2015-08-25 19:54:10PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
 1. THOUGH YOUR PANEL SCHEDULES REFLECTS A WATER HEATER
 IN THE DIRECTORIES AND LOAD CALCS IT IS NOT REFLECTED
 ON THE FLOOR PLANS OF EITHER UNIT.
 2. ALL CEILING LUMINARY OUTLETS SHALL BE LISTED TO
 SUPPORT 50 LBS.
 3. INDICATE THE APPLICABLE SCALE FOR THE DRAWINGS TO BE
 ABLE TO CONFIRM PROPER OUTLET PLACEMENT.
 4. UNIT 2 STAIRWAY IS MISSING THE DUAL CONTROL REQUIRED
 BY NEC 210.70 FOR THE LIGHTING
 5. VERIFY THE LOAD CALCS AS SUBMITTED.
 6. EACH A/C CONDENSING UNIT REQUIRES ITS OWN SERVICE
 GFI RECEPTACLE SERVED FROM ITS RESPECTIVE PANEL.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  