2015-04-16 16:52:401901 SOUTH DIXIE HIGHWAY
 PERMIT #14120130
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SOLID FUEL COOKING OPERATIONS NEED TO CONFORM TO ALL
 THE REQUIREMENTS OF NFPA 96 (HOODS, EXHAUST, AIR
 MOVEMENT, FIRE PROTECTION, CLEANING/MAINTENANCE, FUEL
 STORAGE, EMBER/ASH MANAGEMENT, ETC.). THE PLANS AND
 EQUIPMENT ARE SEVERLY LACKING INFORMATION TO SHOW
 COMPLIANCE WITH ALL THE DETAILED REQUIREMENTS OF NFPA
 96.
  
 ENGINEERED FIRE SPRINKLER CONSTRUCTION DOCUMENTS ARE
 REQUIRED FOR A GENERAL BUILDING PERMIT. AFTER THE
 BUILDING PERMIT HAS BEEN ISSUED, THE SUBCONTRACTORS CAN
 THEN SUBMIT SHOP DRAWINGS (CONFORMING TO THE ENGINEERED
 CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT. PER FLORIDA
 ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE
 PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  