2015-06-23 06:51:05 | BUILDING PLAN REVIEW |
| PERMIT: 14120093 |
| ADD: 809 6TH ST. |
| CONT: MIJO CONSTRUCTION |
| TEL: (561)246-0411 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: MON- TUES. JUNE 22-23/2015 |
| ACTION: DENIED |
| |
| 1) COVER SHEET: |
| 1A) SEMI- COMPLIED. THE COVERSHEET UNDER THE HEADING |
| BUILDING CODE ANALYSIS OCCUPANCY CLASSIFICATION AS A |
| BUSINESS OCCUPANCY, R2 PER CHAPTER 3, SECTION |
| 304.1.THIS WILL CREATE A MIXED USE OCCUPANCY, WHERE IS |
| THE BUSINESS OCCUPANCY? SECTION 304.1 DOES PROVIDE A |
| LIST OF SERVICES THAT ARE BUSINESS OCCUPANCIES WHICH |
| NONE ARE REPRESENTED ON THIS PLAN? |
| |
| THE CODE TABULATION NEEDS TO BE CLARIFIED. THE DESIGNER |
| OF RECORD WILL NEED TO CLARIFY IF THE 1ST FLOOR HAS (5) |
| INDIVIDUAL SLEEPING ROOMS OR THIS IS A SINGLE DWELLING |
| UNIT. PROVIDE A BREAKDOWN OF SLEEPING UNITS AND |
| DWELLING UNITS. 2010 WEST PALM BEACH AMENDMENTS TO THE |
| FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 107. |
| 3.5.1.2 MINIMUM PLAN REVIEW CRITERIA COMMERCIAL |
| BUILDING. |
| |
| |
| 1B) SEMI-COMPLIED. THE COVERSHEET WILL NEED TO PROVIDE |
| IF TRANSIENT OR NON-TRANSIENT, THIS WILL AFFECT IF |
| ACCESSIBILITY BECOMES AN ISSUE. 2010 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION, 107. 3.5.1.2 MINIMUM PLAN REVIEW |
| CRITERIA COMMERCIAL BUILDING. 2010 FBC-B 310.1. |
| |
| 1C) COMPLIED. MINIMUM BUILDING TYPE. |
| |
| 1D)SEMI-COMPLIED. UNKNOWN IF THE 1ST FLOOR IS (5) |
| INDIVIDUAL SLEEPING ROOMS REQUIRING 1 HOUR FIRE |
| SEPARATION BETWEEN THEM OR A SINGLE DWELLING UNIT FOR A |
| FAMILY. |
| |
| 1ST REVIEW COMMENT. THE COVERSHEET ALSO FAILS TO |
| IDENTIFY (DESIGN CRITERIA) 2010 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION, 107. 3.5.1.4 MINIMUM PLAN REVIEW |
| CRITERIA COMMERCIAL BUILDING. |
| .4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL |
| INCLUDE THE FOLLOWING COMPONENTS: |
| FIRE-RESISTANT SEPARATIONS PROVIDE ACTUAL UL LISTINGS |
| OR GYPSUM ASSOC. LISTINGS, VERIFY ICYENE IS PART OF THE |
| RATED FLOOR/ CEILING ASSEMBLY |
| FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION |
| PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS |
| FIRE BLOCKING AND DRAFTSTOPPING AND CALCULATED FIRE |
| RESISTANCE |
| |
| 1E) THE RESPONSE STATEMENT STATES NO FIRE SPRINKLERS |
| REQUIRED. COVERSHEET PROJECT DATA NOTE 2010 FBC-B |
| 907.2.9.1 FIRE SPRINKLERS NOT REQUIRED IN A R-2 |
| DWELLING UNIT LESS THAN 2 STORIES. NOTE 907.2.9.1 DEALS |
| WITH FIRE ALARMS NOT FIRE SPRINKLERS. PLEASE REVIEW |
| 2010 FBC-B 903.2.8 AN AUTOMATIC SPRINKLER SYSTEM |
| INSTALLED IN ACCORDANCE WITH 903.3 SHALL BE PROVIDED |
| THROUGHOUT ALL BUILDINGS WITH A GROUP R FIRE AREA. |
| SEE 2010 FBC-B 903.3.1.2 NFPA 13 R SPRINKLER SYSTEMS. |
| |
| 1ST REVIEW COMMENT. THE COVERSHEET ALSO FAILS TO |
| IDENTIFY (DESIGN CRITERIA) IF THIS OCCUPANCY IS FIRE |
