Date |
Text |
2014-12-20 03:28:38 | 1) YOU HAVE SUBMITTED A COPY OF THE SIZING TABLE FOR PE |
| PIPE YET PE PIPE IS NOT SHOWN ON THE PLANS AS BEING |
| INSTALLED. SUBMIT A COPY OF THE SIZING TABLE FROM THE |
| 2010 FL. BUILDING CODE, RESIDENTIAL, SECTION G2413.3 |
| AND TABLES G2413.4 (5) OR 2413.4 (6) FOR THE TYPE OF |
| PIPE MATERIAL BEING USED.THE PLAN INDICATES FSP ? I |
| ASSUME THIS IS CSST. IF SO, PLEASE REFER TO IT AS SUCH |
| ON THE PLAN. |
| 2) IF CSST IS BEING INSTALLED, SHOW THE CORRESPONDING |
| EHD NUMBER FOR THE PIPE SIZE IN ACCORDANCE WITH 2010 |
| FBCR, SEC.G2413.3 AND THE APPLICABLE SIZING TABLE. |
| 3) INDICATE THE GAS PRESSURE ( PSI ) ON THE PLANS AND |
| THE LOCATION OF THE 2ND STAGE REGULATOR IF APPLICABLE. |
| REGULATORS LOCATED ON THE EXTERIOR OF THE BUILDING |
| SHALL BE APPROVED FOR OUTDOOR INSTALLATION.2010 FBCR, |
| SEC. G2421.1. |
| 4) SUBMIT TWO CLEAN COPIES OF THE GAS PLAN THAT CLEARLY |
| SHOWS THE TYPE OF PIPING THROUGH THE ATTIC SPACE, THE |
| TOTAL BTU LOAD ON THE SYSTEM ( SINCE THE BRANCH LINE |
| FOR THE GENERATOR IS BEING CONNECTED TO THE EXISTING |
| SYSTEM, ALL THE APPLIANCES CONNECTED TO THE SYSTEM |
| SHALL BE INCLUDED IN THE TOTAL BTU. IS THE LOAD OF |
| 300,000 THE TOTAL LOAD OR JUST THE GENERAROR LOAD? |
| INDICATE ON THE PLANS. THE PLANS HAVE ITEMS CROSSED OUT |
| AND ARE SOMEWHAT VAGUE IN NATURE.IN ORDER FOR A |
| COMPLETE REVIEW TO BE DONE, 2 COPIES OF CLEAN DRAWINGS |
| SHALL BE SUBMITTED. I WILL NOT APPROVE THESE PLANS AS |
| THEY ARE. |
| 5) THE NOTE ON THE GAS DRAWING STATES THE TOTAL FOOTAGE |
| OF PIPE IS 30 FEET BUT THE DIMENSIONS SHOWN ON THE |
| SURVEY CLEARLY INDICATE THAT THE TOTAL RUN FROM THE GAS |
| METER TO THE GENERATOR IS MORE THAN 30 FEET. SHOW THE |
| DISTANCE FROM THE GAS METER TO THE FURTHEST OUTLET |
| /GENERATOR. |
| **NOTE** - I SUGGEST THAT SOMEONE CONTACT ME AT |
| 561-805-6692 TO SET UP AN APPOINTMENT TO COME INTO THE |
| BUILDING DIVISION AND MEET WITH ME TO DISCUSS THESE |
| COMMENTS AND ARRIVE AT A RESOLUTION SO WE CAN GET THIS |
| PERMIT ISSUED. THANK YOU. |
| |
| PLUMBING PLAN REVIEW |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| 561-805-6692 |
| [email protected] |
| |
| |
| |