2014-12-22 13:50:3212/22/2014
 PROJECT: 401 S. DIXIE STE302
 PERMIT#: 14120085
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.1ST
 ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) 505.2 LIGHTING CONTROLS (MANDATORY). LIGHTING
 SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS REQUIRED IN
 SECTIONS 505.2.1, 505.2.2, 505.2.3 AND 505.2.4.
  
 2) FLOOR BOX SHALL BE APPROVED FOR INSTALLATION IN A
 FIRE RATED FLOORE/CEILING. NEC 110.3(B)
 A.) FBC 713.4.1 FIRE-RESISTANCE-RATED ASSEMBLIES.
 PENETRATIONS OF THE FIRE-RESISTANCE-RATED FLOOR,
 FLOOR/CEILING ASSEMBLY OR THE CEILING MEMBRANE OF A
 ROOF/CEILING ASSEMBLY SHALL COMPLY WITH SECTIONS
 713.4.1.1 THROUGH 713.4.1.4. PENETRATIONS IN HORIZONTAL
 SMOKE BARRIERS SHALL ALSO COMPLY WITH 713.5.
 B.) FBC 713.4.1.1 THROUGH PENETRATIONS. THROUGH
 PENETRATIONS OF FIRE-RESISTANCE-RATED HORIZONTAL
 ASSEMBLIES SHALL COMPLY WITH SECTION 713.4.1.1.1 OR
 713.4.1.1.2.
 C.) FBC 713.4.1.1(3) PENETRATIONS BY LISTED ELECTRICAL
 BOXES OF ANY MATERIAL, PROVIDED SUCH BOXES HAVE BEEN
 TESTED FOR USE IN FIRE-RESISTANCE-RATED ASSEMBLIES AND
 INSTALLED IN ACCORDANCE WITH THE INSTRUCTIONS INCLUDED
 IN THE LISTING.
  
 3) MULTIWIRE CIRCUITS, NOT PERMITTED. INDIVIDUAL
 PARTITIONS OR GROUPS OF INTERCONNECTED INDIVIDUAL
 PARTITIONS SHALL NOT CONTAIN MULTIWIRE CIRCUITS.NEC
 605.8 (D)
 A.) WIRED PARTITIONS THAT ARE FIXED (SECURED TO
 BUILDING SURFACES) SHALL BE PERMANENTLY CONNECTED TO
 THE BUILDING ELECTRICAL SYSTEM BY ONE OF THE WIRING
 METHODS OF CHAPTER 3. MULTIWIRE BRANCH CIRCUITS
 SUPPLYING POWER TO THE PARTITION SHALL BE PROVIDED WITH
 A MEANS TO
 DISCONNECT SIMULTANEOUSLY ALL UNGROUNDED CONDUCTORS AT
 THE PANELBOARD WHERE THE BRANCH CIRCUIT ORIGINATES. NEC
 605.6 FIXED-TYPE PARTITIONS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
 SEE LINK: HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS
 /SITES/33/2013/09/APPLICATION_RESUBMITTAL_FORM_04132010
 .PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,