2014-12-23 11:49:22 | 1901 SOUTH DIXIE HIGHWAY |
| CHANGE OF OCCUPANCY FROM MERCANTILE TO ASSEMBLY |
| PERMIT #14120130 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| GENERAL: PROVIDE DRAWING NOTE INDICATING, "FIRE |
| PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| BE SUBMITTED BY EMAIL ([email protected]) OR IN WRITING |
| (FAX: 561-804-4774) AND APPROVED BY THE OFFICE OF THE |
| FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY." |
| |
| GENERAL: PER SECTION 10.12.1.2 (NFPA 1), PROVIDE |
| BUILDING ADDRESS VISIBLE FROM THE STREET. NUMBERS SHALL |
| BE ATTACHED TO THE BUILDING AND BE AT LEAST SIX-INCHES |
| IN HEIGHT WITH 1-INCH STROKE AND SHALL CONTRAST THE |
| BACKGROUND. |
| |
| GENERAL: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW |
| EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE |
| BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE |
| ORDERED FROM WWW.KNOXBOX.COM. |
| |
| CIVIL SITE: NO PARKING SIGNS WILL BE NEEDED ON KANUGA |
| DRIVE TO PROVIDE FIRE DEPARTMENT ACCESS TO PROPOSED |
| FIRE DEPARTMENT CONNECTION, BACKFLOW PREVENTER AND |
| EXISTING FIRE HYDRANT. BACKFLOW PREVENTER WILL NEED TO |
| BE PROTECTED FROM VEHICULAR TRAFFIC. |
| |
| SHEET LS: SECONDARY EXIT (KANUGA DRIVE) DOOR SWINGS |
| INTO THE PUBLIC RIGHT OF WAY. |
| |
| SHEET A1.0: MAIN ENTRY DOOR EQUIPPED WITH THUMB TURN |
| LOCK. FOR ASSEMBLY AND EDUCATIONAL OCCUPANCIES WITH AN |
| OCCUPANT LOAD OF 100 OR MORE PERSONS (50 PERSONS PER |
| THE FLORIDA BUILDING CODE), PANIC HARDWARE SHALL BE |
| PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH. NO OTHER |
| LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT BE |
| RELEASED BY THE PANIC HARDWARE. AS A SUBSTITUTE FOR |
| PANIC HARDWARE, THE MAIN ENTRANCE IS PERMITTED TO HAVE |
| AN INTERIOR KEYED DOOR LOCK (AND NO LATCH) WITH A |
| READILY VISIBLE SIGN STATING THIS DOOR TO REMAIN |
| UNLOCKED WHEN THE BUILDING IS OCCUPIED. SIGN LETTERS |
| SHALL BE AT LEAST 1 INCH IN HEIGHT. KEYED LOCK TO BE |
| EQUIPPED WITH AN ?OPEN/LOCKED? INDICATOR WINDOW (SUCH |
| AS ADAMS RITE 4089 OR SIMILAR). A THUMB TURN STYLE LOCK |
| IS NOT PERMITTED TO BE SUBSTITUTED FOR A KEYED LOCK. |
| |
| SHEET A1.2: AREA AT BOTTOM OF STAIR INDICATED AS |
| RECEIVING AREA. WHAT SAFE GUARDS WILL BE IN PLACE TO |
| ENSURE THE EXIT STAIR (SINGLE MEANS OF EGRESS) IS NEVER |
| BLOCKED OR OBSTRUCTED? |
| |
| SHEET A2.0: THE CEILING AND STRUCTURE HEIGHTS CANNOT BE |
| DETERMINED FOR THE UPPER LEVEL. HEAD CLEARANCES OF |
| 7'-6" SHALL BE PROVIDED AND INDICATED ON THE PLANS. |
| |
| SHEET A2.0: PROVIDE A STORAGE LAYOUT. IN GENERAL, |
| INDICATE THE COMMODITIES TO BE STORED, THE QUANTITY TO |
| BE STORED, AND THE HEIGHT OF STORAGE, ETC. |
| |
| SHEET P2.1: EQUIPMENT SCHEDULE INDICATES A CHARCOAL |
| GRILL (ITEM #74). SOLID FUEL AND FIRE PROTECTION |
| INFORMATION AND DETAILS NEEDED FOR APPROVAL. |
| |
| FIRE PROTECTION: FOR ISSUANCE OF A GENERAL BUILDING |
| PERMIT, SECTION 105.3.1.2(2) OF THE FLORIDA BUILDING |
| CODE REQUIRES SEALED FIRE PROTECTION CONSTRUCTION |
| DOCUMENTS FOR THE DESIGN OR ALTERATION OF 50 OR MORE |
| AUTOMATIC FIRE SPRINKLERS. PER FLORIDA ADMINISTRATIVE |
| CODE SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING |
| DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE |
| WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS |
| APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD |
| OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM |
| TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP |
| DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED |
| INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS. |
| |
| WESLEY JOLIN |
| ASSISTANT FIRE MARSHAL |
| WEST PALM BEACH FIRE RESCUE |
| [email protected] |
| (561) 805-6730 |
| |