2015-06-29 10:52:19BUILDING PLAN REVIEW
 PERMIT: 14120130
 ADD: 1901 S. DIXIE HWY.
 CONT: SISCACONSTRUCTION
 TEL: (561)686-5545
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 4TH REVIEW
 DATE: MON. JUNE 29/ 2015
 ACTION: BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1C) PROVISO: THE PLANS INDICATE A PROPOSED UNDERGROUND
 FIRE LINE TAP.2010 FBC-B 903.1.2 GROUP A2 WHEN THE FIRE
 AREA HAS AN OCCUPANT LOAD OF 100 OR MORE FIRE
 SPRINKLERS ARE REQUIED. 107.3.5 MINIMUM PLAN REVIEW
 CRITERIA FOR BUILDINGS. 107.3.5.1 COMMERCIAL BUILDINGS
 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: SCHEMATIC
 FIRE SPRINKLERS
  
 2A) BUILDING PROVISO: MON. JUNE 29/ 2015 RECEIVED
 SIGNED & SEALED LETTER FROM THE DESIGNER OF RECORD THAT
 A REVISION WILL BE FORTH COMING CORRECTING THE FRONT
 ENTRY DOORS TO BE OUT SWING BUT OVER THE PROPERTY LINE,
 THE REVISION WILL NEED TO BE INTO THE BUILDING
 DEPARTMENT AND APPROVED BEFORE THE FRAMING INSPECTION
 CAN OCCUR.
  
 2B) APPROVED, LETTER FROM THE DESIGNER OF RECORD
 SHOWING COMPLIANCE WITH 2010 FL. ACCESSIBILTY CODE SEE
 SECTION 202.4.1 DISPROPORTIONATE COST.
  
 3A) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR
 DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE
 IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING.
 THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED
 UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL. 2010 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS, EFIS
 SYSTEMS
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/C STANDS
  
 4) PROVISO: SUBMIT BEFORE 1ST INSPECTION FOR FOOTINGS.
 SHEET S4.0 ALSO HAS STATEMENTS FOR SOILS REPORTS FOR
 ALL OF THE NEW FOUNDATIONS FOR THE MEZZANINE LEVEL. THE
 ASSUMED SAFE BEARING VALUE OF THE SOILS IS 2500 PSF.
 NOTE 3 READS: SOILS SUPPORTING ALL FOOTING MUST BE
 INSPECTED AND APPROVED BY A REGISETERD SOILS ENGINEER
 BEFORE COMMENCING WORK. APPROVED IN WRITING MUST
 INDICATE THE SOIL IS ADEQUATE TO SAFETLY SUSTAIN
 SPECIFIED SOIL BEARING PRESSURE. 2010 FBC-B 1803.2
 INVESTIGATIONS REQUIRED.
  
 JAMES A. WITMER CBO