2015-04-16 16:52:40 | 1901 SOUTH DIXIE HIGHWAY | | PERMIT #14120130 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | SOLID FUEL COOKING OPERATIONS NEED TO CONFORM TO ALL | | THE REQUIREMENTS OF NFPA 96 (HOODS, EXHAUST, AIR | | MOVEMENT, FIRE PROTECTION, CLEANING/MAINTENANCE, FUEL | | STORAGE, EMBER/ASH MANAGEMENT, ETC.). THE PLANS AND | | EQUIPMENT ARE SEVERLY LACKING INFORMATION TO SHOW | | COMPLIANCE WITH ALL THE DETAILED REQUIREMENTS OF NFPA | | 96. | | | | ENGINEERED FIRE SPRINKLER CONSTRUCTION DOCUMENTS ARE | | REQUIRED FOR A GENERAL BUILDING PERMIT. AFTER THE | | BUILDING PERMIT HAS BEEN ISSUED, THE SUBCONTRACTORS CAN | | THEN SUBMIT SHOP DRAWINGS (CONFORMING TO THE ENGINEERED | | CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT. PER FLORIDA | | ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE | | PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE | | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF | | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, | | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR | | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER | | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) | | AND ANY PERFORMANCE BASED INFORMATION SUCH AS | | PRE-ENGINEERED SYSTEMS. | | | | WESLEY JOLIN | | ASSISTANT FIRE MARSHAL | | FIRE INVESTIGATOR & INSPECTOR | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 805-6730 | | |
|