Plan Review Notes For Permit 14120171
Permit Number 14120171
Review Stop G
Sequence Number 2
Notes
Date Text
2014-12-20 03:28:381) YOU HAVE SUBMITTED A COPY OF THE SIZING TABLE FOR PE
 PIPE YET PE PIPE IS NOT SHOWN ON THE PLANS AS BEING
 INSTALLED. SUBMIT A COPY OF THE SIZING TABLE FROM THE
 2010 FL. BUILDING CODE, RESIDENTIAL, SECTION G2413.3
 AND TABLES G2413.4 (5) OR 2413.4 (6) FOR THE TYPE OF
 PIPE MATERIAL BEING USED.THE PLAN INDICATES FSP ? I
 ASSUME THIS IS CSST. IF SO, PLEASE REFER TO IT AS SUCH
 ON THE PLAN.
 2) IF CSST IS BEING INSTALLED, SHOW THE CORRESPONDING
 EHD NUMBER FOR THE PIPE SIZE IN ACCORDANCE WITH 2010
 FBCR, SEC.G2413.3 AND THE APPLICABLE SIZING TABLE.
 3) INDICATE THE GAS PRESSURE ( PSI ) ON THE PLANS AND
 THE LOCATION OF THE 2ND STAGE REGULATOR IF APPLICABLE.
 REGULATORS LOCATED ON THE EXTERIOR OF THE BUILDING
 SHALL BE APPROVED FOR OUTDOOR INSTALLATION.2010 FBCR,
 SEC. G2421.1.
 4) SUBMIT TWO CLEAN COPIES OF THE GAS PLAN THAT CLEARLY
 SHOWS THE TYPE OF PIPING THROUGH THE ATTIC SPACE, THE
 TOTAL BTU LOAD ON THE SYSTEM ( SINCE THE BRANCH LINE
 FOR THE GENERATOR IS BEING CONNECTED TO THE EXISTING
 SYSTEM, ALL THE APPLIANCES CONNECTED TO THE SYSTEM
 SHALL BE INCLUDED IN THE TOTAL BTU. IS THE LOAD OF
 300,000 THE TOTAL LOAD OR JUST THE GENERAROR LOAD?
 INDICATE ON THE PLANS. THE PLANS HAVE ITEMS CROSSED OUT
 AND ARE SOMEWHAT VAGUE IN NATURE.IN ORDER FOR A
 COMPLETE REVIEW TO BE DONE, 2 COPIES OF CLEAN DRAWINGS
 SHALL BE SUBMITTED. I WILL NOT APPROVE THESE PLANS AS
 THEY ARE.
 5) THE NOTE ON THE GAS DRAWING STATES THE TOTAL FOOTAGE
 OF PIPE IS 30 FEET BUT THE DIMENSIONS SHOWN ON THE
 SURVEY CLEARLY INDICATE THAT THE TOTAL RUN FROM THE GAS
 METER TO THE GENERATOR IS MORE THAN 30 FEET. SHOW THE
 DISTANCE FROM THE GAS METER TO THE FURTHEST OUTLET
 /GENERATOR.
 **NOTE** - I SUGGEST THAT SOMEONE CONTACT ME AT
 561-805-6692 TO SET UP AN APPOINTMENT TO COME INTO THE
 BUILDING DIVISION AND MEET WITH ME TO DISCUSS THESE
 COMMENTS AND ARRIVE AT A RESOLUTION SO WE CAN GET THIS
 PERMIT ISSUED. THANK YOU.
  