2015-01-29 15:33:54 | 1/29/2015 |
| PROJECT: 625 59TH ST |
| PERMIT#: 14120197 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 2ND ELECTRICAL PLAN REVIEW |
| ACTION: DENIED. |
| |
| ORIGINAL COMMENTS NOT ADDRESSED. |
| |
| 1) PROVIDE THE LOCATION OF THE ELECTRIC PANEL AND A |
| PANEL SCHEDULE TO INDICATE THE SOURCE OF ELECTRIC POWER |
| TO FEED THE ENCLOSED CARPORT (GARAGE) |
| |
| 2) PROVIDE THE REQUIRED RECEPTACLE OUTLET 210.52 (G) |
| BASEMENTS AND GARAGES. |
| A) (1) AT LEAST ONE RECEPTACLE OUTLET, IN ADDITION TO |
| THOSE FOR SPECIFIC EQUIPMENT, SHALL BE INSTALLED IN |
| EACH BASEMENT, IN EACH ATTACHED GARAGE, AND IN EACH |
| DETACHED GARAGE WITH ELECTRIC POWER. |
| B) 210.8 (A) DWELLING UNITS. ALL 125-VOLT, |
| SINGLE-PHASE, 15- AND 20-AMPERE RECEPTACLES INSTALLED |
| IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8) SHALL |
| HAVE GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR |
| PERSONNEL. |
| (2) GARAGES, AND ALSO ACCESSORY BUILDINGS THAT HAVE A |
| FLOOR LOCATED AT OR BELOW GRADE LEVEL NOT INTENDED AS |
| HABITABLE |
| ROOMS AND LIMITED TO STORAGE AREAS, WORK AREAS, AND |
| AREAS OF SIMILAR USE |
| |
| 3) PROVIDE THE REQUIRED LIGHT OUTLET INSIDE AND OUTSIDE |
| SEE NEC CODE ARTICLES BELOW: |
| 210.70 LIGHTING OUTLETS REQUIRED. |
| LIGHTING OUTLETS SHALL BE INSTALLED WHERE SPECIFIED IN |
| 210.70(A), (B), AND (C). |
| (A) AT LEAST ONE WALL SWITCH?CONTROLLED LIGHTING OUTLET |
| SHALL BE INSTALLED IN HALLWAYS, STAIRWAYS, ATTACHED |
| GARAGES, AND DETACHED GARAGES WITH ELECTRIC POWER. |
| (B) FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED |
| GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL |
| SWITCH?CONTROLLED LIGHTING OUTLET SHALL BEINSTALLED TO |
| PROVIDE ILLUMINATION ON THE EXTERIOR SIDE OF OUTDOOR |
| ENTRANCES OR EXITS WITH GRADE LEVEL ACCESS. A VEHICLE |
| DOOR IN A GARAGE SHALL NOT BE CONSIDERED AS AN OUTDOOR |
| ENTRANCE OR EXIT. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |
| |
| |
| |
| |
| |