| SPRINKLERED OR NOT? 2010 WEST PALM BEACH AMENDMENTS TO |
| THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, |
| 107. 3.5.1.1 MINIMUM PLAN REVIEW CRITERIA COMMERCIAL |
| BUILDING. |
| .5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: |
| EARLY WARNING SMOKE EVACUATION SYSTEMS |
| SCHEMATIC FIRE SPRINKLERS |
| STANDPIPES |
| PRE-ENGINEERED SYSTEMS |
| RISER DIAGRAM |
| |
| 2) 2ND REQUEST, THE LIFE SAFETY SHEET STILL SHOWS 4 |
| UNITS. SHEETS A1 & A2 FAILS TO IDENTIFY (DESIGN |
| CRITERIA) EGRESS COMPONENTS, 2010 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION, 107. 3.5.1.7 MINIMUM PLAN REVIEW |
| CRITERIA COMMERCIAL BUILDING. |
| . 7. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE |
| IN A LIFE SAFETY PLAN: |
| OCCUPANCY LOAD FOUND ON THE COVERSHEET, THEY NEED TO BE |
| ROUNDED UP TO THE NEXT WHOLE OCCUPANTS. |
| |
| EMERGENCY LIGHTING AND EXIT SIGNS |
| |
| 3) 2ND REQUEST. SHEETS A1 & A2 FAIL TO IDENTIFY 2010 |
| WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION, 107. 3.5.1.8 MINIMUM |
| PLAN REVIEW CRITERIA COMMERCIAL BUILDING. |
| .8. STRUCTURAL REQUIREMENTS SHALL INCLUDE: |
| WIND REQUIREMENTS PROVIDE THE WIND DESIGN CRITERIA, |
| BUILDING ENVELOPE/ PRODUCT APPROVALS |
| |
| STRUCTURAL CALCULATIONS (IF REQUIRED) 2010 EXT. BLDG |
| CODE LEVEL III 807.4. 1 THRU 3. |
| WALL SYSTEMS |
| FLOOR SYSTEMS |
| ROOF SYSTEMS |
| STAIR SYSTEMS & HANDRAILS |
| |
| 4)SEMI ?COMPLIED. DEPENDING IF THE 1ST FLOOR IS |
| TRANSIENT SLEEPING ROOMS THEN ACCESSIBILITY WILL NEED |
| TO BE REVIEWED. |
| SHEETS A1 & A2 FAIL TO IDENTIFY 2010 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION, 107. 3.5.1.10 |
| WHEN THIS STRUCTURE WAS BUILT, IF FAIR HOUSING AND OR |
| FL. ACCESSIBILITY APPLY AND ALL APPLICABLE CODE |
| SECTIONS. |
| |
| 5) SHEETS A1 & A2 FAIL TO IDENTIFY 2010 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION, 107. 3.5.1.11 |
| 11. INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING: |
| INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT) |
| |
| 6) FL. ENERGY CODE: |
| 6A) SEMI- COMPLIED.ENERGY CALCULATIONS FOR UNITS 1 & 2 |
| NONE FOR UNIT 3. |
| |
| 6B)(1) PROVIDE THE MANUFACTURES SPECIFICATIONS AND |
| REPORT FOR THE USE OF ICYENE. SHEET D-1 THE 2 STORY |
| EXTERIOR WALL DETAIL IS MISSING THE FLOOR INSULATION |
| UNDER THE FIRST FLOOR. 2010 FBC-ENERGY CODE 402.4.1, |
| 402.2.6 . |
| |
| 6B)(2) |
| A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. |
| |
| C) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2. |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| |
| TYPE III-TYPE V CONSTRUCTION: |
| 719.2 CONCEALED INSTALLATION. |
| INSULATING MATERIALS, WHERE CONCEALED AS INSTALLED IN |
| BUILDINGS OF ANY TYPE OF CONSTRUCTION, SHALL HAVE A |
| FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A |
| SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450. |
| |
| |
| |
| 6)(3) THE ENERGY CALCULATION TAKES THIS STRUCTURE AS A |
