Plan Review Notes For Permit 14120083 |
Permit Number |
14120083 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-12-30 16:59:19 | NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW | | COMMENTS. | | CODE: 2010 FBC. | | | | 1- TRANSFER DUCT SIZE ON MASTER BEDROOM DOESN'T COMPLY | | WITH THE BALANCED RETURN AIR SEC. M1602.4 OF 2010 | | FBC-RESIDENTIAL. ALL SUPPLY AIR TO THE MASTER BEDROOM | | (INCLUDING BATHROOM AND CLOSETS) NEEDS TO BE CONSIDERED | | FOR THE SIZE OF THE TRANSFER DUCT. SEE EXCEPTION #3 OF | | SEC M1602.4. REVISE AS REQUIRED TO COMPLY. | | | | 2- THE CORRESPONDING LATENT CAPACITY OF THE EQUIPMENT | | SHALL NOT BE LESS THAN THE CALCULATED LATENT LOAD. SEC. | | 403.6.1.1 OF 2010 FBC-ENERGY CONSERVATION. EQUIPMENT | | FOR SYSTEM 1 ON THE EQUIPMENT SIZING CALCULATIONS | | SUBMITTED DON'T COMPLY WITH THIS SECTION. | | | | 3- EQUIPMENT LISTED ON THE EQUIPMENT SIZING | | CALCULATIONS AND EQUIPMENT LISTED ON A/C PLAN M1 DON'T | | MATCH. REVISE AS REQUIRED TO MATCH. SEC. 103.2.2 OF | | 2010 FBC-ENERGY CONSERVATION. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] |
|