2014-12-31 16:28:45 | 12/31/2014 |
| PROJECT: 809 |
| PERMIT#: 14120093 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| 1) PROVIDE A COMPLETE ELECTRICAL LOAD CALCULATION FOR |
| THE FEEDER FOR A MULTI FAMILY DWELLING. THE OVERHEAD |
| SERVICE ENTRANCE CONDUCTORS ARE CURRENTLY INDICATED AS |
| 2/0 AND AS SUCH ARE ONLY RATED A MAXIMUM OF 175AMPS. |
| INDICATE SERVICE ENTRANCE CONDUCTORS APPROVED TO |
| SUPPORT THE TOTAL CONNECTED LOAD AS DETERMINED BY LOAD |
| CALCULATION. NEC 310.16 |
| |
| 2) PROVIDE A GROUNDING ELECTRODE CONDUCTOR SIZED IN |
| ACCORDANCE WITH NEC 250.66 |
| |
| 3) PROVIDE A COMPLETE PANEL DIRECTORY FOR EACH UNIT'S |
| ELECTRICAL PANEL. EVERY CIRCUIT AND CIRCUIT |
| MODIFICATION SHALL BE LEGIBLY IDENTIFIED AS TO ITS |
| CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. NEC 408.4 |
| |
| 4) PROVIDE CIRCUIT NUMBERS ON THE FLOOR PLAN IN |
| ACCORDANCE WITH THE PANEL SCHEDULES. WPB AMENDMENTS FBC |
| 107.3.2 |
| |
| 5) PROVIDE SWITCHING FOR LIGHTING FROM BOTH LANDINGS |
| FOR STAIRWAYS. NEC 210.70 |
| |
| 6) INDICATE LOACTION FOR THE ELECTRICAL PANELS IN EACH |
| OF THE UNITS. WPB AMENDMENTS FBC 107.3.2 |
| |
| 7) PROVIDE A FIRE STOP DETAIL FOR ALL WALL AND FLOOR |
| PENETRATIONS OF FIRE RATED ASSEMBLIES. NEC 300.21, |
| FBC-R 302.4.2, FBC 713.3.2 |
| |
| 8) VERIFY RECEPTACLES SPACING SUCH THAT NO POINT |
| MEASURED HORIZONTALLY ALONG THE FLOOR LINE IN ANY WALL |
| SPACE IS MORE THAN 1.8 M (6 FT) FROM A RECEPTACLE |
| OUTLET. NEC 210.52(A)(1) THROUGH (A)(3). |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |
| |