Plan Review Notes
Plan Review Notes For Permit 14120084
Permit Number 14120084
Review Stop B
Sequence Number 1
Notes
Date Text
2014-12-05 11:36:53BUILDING PLAN REVIEW
 PERMIT: 14120084
 ADD: 401 S. DIXIE HWY. SUITE # 302
 CONT: IBIS BUILDING
 TEL: (561)318-8408
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. DEC. 05/2014
 ACTION: DENIED.
  
 1) SHEET A-1.0 THE DOOR SCHEDULE LIST THE FRONT ENTRY
 DOORS AS TYPE E, A EXISTING DOOR. THE LIFE SAFETY
 SHEETS INDICATE THIS TO BE A 1 HOUR FIRE RATED WALL,
 2010 FBC-B TABLE 715.4 OPENING PROTECTIVES A 1 HR. FIRE
 RATED CORRIDORR REQUIRES A 20 MIN. OPENING PROTECTIVE.
  
 2) SHEET A-1.0 THE FLOOR PLANS IDENTIFIES THE WINDOWS
 WITH A IDENTIFICATION TAG # 1. THE DOOR AND WINDOW
 SCHEDULE UNDER THE HEADING # 1 IDENTIFIES WINDOW & DOOR
 SCHEDULE IDENTIFIES THE WINDOWS TYPE AS A B3. SHEET
 A-2.0 IDENTIFIES THE WINDOW TYPE B3 AS A WOOD FRAMED
 DOOR WITH TEMPERED GLASS.
 THE WINDOW TYPE 1 IS NOT IDENTIFIED NOR DOES THE ISSUE
 OF THE GLAZING BEING A HAZARDOUS LOCATION. SEE 2010
 FBC-B 2406.4;
  
 6. GLAZING IN AN INDIVIDUAL FIXED OR OPERABLE PANEL
 ADJACENT TO A DOOR WHERE THE NEAREST EXPOSED EDGE OF
 THE GLAZING IS WITHIN A 24-INCH (610 MM)
 ARC OF EITHER VERTICAL EDGE OF THE DOOR IN A CLOSED
 POSITION AND WHERE THE BOTTOM EXPOSED EDGE OF THE
 GLAZING IS LESS THAN 60 INCHES (1524 MM)
 ABOVE THE WALKING SURFACE.
  
 7. GLAZING IN AN INDIVIDUAL FIXED OR OPERABLE PANEL,
 OTHER THAN IN THOSE LOCATIONS DESCRIBED IN PRECEDING
 ITEMS 5 AND 6, WHICH MEETS ALL OF THE
 FOLLOWING CONDITIONS:
 7.1. EXPOSED AREA OF AN INDIVIDUAL PANE GREATER THAN 9
 SQUARE FEET (0.84 M2);
 7.2. EXPOSED BOTTOM EDGE LESS THAN 18 INCHES (457 MM)
 ABOVE THE FLOOR;
 7.3. EXPOSED TOP EDGE GREATER THAN 36 INCHES (914 MM)
 ABOVE THE FLOOR; AND
 7.4. ONE OR MORE WALKING SURFACE(S) WITHIN 36 INCHES
 (914 MM) HORIZONTALLY OF THE PLANE OF THE GLAZING.
  
 3) SHEET A-1.0 BREAK ROOM SINK DOES NOT SHOW COMPLIANCE
 FOR A FRONTAL APPROACH MEETING THE FOLLOWING
 ACCESSIBILITY ISSUE:
 2010 FBC-ACCESSIBILIITY 606;
 606.1 GENERAL..
 606.2 CLEAR FLOOR SPACE.
 606.3 HEIGHT.
 606.4 FAUCETS.
 606.5 EXPOSED PIPES AND SURFACES.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676