2015-12-30 15:10:07BUILDING PLAN REVIEW
 PERMIT: 14120093
 ADD: 809 6TH ST.
 CONT: MIJO CONSTRUCTION
 TEL: (561)246-0411
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: WED. DEC. 30/2015
 ACTION: DENIED
  
 1) COVER SHEET:
 1A-D) COMPLIED.
  
 1E) 3RD REQUEST. PLEASE REVIEW 2010 FBC-B 903.2.8 AN
 AUTOMATIC SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH
 903.3 SHALL BE PROVIDED THROUGHOUT ALL BUILDINGS WITH A
 GROUP R FIRE AREA.
 SEE 2010 FBC-B 903.3.1.2 NFPA 13 R SPRINKLER SYSTEMS.
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107. 3.5.1.1 MINIMUM
 PLAN REVIEW CRITERIA COMMERCIAL BUILDING.
 .5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 SCHEMATIC FIRE SPRINKLERS
  
 2) COMPLIED.
  
 3) 3RD REQUEST. SHEETS A1 & A2 FAIL TO IDENTIFY 2010
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107. 3.5.1.8 MINIMUM
 PLAN REVIEW CRITERIA COMMERCIAL BUILDING.
 .8. STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 WIND REQUIREMENTS PROVIDE THE WIND DESIGN CRITERIA,
 BUILDING ENVELOPE/ PRODUCT APPROVALS
  
 STRUCTURAL CALCULATIONS (IF REQUIRED) 2010 EXT. BLDG.
 CODE LEVEL III 807.4. 1 THRU 3. LIVE LOADS FBC-B TABLE
 1607.1.
 FLOOR SYSTEMS PROVIDE FLOOR LOADING
 STAIR SYSTEMS
 HANDRAILS
  
 4) COMPLIED.
 5) 3RD REQUEST. SHEETS A1 & A2 FAIL TO IDENTIFY 2010
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107. 3.5.1.11.
 INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT) SEE
 2010 FBC-B TABLE 803.9.
  
  
 6) FL. ENERGY CODE:
 6A) COMPLIED.
  
 6B)(1) SHEET D-1 THE 1ST FLOOR IS MISSING FLOOR
 INSULATION UNDER THE FIRST FLOOR. 2010 FBC-ENERGY CODE
 402.4.1, 402.2.6 .
  
 6B)(2) A) 3RD REQUEST. FBC-B 2010 1207.3
 STRUCTURE-BORNE SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492.
  
 B)3RD REQUEST. FBC-B 2010 1207.2 1207.2 AIR-BORNE
 SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 C) 3RD REQUEST. FLAME SPREAD- FBC-B 2010 603.1.2
 EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED
 FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE
 SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 200.
  
 TYPE III-TYPE V CONSTRUCTION:
 719.2 CONCEALED INSTALLATION.
 INSULATING MATERIALS, WHERE CONCEALED AS INSTALLED IN
 BUILDINGS OF ANY TYPE OF CONSTRUCTION, SHALL HAVE A
 FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450.
  
  
  
 6)(3) COMPLIED.
  
 6C) 3RD REQUEST. SHEET D-1 COMMON WALL DETAIL INDICATES
 CODE COMPLIANCE FOR FL ENERGY CODE 402.2.12.2, PLEASE
 PROVIDE COMPLIANCE WITH 2010 FBC-B 1207.2 AIR-BORNE
 SOUND. WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE.
  
 6D) 3RD REQUEST. SHEET D-1 TENANT WALL/ FLOOR DETAIL
 INDICATES THE USE OF 3 INCH ATTEN. BATT R-30 BATT
 INSULATION, PLEASE PROVIDE COMPLIANCE WITH FBC-B 1207.3
 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 6E-F) COMPLIED.
  
 7-12) COMPLIED.
  
 13) SHEET D1 PLEASE PROVIDE CODE COMPLIANCE FOR THE 2ND
 FLOOR TENANTS HOW THE SPACE ABOVE THE CEILING& TENANT
 WALL SEPARATION WILL BE MADE CODE COMPLIANT WITH FBC-B
 709.4 OR EXCEPTIONS.
  
 14)COMPLIED. ROOF: FIBERGLASS SHINGLES.
  
 15) DEFERRED SUBMITTAL: PLEASE PROVIDE THE PRODUCT
 APPROVAL ON ICYNENE, WITHIN THE ICC REPORT CIRCLE WHICH
 SUB-SYSTEM YOU INTEND ON USING IN ACCORDANCE WITH THE
 MANUFACTURER?S INSTRUCTIONS. PLEASE ALSO SEE 2010 FBC-B
 2603.4.1.6 IGNITION BARRIER REQUIREMENT, DIFFERENT FROM
 THE THERMAL BARRIER REQUIREMENTS.
  
 16) 3RD REQUEST. SHEET D-1 INTERIOR FINISHES, WITH THE
 DESIGNER NOT LISTING THE OCCUPANCY TYPE R-1 OR R-2 THE
 COMPLIANCE WITH TABLE 803.9 IS A UNKNOWN, ALSO IF FIRE
 SPRINKLERED OR NOT.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107. 3.5.1.11.
 INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT) SEE
 2010 FBC-B TABLE 803.9.
  
 17) 3RD REQUEST. 2010 EXISTING BUILDING CODE, LEVEL III
 ALTERATION PLEASE REVIEW 804.1 AUTOMATIC SPRINKLER
 SYSTEMS. AUTOMATIC SPRINKLER SYSTEMS SHALL BE PROVIDED
 IN ALL WORK AREAS IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING. THE FIRE SPRINKLER PLANS NEED
 TO BE SUBMITTED PROVIDE THE HYDRAULIC CALCS FOR THE
 FIRE SPRINKLERS AND A SCHEMATIC LAYOUT. THE FIRE
 SPRINKLER SHOP DRAWINGS WILL BE SUBMITTED UNDER
 SEPARATE PERMIT.
  
 2010 FBC-B [F] 903.2.8 GROUP R. AN AUTOMATIC SPRINKLER
 SYSTEM INSTALLED IN ACCORDANCE WITH SECTION 903.3 SHALL
 BE PROVIDED THROUGHOUT ALL BUILDINGS WITH A GROUP R
 FIRE AREA.
  
 2010 FBC-B F] 903.3 INSTALLATION REQUIREMENTS.
 AUTOMATIC SPRINKLER SYSTEMS SHALL BE DESIGNED AND
 INSTALLED IN ACCORDANCE WITH SECTIONS 903.3.1 THROUGH
 903.3.6.
  
 18) COMPLIED. SHEET A3 PRESSURES FOR WINDOWS AND DOORS.
  
 19) COMPLIED. EGRESS WINDOWS.
  
 20-22) DEFERRED SUBMITTALS. 107.3.4.2 DEFERRED
 SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, DEFERRED
 SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN
 THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION
 AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL
 WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL
 ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING
 OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS
 ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE
 BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED SUBMITTAL
 ITEMS SHALL BE SUBMITTED TO THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW
 THEM AND FORWARD THEM TO THE BUILDING OFFICIAL WITH A
 NOTATION INDICATING THAT THE DEFERRED SUBMITTAL
 DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL
 CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED
 SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE
 BUILDING OFFICIAL.
  
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS/ MULLIONS
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
  
 21)COMPLIED. ROOFING EXISTING NOT REPLACING
  
 22) DEFERRED SUBMITTAL. 2010 FBC 107.3.4.1 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 23) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  