Plan Review Notes
Plan Review Notes For Permit 14120052
Permit Number 14120052
Review Stop B
Sequence Number 2
Notes
Date Text
2014-12-11 16:11:23****PROVISO****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 TARGET SURVEYING JOB #165993
  
 ELEVATION CERTIFICATE PROVIDED SHOWS A GARAGE FLOOR
 ELEVATION OF 6.7', MECHANICAL EQUIPMENT IS AT 6.6'. AS
 THIS IMPROVEMENT CONSTITUTES A SUBSTANTIAL IMPROVEMENT,
 PER CONTRACTOR, FLOOD VENTS WILL BE INSTALLED IN THE
 GARAGE AND THE MECHANICAL EQUIPMENT WILL BE RAISED TO
 7.5'.
  
 A FINISHED CONSTRUCTION ELEVATION CERTIFICATE WILL BE
 REQUIRED PRIOR TO FINAL INSPECTION. INCORPORATE THE
 FOLLOWING CORRECTIONS INTO THE ELEVATION CERTIFICATE:
  
 A1, INCLUDE OWNER'S NAME
  
 A8, FLOOD VENTS ARE TO BE INSTALLED. IF THEY ARE
 ENGINEERED FLOOD VENTS, INCLUDE THE PRODUCT APPROVAL AS
 WELL AS A PHOTOGRAPH OF THE INSTALLED VENTS.
  
 A9, CONFIRM GARAGE SQUARE FOOT AREA AS FLOOD VENTS ARE
 PROPOSED.
  
 B1, INCLUDE COMMUNITY NAME (CITY OF WEST PALM BEACH).
  
 B4, REVISE, SHOULD BE 120229 0020.
  
 COMMENTS SECTION STATES THAT ACCESS IS UNAVAILABLE TO
 THE GARAGE. AN ACCURATE GARAGE SQUARE FOOT AREA IS
 REQUIRED AFTER FLOOD VENTS ARE INSTALLED.
 COMMENTS SECTION, INCLUDE SOURCE OF LATITUDE/LONGITUDE.
 COMMENT SECTION, DESCRIBE MACHINERY IN C2E.
  
 AN ORIGINAL SIGNED AND SEALED ELEVATION CERTIFICATE
 WILL BE REQUIRED (NO DIGITAL SIGNATURE)
  
  
  