Plan Review Notes For Permit 14120094 |
Permit Number |
14120094 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-12-28 13:15:45 | 1ST REVIEW: FBC 2010 | | | | THE PLAN IS UNCLEAR AS TO THE EXTENT OF THE PROPOSED | | ELECTRICAL WORK. IS THE SERVICE NEW? THE PANEL SCHEDULE | | IS INCONSISTENT WITH THE MECHANICAL EQUIPMENT SPECIFIED | | IN THE ENERGY SUBMITTAL AS TO BREAKER SIZE AND HEAT | | STRIP KW. THERE IS NO INDICATION OF A LUMINARE IN THE | | ATTIC FOR THE AHU, SEE MECHANICAL COMMENTS. | | | | THE PLAN DOES NOT HAVE ADEQUATE DETAIL TO DETERMINE | | COMPLIANCE WITH THE FOLLOWING SECTIONS: | | | | FBC- 107.3.5.3 ? SMOKE DETECTORS PURSUANT TO FBC-R | | 314.3.1 AS REQUIRED FOR NEW DWELLINGS. | | NEC 210.12B - OUTLETS TO BE AFCI PROTECTED. | | NEC 210.52 (B) (3) - KITCHEN COUNTER TOP RECEPTACLES | | SHALL BE SUPPLIED BY NO FEWER THAN TWO SMALL APPLIANCE | | BRANCH CIRCUITS. | | NEC 210.63 - GFI SERVICE OUTLET FOR WITHIN 25? OF | | MECHANICAL EQUIPMENT. | | NEC 406.11- TAMPER RESISTANT RECEPTACLES. | | | | ADDITIONALLY, THERE ARE NO DISCONNECTS SHOWN FOR | | MECHANICAL EQUIPMENT OR WH AND NO WATER HEATER LOCATION | | SHOWN. | | | | | | STEVEN KENNEDY, CBO | | CHIEF PLANS EXAMINER | | (561) 805-6710 | | [email protected] | | | 2014-12-03 13:39:52 | INADVERTANT PUNCH BY FIRE PREVENTION |
|