Plan Review Notes
Plan Review Notes For Permit 14120171
Permit Number 14120171
Review Stop E
Sequence Number 1
Notes
Date Text
2014-12-09 14:30:57FBC- 107.3.5.3. PROVIDE A DETAILED ELECTRICAL SERVICE
 RISER TO INCLUDE THE FOLLOWING: A GROUNDING ELECTRODE
 SYSTEM. ALL SERVICE DISCONNECTS, TRANSFER SWITCHES AND
 PANELS. ALL CONDUIT AND WIRE SIZES. A COMPLETE DETAILED
 LOAD CALCULATION(S). CLEAR AND SPECIFIC PANEL
 DIRECTORIES. ALL CIRCUIT NUMBERS AS INDICATED ON THE
 PANEL DIRECTORIES SHOWN ON THE FLOOR PLAN.. PROVIDE ALL
 NECESSARY ELECTRICAL PLANS TO INDICATE THE RELOCATION
 OF THE GENERATOR, THE LOCATION OF THE GENERATOR
 DISCONNECT(S), AND THE LOCATION, ROUTING, TYPE AND SIZE
 OF CONDUITS AND WIRING.