Plan Review Notes For Permit 14120093 |
Permit Number |
14120093 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-12-31 10:42:36 | PLAN DENIED | | | | 1) SHOW SIZE AND LOCATION OF RETURN AIR | | ON THE PLAN PER SECTION 107 FBC 2010 | | 2) PROVIDE EQUIPMENT SCHEDULE ON PLAN. | | PER SECTION 107 FBC 2010 | | 3) SHOW TERMINATION OF BATHROOM EXHAUST | | PER SECTION 501.2 EXHAUST DISCHARGE. | | 2010 FBC (M) | | 4) REFER TO SECTION 602.2.1 MATERIALS WITHIN | | PLENUM'S NO COMBUSTIBLES IN RETURN | | AIR PLENUM INCLUDING DOOR | | | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 |
|