Plan Review Notes For Permit 14120098 |
Permit Number |
14120098 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-12-04 07:46:47 | ROOFING REVISION BUILDING REVIEW COMMENTS. | | | | 1- MIAMI-DADE NOA 12-0716.18 SUBMITTED WAS SUPERSEDED | | BY MIAMI-DADE. NEED TO PROVIDE CURRENT NOA AS REQUIRED | | BY DCA RULE 9N-3. VISIT THE MIAMI-DADE WEBSITE AND | | DOWNLOAD CURRENT NOA AND RE-SUBMIT TWO COPIES. | | | | 2- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS (2 | | COPIES WITH ORIGINAL SEAL AND SIGNATURE) AS REQUIRED BY | | GENERAL LIMITATION #7 ON LAST PAGE OF NOA SUBMITTED. | | NEED THE RAS 117 CALCULATIONS TO MEET THE DESIGN | | PRESSURES REQUIRED BY SEC. R301.1 OF 2010 | | FBC-RESIDENTIAL. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] |
|