Plan Review Notes
Plan Review Notes For Permit 14120197
Permit Number 14120197
Review Stop E
Sequence Number 2
Notes
Date Text
2015-01-29 15:33:541/29/2015
 PROJECT: 625 59TH ST
 PERMIT#: 14120197
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED.
  
 ORIGINAL COMMENTS NOT ADDRESSED.
  
 1) PROVIDE THE LOCATION OF THE ELECTRIC PANEL AND A
 PANEL SCHEDULE TO INDICATE THE SOURCE OF ELECTRIC POWER
 TO FEED THE ENCLOSED CARPORT (GARAGE)
  
 2) PROVIDE THE REQUIRED RECEPTACLE OUTLET 210.52 (G)
 BASEMENTS AND GARAGES.
 A) (1) AT LEAST ONE RECEPTACLE OUTLET, IN ADDITION TO
 THOSE FOR SPECIFIC EQUIPMENT, SHALL BE INSTALLED IN
 EACH BASEMENT, IN EACH ATTACHED GARAGE, AND IN EACH
 DETACHED GARAGE WITH ELECTRIC POWER.
 B) 210.8 (A) DWELLING UNITS. ALL 125-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE RECEPTACLES INSTALLED
 IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8) SHALL
 HAVE GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR
 PERSONNEL.
 (2) GARAGES, AND ALSO ACCESSORY BUILDINGS THAT HAVE A
 FLOOR LOCATED AT OR BELOW GRADE LEVEL NOT INTENDED AS
 HABITABLE
 ROOMS AND LIMITED TO STORAGE AREAS, WORK AREAS, AND
 AREAS OF SIMILAR USE
  
 3) PROVIDE THE REQUIRED LIGHT OUTLET INSIDE AND OUTSIDE
 SEE NEC CODE ARTICLES BELOW:
 210.70 LIGHTING OUTLETS REQUIRED.
 LIGHTING OUTLETS SHALL BE INSTALLED WHERE SPECIFIED IN
 210.70(A), (B), AND (C).
 (A) AT LEAST ONE WALL SWITCH?CONTROLLED LIGHTING OUTLET
 SHALL BE INSTALLED IN HALLWAYS, STAIRWAYS, ATTACHED
 GARAGES, AND DETACHED GARAGES WITH ELECTRIC POWER.
 (B) FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED
 GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL
 SWITCH?CONTROLLED LIGHTING OUTLET SHALL BEINSTALLED TO
 PROVIDE ILLUMINATION ON THE EXTERIOR SIDE OF OUTDOOR
 ENTRANCES OR EXITS WITH GRADE LEVEL ACCESS. A VEHICLE
 DOOR IN A GARAGE SHALL NOT BE CONSIDERED AS AN OUTDOOR
 ENTRANCE OR EXIT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  
  
  
  
  