| SLAB ON GRADE, PLEASE CORRECT. 2010 FBC-ENERGY CODE |
| 402.4.1 & 402.2.6. |
| |
| 6C) SHEET D-1 COMMON WALL DETAIL INDICATES CODE |
| COMPLIANCE FOR FL ENERGY CODE 402.2.12.2, PLEASE |
| PROVIDE COMPLIANCE WITH 2010 FBC-B 1207.2 AIR-BORNE |
| SOUND. WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE. |
| |
| 6D) SHEET D-1 TENANT WALL/ FLOOR DETAIL INDICATES THE |
| USE OF 3 INCH ATTEN. BATT R-30 BATT INSULATION, PLEASE |
| PROVIDE COMPLIANCE WITH FBC-B 1207.3 STRUCTURE-BORNE |
| SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| 6E) THE ENERGY CALCULATIONS INDICATE A SHGC OF 0.5 |
| PLEASE PROVIDE DOCUMENTATION, FL ENERGY CODE TABLE |
| 402.1.1 GLAZED FENESTRATION 0.30. |
| |
| 6F) NOTE SHEET A2 DOES NOT SHOW ATTIC ACCESS NOR |
| COMPLIANCE WITH: |
| 2010 FBC-B 1209.2 ATTIC ACCESS. |
| 7) COMPLIED. |
| |
| 8) COMPLIED. SHEET A1 STAIR # 3 ONLY SHOWS ONE SIDE OF |
| THE STAIRWELL WITH A FIRE RATED WALL. FBC-B 1022.1 |
| |
| 9) SHEET A1 STAIR # 3 IS MISSING THE CEILING |
| INFORMATION BELOW THE STAIR AND ENCLOSURES UNDER |
| STAIRWAYS ARE TO COMPLY WITH FBC-B 1009.6.3. |
| |
| 10) SHEET A1 STAIR # 3 ALSO DOES NOT INDICATE FIRE |
| BLOCKING. |
| |
| 11) SHEET D1 DETAIL FOR THE TENANT SEPARATION WALL |
| SHOWS THE HORIZONTAL SEPARATION BETWEEN THE 1ST FLOOR |
| UNITS & 2ND FLOOR UNITS THE EXTERIOR WALL DETAIL SHOWS |
| A 2 LAYERS OF 5/8 TYPE X ON THE CEILING. PROVIDE EITHER |
| A UL LISTING OR GYPSUM ASSOC . LISTING FOR THE FLOOR |
| CEILING ASSEMBLY 2 HOURS WITH THE USE OF ICYENE |
| INSULATION. |
| |
| WHAT BOTH DETAILS FAIL TO PROVIDE IS THROUGH THE |
| CAVITIES IN THE FLOOR TRUSSES HOW THE FIRE PARTITION |
| BETWEEN THE UPSTAIRS UNITS 2 & 3 OCCURS IN THE FLOOR |
| TRUSS, TRUSS SYSTEM. 439.2 SEE SECTION 709.4 |
| CONTINUITY. IF THE PARTITIONS ARE NOT CONTINUOUS TO THE |
| SHEATHING, DECK OR SLAB, AND WHERE CONSTRUCTED OF |
| COMBUSTIBLE CONSTRUCTION, THE SPACE BETWEEN THE CEILING |
| AND THE SHEATHING, DECK OR SLAB ABOVE SHALL BE |
| FIREBLOCKED OR DRAFTSTOPPED IN ACCORDANCE WITH SECTIONS |
| 717.2 AND 717.3 AT THE PARTITION LINE. |
| |
| 12A) SHOW COMPLIANCE WITH 709.4 FIRE PARTITIONS EXTEND |
| FROM THE TOP OF FOUNDATIONS THEN THERE SHOULD BE A |
| SECTION THROUGH THE 1ST FLOOR SHOWING THE STEM WALL & |
| FOOTER UNDER THE TENANT SEPARATION WALL. 2010 FBC-B |
| 709.4. |
| |
| 12B) STEM WALL CONSTRUCTION THEN IN ONE OF THE TENANT |
| SPACES A NEW ACCESS WILL ALSO BE REQUIRED TO THE SPACE |
| BENEATH THE FLOOR SYSTEM.1203.3. |
| |
| 13) SHEET D1 PLEASE PROVIDE CODE COMPLIANCE FOR THE 2ND |
| FLOOR TENANTS HOW THE SPACE ABOVE THE CEILING WILL BE |
| MADE CODE COMPLIANT WITH FBC-B 709.4 OR EXCEPTIONS. |
| |
| 14)COMPLIED. ROOF: FIBERGLASS SHINGLES. |
| |
| 15) SEMI-COMPLIED RESPONSE INDICATES THE ATTIC IS TO BE |
| ENCLOSED AND SPRAYED WITH ICYNENE INSULATION. |
| PLEASE PROVIDE THE PRODUCT APPROVAL ON ICYNENE, WITHIN |
