Plan Review Notes
Plan Review Notes For Permit 14120093
Permit Number 14120093
Review Stop M
Sequence Number 1
Notes
Date Text
2014-12-31 10:42:36PLAN DENIED
  
 1) SHOW SIZE AND LOCATION OF RETURN AIR
 ON THE PLAN PER SECTION 107 FBC 2010
 2) PROVIDE EQUIPMENT SCHEDULE ON PLAN.
 PER SECTION 107 FBC 2010
 3) SHOW TERMINATION OF BATHROOM EXHAUST
 PER SECTION 501.2 EXHAUST DISCHARGE.
 2010 FBC (M)
 4) REFER TO SECTION 602.2.1 MATERIALS WITHIN
 PLENUM'S NO COMBUSTIBLES IN RETURN
 AIR PLENUM INCLUDING DOOR
  