Plan Review Notes For Permit 14120085 |
Permit Number |
14120085 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-01-16 15:35:33 | 2ND REVIEW FBC 2100 | | | | SEE THE FIRST REVIEW COMMENTS; APPLICANT STATES THERE | | ARE NO MECHANICAL IMPROVEMENTS, HOWEVER, THE | | RECONFIGURATION OF SPACE TO PROVIDE A NEW BATHROOM & | | BEDROOM. CALLS FOR AN ADDED DUCT AND MEHANICAL | | VENTILATION. PROVIDE A MECHANICAL PLAN TO DEMONSTRATE | | COMPLIANCE WITH: | | FBC 107 - MINIMUM PLAN REVIEW CRITERIA, SHOW DUCT | | SYSTEM, INCLUDE BALANCED AIR RETURNS. | | FBCR- M1507.1 GENERAL. | | WHERE TOILET ROOMS AND BATHROOMS ARE MECHANICALLY | | VENTILATED, THE VENTILATION EQUIPMENT SHALL BE | | INSTALLED IN ACCORDANCE WITH THIS SECTION. | | M1507.2 RECIRCULATION OF AIR. | | EXHAUST AIR FROM BATHROOMS AND TOILET ROOMS SHALL NOT | | BE RECIRCULATED WITHIN A RESIDENCE OR TO ANOTHER | | DWELLING UNIT AND SHALL BE EXHAUSTED DIRECTLY TO THE | | OUTDOORS. EXHAUST AIR FROM BATHROOMS AND TOILET ROOMS | | SHALL NOT DISCHARGE INTO AN ATTIC, CRAWL SPACE OR OTHER | | AREAS INSIDE THE BUILDING. | | M1507.3 VENTILATION RATE. | | VENTILATION SYSTEMS SHALL BE DESIGNED TO HAVE THE | | CAPACITY TO EXHAUST THE MINIMUM AIR FLOW RATE | | DETERMINED IN ACCORDANCE WITH TABLE M1507.3. | | TABLE M1507.3 | | MINIMUM REQUIRED EXHAUST RATES FOR ONE- AND TWO-FAMILY | | DWELLINGS; BATHROOMS?TOILET ROOMS MECHANICAL EXHAUST | | CAPACITY OF 50 CFM INTERMITTENT OR 20 CFM | | CONTINUOUS. | | | | STEVEN KENNEDY, CBO | | CHIEF PLANS EXAMINER | | (561) 805-6710 | | [email protected] | | | | | | |
|