2014-12-22 13:50:32 | 12/22/2014 |
| PROJECT: 401 S. DIXIE STE302 |
| PERMIT#: 14120085 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS.1ST |
| ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| 1) 505.2 LIGHTING CONTROLS (MANDATORY). LIGHTING |
| SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS REQUIRED IN |
| SECTIONS 505.2.1, 505.2.2, 505.2.3 AND 505.2.4. |
| |
| 2) FLOOR BOX SHALL BE APPROVED FOR INSTALLATION IN A |
| FIRE RATED FLOORE/CEILING. NEC 110.3(B) |
| A.) FBC 713.4.1 FIRE-RESISTANCE-RATED ASSEMBLIES. |
| PENETRATIONS OF THE FIRE-RESISTANCE-RATED FLOOR, |
| FLOOR/CEILING ASSEMBLY OR THE CEILING MEMBRANE OF A |
| ROOF/CEILING ASSEMBLY SHALL COMPLY WITH SECTIONS |
| 713.4.1.1 THROUGH 713.4.1.4. PENETRATIONS IN HORIZONTAL |
| SMOKE BARRIERS SHALL ALSO COMPLY WITH 713.5. |
| B.) FBC 713.4.1.1 THROUGH PENETRATIONS. THROUGH |
| PENETRATIONS OF FIRE-RESISTANCE-RATED HORIZONTAL |
| ASSEMBLIES SHALL COMPLY WITH SECTION 713.4.1.1.1 OR |
| 713.4.1.1.2. |
| C.) FBC 713.4.1.1(3) PENETRATIONS BY LISTED ELECTRICAL |
| BOXES OF ANY MATERIAL, PROVIDED SUCH BOXES HAVE BEEN |
| TESTED FOR USE IN FIRE-RESISTANCE-RATED ASSEMBLIES AND |
| INSTALLED IN ACCORDANCE WITH THE INSTRUCTIONS INCLUDED |
| IN THE LISTING. |
| |
| 3) MULTIWIRE CIRCUITS, NOT PERMITTED. INDIVIDUAL |
| PARTITIONS OR GROUPS OF INTERCONNECTED INDIVIDUAL |
| PARTITIONS SHALL NOT CONTAIN MULTIWIRE CIRCUITS.NEC |
| 605.8 (D) |
| A.) WIRED PARTITIONS THAT ARE FIXED (SECURED TO |
| BUILDING SURFACES) SHALL BE PERMANENTLY CONNECTED TO |
| THE BUILDING ELECTRICAL SYSTEM BY ONE OF THE WIRING |
| METHODS OF CHAPTER 3. MULTIWIRE BRANCH CIRCUITS |
| SUPPLYING POWER TO THE PARTITION SHALL BE PROVIDED WITH |
| A MEANS TO |
| DISCONNECT SIMULTANEOUSLY ALL UNGROUNDED CONDUCTORS AT |
| THE PANELBOARD WHERE THE BRANCH CIRCUIT ORIGINATES. NEC |
| 605.6 FIXED-TYPE PARTITIONS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| SEE LINK: HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS |
| /SITES/33/2013/09/APPLICATION_RESUBMITTAL_FORM_04132010 |
| .PDF |
| |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |