Plan Review Notes For Permit 14120181 |
Permit Number |
14120181 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-12-31 15:20:46 | PLAN REVIEW COMMENTS | | | | 1ST REVIEW: FBC 2010 | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) ON SHEET A-1, THE WRONG EDITION OF ASCE 7 IS | | SPECIFIED. ASCE 7 - 10 IS THE STANDARD THAT IS | | REFERENCED IN CHAPTER 43 OF THE 2010 FBC RESIDENTIAL. | | | | 2) THE FIRST FLOOR PLAN ON SHEET A-2 APPEARS TO SHOW | | THE NEW SLIDING GLASS DOORS AS THREE PANELS. THE DOOR | | AND WINDOW SCHEDULE ON SHEET A-2 INDICATES THAT THE 9' | | X 8' SLIDING GLASS DOORS ARE 2 PANELS. PLEASE CLARIFY. | | FBC 107.2.1 | | | | 3) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE NEW | | 16' X 7' OVERHEAD GARAGE DOOR AND THE NEW 6' X 8' | | DOUBLE OUTSWING ENTRY DOOR THAT HAVE BEEN REVIEWED AND | | APPROVED IN WRITING BY THE DESIGNER OF RECORD. DCA RULE | | 9N-3 AND FBC 107.3.4.1 | | |
|