| THE ICC REPORT CIRCLE WHICH SUB-SYSTEM YOU ENTEND ON |
| USING IN ACCORDANCE WITH THE MANUFACTURERS |
| INSTRUCTIONS. PLEASE ALSO SEE 2010 FBC-B 2603.4.1.6 |
| IGNITION BARRIER REQUIREMENT, DIFFERENT FROM THE |
| THERMAL BARRIER REQUIREMENTS. |
| |
| 16) 2ND REQUEST. SHEET D-1 INTERIOR FINISHES, WITH THE |
| DESIGNER NOT LISTING THE OCCUPANCY TYPE R-1 OR R-2 THE |
| COMPLIANCE WITH TABLE 803.9 IS A UNKNOWN, ALSO IF FIRE |
| SPRINKLERED OR NOT. |
| |
| 17) 2ND REQUEST. 2010 EXISTING BUILDING CODE, LEVEL III |
| ALTERATION PLEASE REVIEW 804.1 AUTOMATIC SPRINKLER |
| SYSTEMS. AUTOMATIC SPRINKLER SYSTEMS SHALL BE PROVIDED |
| IN ALL WORK AREAS IN ACCORDANCE WITH THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 2010 FBC-B [F] 903.2.8 GROUP R. AN AUTOMATIC SPRINKLER |
| SYSTEM INSTALLED IN ACCORDANCE WITH SECTION 903.3 SHALL |
| BE PROVIDED THROUGHOUT ALL BUILDINGS WITH A GROUP R |
| FIRE AREA. |
| |
| 2010 FBC-B F] 903.3 INSTALLATION REQUIREMENTS. |
| AUTOMATIC SPRINKLER SYSTEMS SHALL BE DESIGNED AND |
| INSTALLED IN ACCORDANCE WITH SECTIONS 903.3.1 THROUGH |
| 903.3.6. |
| |
| 18) COMPLIED. SHEET A3 PRESSURES FOR WINDOWS AND DOORS. |
| |
| 19) COMPLIED. EGRESS WINDOWS. |
| |
| 20-22) DEFERRED SUBMITTALS. 107.3.4.2 DEFERRED |
| SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, DEFERRED |
| SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN |
| THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION |
| AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL |
| WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL |
| ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING |
| OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS |
| ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE |
| BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED SUBMITTAL |
| ITEMS SHALL BE SUBMITTED TO THE REGISTERED DESIGN |
| PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW |
| THEM AND FORWARD THEM TO THE BUILDING OFFICIAL WITH A |
| NOTATION INDICATING THAT THE DEFERRED SUBMITTAL |
| DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL |
| CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED |
| SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE |
| DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE |
| BUILDING OFFICIAL. |
| |
| 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 |
| COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF |
| PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B) WINDOWS/ MULLIONS |
| (D) ROOFING PRODUCTS AND ASSEMBLIES |
| (E) SHUTTERS |
| |
| 21)COMPLIED. ROOFING EXISTING NOT REPLACING |
| |
| 22) DEFERRED SUBMITTAL. 2010 FBC 107.3.4.1 PRODUCT |
| APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE |
| DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN |
| WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. |
| |
| 23) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |