2014-12-05 11:36:53 | BUILDING PLAN REVIEW |
| PERMIT: 14120084 |
| ADD: 401 S. DIXIE HWY. SUITE # 302 |
| CONT: IBIS BUILDING |
| TEL: (561)318-8408 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: FRI. DEC. 05/2014 |
| ACTION: DENIED. |
| |
| 1) SHEET A-1.0 THE DOOR SCHEDULE LIST THE FRONT ENTRY |
| DOORS AS TYPE E, A EXISTING DOOR. THE LIFE SAFETY |
| SHEETS INDICATE THIS TO BE A 1 HOUR FIRE RATED WALL, |
| 2010 FBC-B TABLE 715.4 OPENING PROTECTIVES A 1 HR. FIRE |
| RATED CORRIDORR REQUIRES A 20 MIN. OPENING PROTECTIVE. |
| |
| 2) SHEET A-1.0 THE FLOOR PLANS IDENTIFIES THE WINDOWS |
| WITH A IDENTIFICATION TAG # 1. THE DOOR AND WINDOW |
| SCHEDULE UNDER THE HEADING # 1 IDENTIFIES WINDOW & DOOR |
| SCHEDULE IDENTIFIES THE WINDOWS TYPE AS A B3. SHEET |
| A-2.0 IDENTIFIES THE WINDOW TYPE B3 AS A WOOD FRAMED |
| DOOR WITH TEMPERED GLASS. |
| THE WINDOW TYPE 1 IS NOT IDENTIFIED NOR DOES THE ISSUE |
| OF THE GLAZING BEING A HAZARDOUS LOCATION. SEE 2010 |
| FBC-B 2406.4; |
| |
| 6. GLAZING IN AN INDIVIDUAL FIXED OR OPERABLE PANEL |
| ADJACENT TO A DOOR WHERE THE NEAREST EXPOSED EDGE OF |
| THE GLAZING IS WITHIN A 24-INCH (610 MM) |
| ARC OF EITHER VERTICAL EDGE OF THE DOOR IN A CLOSED |
| POSITION AND WHERE THE BOTTOM EXPOSED EDGE OF THE |
| GLAZING IS LESS THAN 60 INCHES (1524 MM) |
| ABOVE THE WALKING SURFACE. |
| |
| 7. GLAZING IN AN INDIVIDUAL FIXED OR OPERABLE PANEL, |
| OTHER THAN IN THOSE LOCATIONS DESCRIBED IN PRECEDING |
| ITEMS 5 AND 6, WHICH MEETS ALL OF THE |
| FOLLOWING CONDITIONS: |
| 7.1. EXPOSED AREA OF AN INDIVIDUAL PANE GREATER THAN 9 |
| SQUARE FEET (0.84 M2); |
| 7.2. EXPOSED BOTTOM EDGE LESS THAN 18 INCHES (457 MM) |
| ABOVE THE FLOOR; |
| 7.3. EXPOSED TOP EDGE GREATER THAN 36 INCHES (914 MM) |
| ABOVE THE FLOOR; AND |
| 7.4. ONE OR MORE WALKING SURFACE(S) WITHIN 36 INCHES |
| (914 MM) HORIZONTALLY OF THE PLANE OF THE GLAZING. |
| |
| 3) SHEET A-1.0 BREAK ROOM SINK DOES NOT SHOW COMPLIANCE |
| FOR A FRONTAL APPROACH MEETING THE FOLLOWING |
| ACCESSIBILITY ISSUE: |
| 2010 FBC-ACCESSIBILIITY 606; |
| 606.1 GENERAL.. |
| 606.2 CLEAR FLOOR SPACE. |
| 606.3 HEIGHT. |
| 606.4 FAUCETS. |
| 606.5 EXPOSED PIPES AND SURFACES. |
| |
| 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |