 1901 S DIXIE HWY
 INTERIOR IMPROVEMENT
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENT.
  
 VERIFY THIS BUILDING WILL HAVE ONLY ONE POINT OF
 ELECTRICAL SERVICE. INDICATE
 THE INTENDED USE FOR THE ELECTRICAL PANELS SHOW ON THE
 WEST EXTERIOR ELEVATION OF SHEET A3. NEC 230.2
  
 NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR ALARM
 SYSTEMS, SECURITY, SITE LIGHTING AND DATA SYSTEMS.
  