Plan Review Notes
Plan Review Notes For Permit 14120130
Permit Number 14120130
Review Stop P
Sequence Number 1
Notes
Date Text
2014-12-22 05:18:261) SHT.A4.0 - DETAIL #1 - STAFF R.R.- THE HEIGHT OF THE
 GRAB BAR ABOVE THE FINISH FLOOR SHALL BE MEASURED TO
 THE TOP OF THE GRIPPING SURFACE, NOT TO THE CENTERLINE
 OF THE BAR AS SHOWN.2010 FL. ACCESS. CODE SEC.609.4.
 2) LIFE SAFETY PLAN - INDICATE THE PREVIOUS OCCUPANCY
 ON THE PLAN. WPB AMEND. TO 2010 FBC SEC.107.2.1.. SEE
 THE BUILDING PLAN REVIEW COMMENT.
 3) A SERVICE SINK IS REQUIRED PER TABLE 403.1.
 4) SUBMIT MANUFACTURER SPECIFICATION SHEETS AND
 INSTALLATION MANUAL FOR THE TANKLESS WATER HEATERS. THE
 TANKLESS WATER HEATERS SHALL BE LISTED AND LABELED PER
 THE 2010 FL. GAS CODE SEC. 301.3.
 5) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL
 THE GAS APPLIANCES/EQUIPMENT. ALL EQUIPMENT SHALL BE
 LISTED AND LABELED PER SEC. 301.3 OF THE 2010 FGC.
 6) SHT. P0.2 - THE SANITARY RISER DOES NOT COMPLY WITH
 SEC.909 OF THE FL. PLUMBING CODE FOR THE NUMBER AND
 TYPE OF FIXTURES PERMITTED ON A WET VENT.
 7) SHT.P1.1A - A FLOOR DRAIN IS SHOWN IN THE WARE
 WASHING AREA (#113) BUT IS NOT SHOWN ON THE GREASY
 WASTE RISER ON P0.2.CLARIFY.
 8) SHT.P1.1A - SHOW THE INDIRECT WASTE FROM FIXTURE #7
 TO THE FLOOR DRAIN ON RISER P0.2.
 9) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE
 TANKLESS WATER HEATERS & ALL THE GAS APPLIANCES ON THE
 FIRST FLOOR. 201 FL. GAS CODE SEC.304.
 10) SUBMIT VENTING DETAILS FOR THE TANKLESS WATER
 HEATERS. 201 FGC SEC.503.THE PLUMBING PLANS REFER TO
 THE MECHANICAL SHEETS FOR DETAILS BUT THERE IS JUST A
 PLAN VIEW WITH NO DETAILS.
 11) SUBMIT MANUF. SPECS FOR THE VENTLESS GAS
 REGULATORS. WPB AMEND. TO 2010 FBC SEC.107.2.1, FGC
 SEC.410.0.
 12) SHOW THE INCREMENTAL BTU/CFH LOAD ON THE GAS PIPING
 SYSTEMFROM THE ENTRANCE METER TO THE FURTHEST OUTLET.
 13) WHERE IS PAGE 2 OF 2 FOR THE GREASE INTERCEPTOR
 DETAILS.?
 14) THE GREASE TRAPS APPEAR TO BE LOCATED ON LOT 6. IS
 THIS PROPERTY OWNED BY THE RESTAURANT?
 15) PROVIDE A LEGEND FOR THE HOT, COLD, HOT WATER
 RETURN AND THE TEMPERED WATER. THE RISER SHOWS THE
 INDIVIDUAL WATER IDENTIFIED WITH DOTS AND DASHES.WPB
 AMEND. TO 2010 FBC SEC.107.2.1
 16) PROVIDE INFORMATION/DETAILS FOR THE REGULATOR VENT
 FOR THE TANKLESS WATER HEATERS. WPB AMEND. TO 2010 FBC
 SEC.107.2.1.COMPLY W/ 2010 FGC SEC.410.3.1.
 17) TOILET ROOMS SHALL NOT OPEN DIRECTLY INTO A ROOM
 USED FOR THE PREPARATION OF FOOD FOR SERVICE TO THE
 PUBLIC. 2010 FL. BLDG. CODE. SEC.1210.5.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  