2015-01-15 08:26:09 | BUILDING PLAN REVIEW |
| PERMIT: 14120169 |
| ADD: 716 N. SAPODILLA AVE. |
| CONT: NUJAK DEV. |
| TEL: (561)847-3291 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: THURS. JAN. 15/ 2015 |
| ACTION: DENIED |
| |
| NOTICE!!!!!!!!! CHAPTER 553.80(2)(B) FLORIDA STATUTES |
| STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A FEE OF |
| FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE |
| REJECTED (3) OR MORE TIMES FOR REPEATED FAILURE TO |
| CORRECT A CODE VIOLATION. |
| |
| 1) COMPLIED. |
| PLEASE PROVIDE A SURVEY, EXTERIOR DOORS CAN NOT SWING |
| OVER THE PROPERTY LINES. 2010 FBC-B 3202.2 |
| ENCROACHMENTS ABOVE GRADE AND BELOW 8 FEET IN HEIGHT. |
| ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY ABOVE GRADE |
| AND BELOW 8 FEET (2438 MM) IN HEIGHT SHALL BE |
| PROHIBITED EXCEPT AS PROVIDED FOR IN SECTIONS 3202.2.1 |
| THROUGH 3202.2.3. DOORS AND WINDOWS SHALL NOT OPEN OR |
| PROJECT INTO THE PUBLIC RIGHT-OF-WAY. |
| |
| 2) COMPLIDED. |
| ALSO NOTE HOW FAR THE BUILDING IS FROM THE PROPERT |
| LINE. 2010 FBC-B TABLE 705.8 MAXIMUM AREA OF EXTERIOR |
| WALL OPENINGS BASED ON FIRE SEPARATION DISTANCE AND |
| DEGREE OF OPENING PROTECTION. |
| |
| 3) 2ND REQUEST, THIS APPEARS TO BE A FLORIDA APPROVAL |
| PLEASE SUBMIT THE COVERSHEET TO THE CURRENT CODE. THE |
| PRODUCT APPROVAL SUBMITTED DOES NOT HAVE THE |
| COVERSHEETS TO WHICH CODE THIS WAS APPROVED. SHEET # 3 |
| INDICATES THIS REPORT EXPIRED 03/31/2010. |
| 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 |
| COMPONENTS & CLADDING |
| |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| |
| 4) 2ND REQUEST. 2010 FBC 107.3.4.1 PRODUCT APPROVALS. |
| THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE |
| 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 5) COMPLIED> . SHEET A-1 WIND DESIGN CRITERIA: |
| 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| CHAPTER 6 OF ASCE 7-10. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| |
| |