Plan Review Notes
Plan Review Notes For Permit 14120098
Permit Number 14120098
Review Stop B
Sequence Number 1
Notes
Date Text
2014-12-04 07:46:47ROOFING REVISION BUILDING REVIEW COMMENTS.
  
 1- MIAMI-DADE NOA 12-0716.18 SUBMITTED WAS SUPERSEDED
 BY MIAMI-DADE. NEED TO PROVIDE CURRENT NOA AS REQUIRED
 BY DCA RULE 9N-3. VISIT THE MIAMI-DADE WEBSITE AND
 DOWNLOAD CURRENT NOA AND RE-SUBMIT TWO COPIES.
  
 2- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS (2
 COPIES WITH ORIGINAL SEAL AND SIGNATURE) AS REQUIRED BY
 GENERAL LIMITATION #7 ON LAST PAGE OF NOA SUBMITTED.
 NEED THE RAS 117 CALCULATIONS TO MEET THE DESIGN
 PRESSURES REQUIRED BY SEC. R301.1 OF 2010
 FBC-RESIDENTIAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]