Plan Review Notes
Plan Review Notes For Permit 14120094
Permit Number 14120094
Review Stop E
Sequence Number 1
Notes
Date Text
2014-12-28 13:15:451ST REVIEW: FBC 2010
  
 THE PLAN IS UNCLEAR AS TO THE EXTENT OF THE PROPOSED
 ELECTRICAL WORK. IS THE SERVICE NEW? THE PANEL SCHEDULE
 IS INCONSISTENT WITH THE MECHANICAL EQUIPMENT SPECIFIED
 IN THE ENERGY SUBMITTAL AS TO BREAKER SIZE AND HEAT
 STRIP KW. THERE IS NO INDICATION OF A LUMINARE IN THE
 ATTIC FOR THE AHU, SEE MECHANICAL COMMENTS.
  
 THE PLAN DOES NOT HAVE ADEQUATE DETAIL TO DETERMINE
 COMPLIANCE WITH THE FOLLOWING SECTIONS:
  
 FBC- 107.3.5.3 ? SMOKE DETECTORS PURSUANT TO FBC-R
 314.3.1 AS REQUIRED FOR NEW DWELLINGS.
 NEC 210.12B - OUTLETS TO BE AFCI PROTECTED.
 NEC 210.52 (B) (3) - KITCHEN COUNTER TOP RECEPTACLES
 SHALL BE SUPPLIED BY NO FEWER THAN TWO SMALL APPLIANCE
 BRANCH CIRCUITS.
 NEC 210.63 - GFI SERVICE OUTLET FOR WITHIN 25? OF
 MECHANICAL EQUIPMENT.
 NEC 406.11- TAMPER RESISTANT RECEPTACLES.
  
 ADDITIONALLY, THERE ARE NO DISCONNECTS SHOWN FOR
 MECHANICAL EQUIPMENT OR WH AND NO WATER HEATER LOCATION
 SHOWN.
  
  