Plan Review Notes
Plan Review Notes For Permit 14120130
Permit Number 14120130
Review Stop M
Sequence Number 3
Notes
Date Text
2015-06-15 15:38:04PASS PROVISO
 1) KITCHEN HOODS ARE NOT PART OF THIS REVIEW.
 HOODS REQUIRE SEPARATE APPLICATION, PLANS AND PERMIT
 2) PROVIDE A DETAIL FROM THE ENGINEER ON CURB TO ROOF
 AND RTU TO CURB TIE DOWN, SHOW TYPE AND SIZE OF
 ANCHOR USED. PER SECTION 301.12 WIND RESISTANCE
 2010 FBC (M)
 3) CALL IN INSPECTION BEFOR RTU IS INSTALLED SO
 INSPECTOR CAN SEE SECURE STRAP AND TEX SCREWS.
 4) REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROLS
 2010 FLORIDA ENERGY CODE
  