Plan Review Notes
Plan Review Notes For Permit 14120093
Permit Number 14120093
Review Stop E
Sequence Number 1
Notes
Date Text
2014-12-31 16:28:4512/31/2014
 PROJECT: 809
 PERMIT#: 14120093
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE A COMPLETE ELECTRICAL LOAD CALCULATION FOR
 THE FEEDER FOR A MULTI FAMILY DWELLING. THE OVERHEAD
 SERVICE ENTRANCE CONDUCTORS ARE CURRENTLY INDICATED AS
 2/0 AND AS SUCH ARE ONLY RATED A MAXIMUM OF 175AMPS.
 INDICATE SERVICE ENTRANCE CONDUCTORS APPROVED TO
 SUPPORT THE TOTAL CONNECTED LOAD AS DETERMINED BY LOAD
 CALCULATION. NEC 310.16
  
 2) PROVIDE A GROUNDING ELECTRODE CONDUCTOR SIZED IN
 ACCORDANCE WITH NEC 250.66
  
 3) PROVIDE A COMPLETE PANEL DIRECTORY FOR EACH UNIT'S
 ELECTRICAL PANEL. EVERY CIRCUIT AND CIRCUIT
 MODIFICATION SHALL BE LEGIBLY IDENTIFIED AS TO ITS
 CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. NEC 408.4
  
 4) PROVIDE CIRCUIT NUMBERS ON THE FLOOR PLAN IN
 ACCORDANCE WITH THE PANEL SCHEDULES. WPB AMENDMENTS FBC
 107.3.2
  
 5) PROVIDE SWITCHING FOR LIGHTING FROM BOTH LANDINGS
 FOR STAIRWAYS. NEC 210.70
  
 6) INDICATE LOACTION FOR THE ELECTRICAL PANELS IN EACH
 OF THE UNITS. WPB AMENDMENTS FBC 107.3.2
  
 7) PROVIDE A FIRE STOP DETAIL FOR ALL WALL AND FLOOR
 PENETRATIONS OF FIRE RATED ASSEMBLIES. NEC 300.21,
 FBC-R 302.4.2, FBC 713.3.2
  
 8) VERIFY RECEPTACLES SPACING SUCH THAT NO POINT
 MEASURED HORIZONTALLY ALONG THE FLOOR LINE IN ANY WALL
 SPACE IS MORE THAN 1.8 M (6 FT) FROM A RECEPTACLE
 OUTLET. NEC 210.52(A)(1) THROUGH (A)(3).
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  