH A SIMILAR NAME BY THE | | SAME MANUFACTURER FOR WHICH THERE IS A FLAME SPREAD | | TEST. THE MANUFACTURER WOULD NEED TO PROVIDE A LETTER | | OF EXPLANATION. | | | | | | | | | | |
|