Plan Review Notes
Plan Review Notes For Permit 14120130
Permit Number 14120130
Review Stop P
Sequence Number 2
Notes
Date Text
2015-04-19 09:22:201) SUBMIT MANUF. SPECIFICATIONS FOR ALL GAS
 APPLIANCES/EQUIPMENT.ALL EQUIPMENT SHALL BE LISTED AND
 LABELED PER THE 2010 FUEL GAS CODE SEC.301.3. THE
 NARRATIVE RESPONSE REFERS TO SHT. QF 101FOR GAS
 EQUIPMENT AND SPECIFICATIONS. THERE IS NO SHT. QF 101.
 CLARIFY.
 2) SUBMIT VENTING DETAILS FOR THE TANKLESS WATER
 HEATERS. THE TANKLESS WATER HEATERS ARE DIRECT VENT
 APPLIANCES AND THE VENTING IS USUALLY SHOWN IN THE
 MANUFACTURER'S INSTALLATION MANUAL. SUBMIT THE VENT
 DETAILS FROM THE MANUFACTURER.THE NARRATIVE RESPONSE
 STATES TO SEE SHT.P0.2 FOR WATER HEATER VENT
 DETAIL.THERE IS NO VENT DETAIL ON P0.2, JUST A CLOUDED
 EMPTY BOX. WPB AMEND. TO 2010 FBC SEC. 107.3.5.1.5.
 3) SUBMIT MANUF. SPECIFICATION SHEETS FOR THE VENTLESS
 GAS REGULATORS. THE NARRATIVE RESPONSE REFERS TO SHT.
 P1.1B & ATTACHED CUT SHEET.THERE IS NO ADDITIONAL
 INFORMATION ON SHT.P1.1B & NO ATTACHED CUT SHEET.
 CLARIFY.
 4) THE BTU LOAD OF THE APPLIANCES LISTED ON SHT. P1.2
 AND SHT.P0.3 DO NOT CORRELATE. I HAVE ADDED THE BTU
 LOAD A FEW TIMES ON SHT. P1.2 AND THE TOTAL BTU LOAD I
 CALCULATED IS 1,559,000. CLARIFY.
 5) SHT. P1.2 - PLEASE EXPLAIN HOW YOU ARRIVED AT THE
 CUBIC FOOTAGE OF 94,880 FOR THE RESTAURANT. IT IS
 UNCLEAR TO ME HOW YOU ARRIVED AT YOUR COMBUSTION AIR
 CALCULATIONS. IN ACCORDANCE WITH THE STANDARD METHOD IN
 THE 2010 FGC SEC.304.5.1, 50 CU. FT. OF COMBUSTION AIR
 IS REQUIRED FOR EACH 1,000 BTU OF THE APPLIANCE RATING.
 TAKING THE TOTAL BTU LOAD FROM COMMENT #4, 1,559,000
 DIVIDED BY 1000 = (1,559 ) X (50 CU. FT. ) = 77,950 CU.
 FT. OF COMBUSTION AIR REQUIRED. THE CUBIC FOOTAGE OF
 THE RESTAURANT ON P1.2 IS SHOWN AS 94,880 AND ALSO AS
 81,900 BEING DIVIDED BY 50 CU.FT. I DO NOT KNOW HOW YOU
 ARRIVED AT YOUR BTU PARAMETERS FOR THE COMBUSTION AIR.
 CLARIFY.
 6) THE VENTING OF THE TANKLES WATER HEATRS SHALL COMPLY
 WITH THE APPROPRIATE TABLE FROM FGC SEC.504 AND TABLE
 504.2 FOR THE APPLICABLE TYPE OF VENT MATERIAL BEING
 USED OR SUBMIT THE MANUFACTURER'S INSTALLATION DETAILS
 FOR THE VENTING OF MULTIPLE UNITS.
 7) SHT. P0.2 - THE SANITARY RISER AS DRAWN DOES NOT
 COMPLY WITH 2010 FPC SEC. 909 FOR A WET VENT SYSTEM.THE
 WATER CLOSETS SHALL BE INDIVIDUALLY VENTED OR THE
 SYSTEM SHALL BE DESIGNED AS A CIRCUIT VENT IN
 COMPLIANCE WITH FPC SEC.911.
 8) THE MOP SINK IS SHOWN WITH A VENT ON THE PLAN VIEW
 DRAWING ( P1.1A ) BUT NOT ON THE RISER. CLARIFY.
 9) THE STAFF RESTROOM CLEARLY OPENS INTO THE FOOD PREP
 AREA. THERE IS A DOUGH PREP AREA ALMOST DIRECTLY IN
 FRONT OF IT.TOILET ROOMS SHALL NOT OPEN DIRECTLY INTO A
 ROOM USED FOR THE PREPARATION OF FOOD FOR SERVICE TO
 THE PUBLIC PER THE 2010 FBC SEC.1210.5.
 10) SUBMIT A COMPLETE FOOD SERVICE EQUIPMENT PLAN.WPB
 AMEND. TO 2010 FBC SEC. 107.2.1.
  