Plan Review Notes
Plan Review Notes For Permit 14120119
Permit Number 14120119
Review Stop G
Sequence Number 1
Notes
Date Text
2014-12-06 03:51:511) SUBMIT TWO COPIES OF THE APPLICABLE GAS SIZING TABLE
 FROM THE 2010 FL. GAS CODE FOR THIS INSTALLATION. IF
 YOU ARE INSTALLING MORE THAN ONE TYPE OF PIPE MATERIAL,
 SUBMIT COPIES OF THE SIZING TABLE FROM THE FUEL GAS
 CODE FOR EACH TYPE OF PIPE BEING USED.WPB AMEND. TO
 2010 FBC SEC. 107.3.5.1.3.
 2) APPLIANCES REGULATED BY THE GAS CODE SHALL BE LISTED
 AND LABELED FOR THE APPLICATION IN WHICH THEY ARE BEING
 USED PER 2010 FGC SEC.301.3. SUBMIT MANUF.
 SPECIFICATION SHEETS (2 COPIES) FOR ALL GAS APPLIANCES.
 3) THERE ARE TWO SECTIONS OF PIPE WHERE THE LENGTH
 DIMENSIONS ARE SHOWN IN INCHES. LOOK AT THE SECTION OF
 PIPE AT OUTLET "C". THE LENGTH IS SHOWN AS 7 INCHES AND
 SECTION 2 IS SHOWN AS 23 INCHES. CLARIFY
 4) INDICATE THE TYPES OF PIPE MATERIAL BEING USED. I
 CANNOT DO A COMPLETE REVIEW UNTIL YOU PUT THE TYPE OF
 PIPE MATERIAL ON THE PLANS. THERE MAY BE ADDITIONAL
 COMMENTS WHEN THIS INFORMATION IS SUBMITTED.
 5) SUPPLY INFORMATION FOR THE TYPE OF VENT MATERIAL
 BEING USED FOR THE APPLIANCES W/VENTS.
 6) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2010
 FL. FUEL GAS CODE SEC.304.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  