2015-01-16 15:35:332ND REVIEW FBC 2100
  
 SEE THE FIRST REVIEW COMMENTS; APPLICANT STATES THERE
 ARE NO MECHANICAL IMPROVEMENTS, HOWEVER, THE
 RECONFIGURATION OF SPACE TO PROVIDE A NEW BATHROOM &
 BEDROOM. CALLS FOR AN ADDED DUCT AND MEHANICAL
 VENTILATION. PROVIDE A MECHANICAL PLAN TO DEMONSTRATE
 COMPLIANCE WITH:
 FBC 107 - MINIMUM PLAN REVIEW CRITERIA, SHOW DUCT
 SYSTEM, INCLUDE BALANCED AIR RETURNS.
 FBCR- M1507.1 GENERAL.
 WHERE TOILET ROOMS AND BATHROOMS ARE MECHANICALLY
 VENTILATED, THE VENTILATION EQUIPMENT SHALL BE
 INSTALLED IN ACCORDANCE WITH THIS SECTION.
 M1507.2 RECIRCULATION OF AIR.
 EXHAUST AIR FROM BATHROOMS AND TOILET ROOMS SHALL NOT
 BE RECIRCULATED WITHIN A RESIDENCE OR TO ANOTHER
 DWELLING UNIT AND SHALL BE EXHAUSTED DIRECTLY TO THE
 OUTDOORS. EXHAUST AIR FROM BATHROOMS AND TOILET ROOMS
 SHALL NOT DISCHARGE INTO AN ATTIC, CRAWL SPACE OR OTHER
 AREAS INSIDE THE BUILDING.
 M1507.3 VENTILATION RATE.
 VENTILATION SYSTEMS SHALL BE DESIGNED TO HAVE THE
 CAPACITY TO EXHAUST THE MINIMUM AIR FLOW RATE
 DETERMINED IN ACCORDANCE WITH TABLE M1507.3.
 TABLE M1507.3
 MINIMUM REQUIRED EXHAUST RATES FOR ONE- AND TWO-FAMILY
 DWELLINGS; BATHROOMS?TOILET ROOMS MECHANICAL EXHAUST
 CAPACITY OF 50 CFM INTERMITTENT OR 20 CFM
 CONTINUOUS.
  