2015-06-29 10:52:19 | BUILDING PLAN REVIEW |
| PERMIT: 14120130 |
| ADD: 1901 S. DIXIE HWY. |
| CONT: SISCACONSTRUCTION |
| TEL: (561)686-5545 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 4TH REVIEW |
| DATE: MON. JUNE 29/ 2015 |
| ACTION: BUILDING APPROVED WITH EXCEPTION! |
| THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| |
| 1C) PROVISO: THE PLANS INDICATE A PROPOSED UNDERGROUND |
| FIRE LINE TAP.2010 FBC-B 903.1.2 GROUP A2 WHEN THE FIRE |
| AREA HAS AN OCCUPANT LOAD OF 100 OR MORE FIRE |
| SPRINKLERS ARE REQUIED. 107.3.5 MINIMUM PLAN REVIEW |
| CRITERIA FOR BUILDINGS. 107.3.5.1 COMMERCIAL BUILDINGS |
| 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: SCHEMATIC |
| FIRE SPRINKLERS |
| |
| 2A) BUILDING PROVISO: MON. JUNE 29/ 2015 RECEIVED |
| SIGNED & SEALED LETTER FROM THE DESIGNER OF RECORD THAT |
| A REVISION WILL BE FORTH COMING CORRECTING THE FRONT |
| ENTRY DOORS TO BE OUT SWING BUT OVER THE PROPERTY LINE, |
| THE REVISION WILL NEED TO BE INTO THE BUILDING |
| DEPARTMENT AND APPROVED BEFORE THE FRAMING INSPECTION |
| CAN OCCUR. |
| |
| 2B) APPROVED, LETTER FROM THE DESIGNER OF RECORD |
| SHOWING COMPLIANCE WITH 2010 FL. ACCESSIBILTY CODE SEE |
| SECTION 202.4.1 DISPROPORTIONATE COST. |
| |
| 3A) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF |
| THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR |
| DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE |
| REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING |
| OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED |
| SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE |
| IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING. |
| THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED |
| UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN |
| APPROVED BY THE BUILDING OFFICIAL. 2010 FBC-B 1609.1.2 |
| PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS & |
| CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE |
| 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B) WINDOWS |
| (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS, EFIS |
| SYSTEMS |
| (D) ROOFING PRODUCTS AND ASSEMBLIES |
| (G) PRE-ENGINEERED A/C STANDS |
| |
| 4) PROVISO: SUBMIT BEFORE 1ST INSPECTION FOR FOOTINGS. |
| SHEET S4.0 ALSO HAS STATEMENTS FOR SOILS REPORTS FOR |
| ALL OF THE NEW FOUNDATIONS FOR THE MEZZANINE LEVEL. THE |
| ASSUMED SAFE BEARING VALUE OF THE SOILS IS 2500 PSF. |
| NOTE 3 READS: SOILS SUPPORTING ALL FOOTING MUST BE |
| INSPECTED AND APPROVED BY A REGISETERD SOILS ENGINEER |
| BEFORE COMMENCING WORK. APPROVED IN WRITING MUST |
| INDICATE THE SOIL IS ADEQUATE TO SAFETLY SUSTAIN |
| SPECIFIED SOIL BEARING PRESSURE. 2010 FBC-B 1803.2 |
| INVESTIGATIONS REQUIRED. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |